← Alaska

Tap water quality report

Ketchikan Public Utilities

EPA monitoring tested this supplier for 71 contaminants and detected 13. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

71
contaminants tested
13
detected
8,937
people served
123
health-based violations
Water source
Surface water
Ownership
Local government
Counties served
Ketchikan Gateway Borough

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

123
health-based violations
178
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2016-10-01 → 2016-12-31
MCL Health-based Resolved 2016-10-01 → 2016-12-31
MCL Health-based Resolved 2016-07-01 → 2016-09-30
MCL Health-based Resolved 2016-07-01 → 2016-09-30
MCL Health-based Resolved 2016-01-01 → 2016-03-31
MCL Health-based Resolved 2016-01-01 → 2016-03-31
MCL Health-based Resolved 2015-10-01 → 2015-12-31
MCL Health-based Resolved 2015-10-01 → 2015-12-31
MCL Health-based Resolved 2015-01-01 → 2015-03-31
MCL Health-based Resolved 2015-01-01 → 2015-03-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Chloroform
83.485 µg/L
No EPA limit set
worst single sample: 114 µg/L
78/78 SYR4 2012–2019
TTHM
87.07 µg/L 109%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 114 µg/L
75/75 SYR4 2012–2019
Dichloroacetic Acid
51.775 µg/L
No EPA limit set
worst single sample: 59.7 µg/L
74/74 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
146.7 µg/L 244%
of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 186 µg/L
74/74 SYR4 2012–2019
Trichloroacetic Acid
92.49 µg/L
No EPA limit set
worst single sample: 124 µg/L
74/74 SYR4 2012–2019
Bromodichloromethane
1.8 µg/L
No EPA limit set
worst single sample: 2.3 µg/L
73/74 SYR4 2012–2019
Copper
298.1 µg/L 23%
of the EPA limit 1300 µg/L
worst single sample: 440 µg/L
60/60 SYR4 2012–2018
Monochloroacetic Acid
5.34 µg/L
No EPA limit set
worst single sample: 8.2 µg/L
53/72 SYR4 2012–2019
Lead
9.335 µg/L 62%
of the EPA limit 15 µg/L
worst single sample: 30.5 µg/L
51/60 SYR4 2012–2018
Lead
0.0025 mg/L 17%
of the EPA limit 0.0150 mg/L
16/16 LCR 2024
Nitrate-Nitrite
114 µg/L 1.1%
of the EPA limit 10000 µg/L
worst single sample: 115 µg/L
3/7 SYR4 2012–2018
Monobromoacetic Acid
3.045 µg/L
No EPA limit set
worst single sample: 3.1 µg/L
2/74 SYR4 2012–2019
Gross Beta Particle Activity
0.4800 pCi/L
No EPA limit set
1/1 SYR4 2016
58 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-Dichloropropane11Cl-PF3OUdS4:2 Fts6:2 Fts8:2 Fts9Cl-PF3ONSAdonaArsenicBenzeneBromoformChlorobenzeneCarbon TetrachlorideCombined Radium (-226 And -228)DichloromethaneDibromoacetic AcidDibromochloromethaneEthylbenzeneHfpo-DaNetfosaaNfdhaNmefosaaNitrateNitritePfbaPFBSPfdaPfdoaPfeesaPfhpaPfhpsPfhxaPFHXSPfmbaPfmpaPFNAPFOAPFOSPfpeaPfpesPftaPftrdaPfunaStyreneTetrachloroethyleneTolueneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneLithiumO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
KLEINEGGER, JOHN
Phone
907-228-2441
Email
[email protected]

Frequently asked questions about Ketchikan Public Utilities

Is Ketchikan Public Utilities tap water safe to drink?

EPA monitoring detected 13 contaminants in Ketchikan Public Utilities's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Ketchikan Public Utilities's water?

EPA monitoring detected Chloroform, TTHM, Dichloroacetic Acid, Total Haloacetic Acids (HAA5), Trichloroacetic Acid, and others. The full list with the level and data source for each is above.

How many people does Ketchikan Public Utilities serve?

Ketchikan Public Utilities reports serving 8,937 people in Alaska, per its EPA record.

Has Ketchikan Public Utilities had any water quality violations?

The EPA has 178 violations on file for Ketchikan Public Utilities, of which 123 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.