Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Archived | 2003-08-01 → 2003-08-31 |
| MCL | Health-based | Archived | 2003-08-01 → 2003-08-31 |
| RPT | Monitoring | Resolved | 2022-09-11 |
| RPT | Monitoring | Resolved | 2022-09-11 |
| RPT | Monitoring | Resolved | 2022-04-11 |
| RPT | Monitoring | Resolved | 2022-04-11 |
| MR | Monitoring | Resolved | 2022-01-01 |
| MR | Monitoring | Resolved | 2022-01-01 |
| MR | Monitoring | Resolved | 2021-01-11 |
| MR | Monitoring | Resolved | 2021-01-11 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 220 µg/L 2.2% of the EPA limit 10000 µg/L
worst single sample: 240 µg/L | 54/82 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 59.4 µg/L 0.6% of the EPA limit 10000 µg/L
worst single sample: 160 µg/L | 25/34 | SYR4 | 2012–2019 |
| Lead | 0.0016 mg/L 11% of the EPA limit 0.0150 mg/L | 23/23 | LCR | 2024 |
| Copper | 58.55 µg/L 4.5% of the EPA limit 1300 µg/L
worst single sample: 63.2 µg/L | 16/17 | SYR4 | 2013–2019 |
| Total Haloacetic Acids (HAA5) | 2.8245 µg/L 4.7% of the EPA limit 60 µg/L
worst single sample: 3 µg/L | 14/16 | SYR4 | 2012–2019 |
| Chloroform | 4.318 µg/L No EPA limit set
worst single sample: 6.32 µg/L | 12/20 | SYR4 | 2012–2019 |
| TTHM | 7.8505 µg/L 9.8% of the EPA limit 80 µg/L
worst single sample: 8.89 µg/L | 12/16 | SYR4 | 2012–2019 |
| Di(2-ethylhexyl) Phthalate | 0.1525 µg/L 2.5% of the EPA limit 6 µg/L
worst single sample: 0.2200 µg/L | 10/29 | SYR4 | 2013–2019 |
| Bromodichloromethane | 2.192 µg/L No EPA limit set
worst single sample: 2.6 µg/L | 9/20 | SYR4 | 2012–2019 |
| Fluoride | 654.8 µg/L 16% of the EPA limit 4000 µg/L
worst single sample: 658 µg/L | 9/16 | SYR4 | 2013–2019 |
| Dibromochloromethane | 1.926 µg/L No EPA limit set
worst single sample: 2.5 µg/L | 8/20 | SYR4 | 2012–2019 |
| Barium | 50 µg/L 2.5% of the EPA limit 2000 µg/L | 7/15 | SYR4 | 2013–2019 |
| Lead | 7.018 µg/L 47% of the EPA limit 15 µg/L
worst single sample: 7.54 µg/L | 7/17 | SYR4 | 2013–2019 |
| Gross Alpha, Excl. Radon And U | 7.1225 pCi/L 47% of the EPA limit 15 pCi/L
worst single sample: 8.9 pCi/L | 6/7 | SYR4 | 2014–2015 |
| Chromium | 0.4957 µg/L 0.5% of the EPA limit 100 µg/L
worst single sample: 0.4960 µg/L | 4/17 | SYR4 | 2013–2019 |
| Nitrite | 2.9 µg/L 0.3% of the EPA limit 1000 µg/L
worst single sample: 3 µg/L | 3/34 | SYR4 | 2012–2019 |
| Lithium | 18.7 µg/L No EPA limit set | 3/5 | UCMR-5 | 2025 |
| Arsenic | 0.4847 µg/L 4.8% of the EPA limit 10 µg/L
worst single sample: 0.4880 µg/L | 2/17 | SYR4 | 2013–2019 |
| Gross Beta Particle Activity | 9.73 pCi/L No EPA limit set
worst single sample: 9.9 pCi/L | 2/2 | SYR4 | 2014 |
| 2,4-D | 0.5200 µg/L 0.7% of the EPA limit 70 µg/L | 1/30 | SYR4 | 2012–2019 |
| Bromoform | 0.4100 µg/L No EPA limit set | 1/20 | SYR4 | 2012–2019 |
| Ethylbenzene | 0.3400 µg/L 0% of the EPA limit 700 µg/L | 1/20 | SYR4 | 2012–2019 |
| Glyphosate | 17.35 µg/L 2.5% of the EPA limit 700 µg/L | 1/29 | SYR4 | 2013–2019 |
| Selenium | 2 µg/L 4% of the EPA limit 50 µg/L | 1/17 | SYR4 | 2013–2019 |
| Thallium, Total | 0.2830 µg/L 14% of the EPA limit 2 µg/L | 1/17 | SYR4 | 2013–2019 |
| Xylenes, Total | 0.2500 µg/L 0% of the EPA limit 10000 µg/L | 1/20 | SYR4 | 2012–2019 |
79 contaminants tested, none detected
Utility contact
Frequently asked questions about Mccall Water System Inc
Is Mccall Water System Inc tap water safe to drink?
EPA monitoring detected 26 contaminants in Mccall Water System Inc's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Mccall Water System Inc's water?
EPA monitoring detected Nitrate, Nitrate-Nitrite, Lead, Copper, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.
How many people does Mccall Water System Inc serve?
Mccall Water System Inc reports serving 8,400 people in Alabama, per its EPA record.
Has Mccall Water System Inc had any water quality violations?
The EPA has 33 violations on file for Mccall Water System Inc, of which 2 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.