What was found in Ripley's water
The level at the city's main supplier, the highest level anywhere in the city, the EPA limit for each, and where every figure comes from.
| Contaminant | Level vs EPA limit | Suppliers | Source |
|---|---|---|---|
| Fluoride | 854.5 µg/L 21% of the EPA limit 4000 µg/L Highest in the city: RIPLEY CITY OF · 5,420 people · 2019 | 1/3 | SYR4 |
| Copper | 605.05 µg/L 47% of the EPA limit 1300 µg/L Main supplier: SOUTHERN JACKSON COUNTY P S D · 6,070 people · 2019
Highest in the city: 802.25 µg/L — SOUTHERN JACKSON COUNTY PSD ROUTE 33 · 170 people · 2019 | 3/3 | SYR4 |
| Nitrate | 300 µg/L 3% of the EPA limit 10000 µg/L Highest in the city: RIPLEY CITY OF · 5,420 people · 2019 | 1/3 | SYR4 |
| Nitrate-Nitrite | 300 µg/L 3% of the EPA limit 10000 µg/L Highest in the city: RIPLEY CITY OF · 5,420 people · 2017 | 1/3 | SYR4 |
| TTHM | 110 µg/L 138% of the EPA limit, at the 95th percentile of samples — 80 µg/L Main supplier: SOUTHERN JACKSON COUNTY P S D · 6,070 people · 2019 | 3/3 | SYR4 |
| Total Haloacetic Acids (HAA5) | 101 µg/L 168% of the EPA limit, at the 95th percentile of samples — 60 µg/L Main supplier: SOUTHERN JACKSON COUNTY P S D · 6,070 people · 2019 | 3/3 | SYR4 |
| Chloroform | 95.7 µg/L No EPA limit set Main supplier: SOUTHERN JACKSON COUNTY P S D · 6,070 people · 2019 | 3/3 | SYR4 |
| Trichloroacetic Acid | 65.42 µg/L No EPA limit set Main supplier: SOUTHERN JACKSON COUNTY P S D · 6,070 people · 2019 | 3/3 | SYR4 |
| Barium | 43.68 µg/L 2.2% of the EPA limit 2000 µg/L Highest in the city: RIPLEY CITY OF · 5,420 people · 2019 | 1/3 | SYR4 |
| Dichloroacetic Acid | 39.94 µg/L No EPA limit set Main supplier: SOUTHERN JACKSON COUNTY P S D · 6,070 people · 2019 | 3/3 | SYR4 |
| Bromodichloromethane | 13.45 µg/L No EPA limit set Main supplier: SOUTHERN JACKSON COUNTY P S D · 6,070 people · 2019
Highest in the city: 14.02 µg/L — SOUTHERN JACKSON COUNTY PSD ROUTE 33 · 170 people · 2019 | 3/3 | SYR4 |
| Monochloroacetic Acid | 7.4925 µg/L No EPA limit set Main supplier: SOUTHERN JACKSON COUNTY P S D · 6,070 people · 2019
Highest in the city: 12.43 µg/L — RIPLEY CITY OF · 5,420 people · 2019 | 3/3 | SYR4 |
| Monobromoacetic Acid | 10.865 µg/L No EPA limit set Main supplier: SOUTHERN JACKSON COUNTY P S D · 6,070 people · 2019 | 3/3 | SYR4 |
| Lead | 4.08 µg/L 27% of the EPA limit 15 µg/L Main supplier: SOUTHERN JACKSON COUNTY P S D · 6,070 people · 2019
Highest in the city: 10.36 µg/L — SOUTHERN JACKSON COUNTY PSD ROUTE 33 · 170 people · 2019 | 3/3 | SYR4 |
| Dibromochloromethane | 1.585 µg/L No EPA limit set Main supplier: SOUTHERN JACKSON COUNTY P S D · 6,070 people · 2019 | 3/3 | SYR4 |
| Dibromoacetic Acid | 1.515 µg/L No EPA limit set Main supplier: SOUTHERN JACKSON COUNTY P S D · 6,070 people · 2019 | 1/3 | SYR4 |
| Bromoform | 0.5830 µg/L No EPA limit set Main supplier: SOUTHERN JACKSON COUNTY P S D · 6,070 people · 2019
Highest in the city: 1.5 µg/L — RIPLEY CITY OF · 5,420 people · 2019 | 2/3 | SYR4 |
| Selenium | 0.2550 µg/L 0.5% of the EPA limit 50 µg/L Highest in the city: RIPLEY CITY OF · 5,420 people · 2019 | 1/3 | SYR4 |
| Lead | 0.0043 mg/L 29% of the EPA limit 0.0150 mg/L Main supplier: SOUTHERN JACKSON COUNTY P S D · 6,070 people · 2025 | 3/3 | LCR |
Water suppliers serving Ripley
| Supplier | Population served |
|---|---|
| SOUTHERN JACKSON COUNTY P S D | 6,070 |
| RIPLEY CITY OF | 5,420 |
| SOUTHERN JACKSON COUNTY PSD ROUTE 33 | 170 |
Frequently asked questions about Ripley tap water
Is Ripley tap water safe to drink?
EPA testing detected 19 contaminants in the water serving Ripley. A detection isn't the same as a violation — most detected levels are within federal limits. Check the level and source for each contaminant above, and your utility's annual Consumer Confidence Report for the official compliance status.
How many water suppliers serve Ripley?
3 public water suppliers report drinking-water monitoring for Ripley, West Virginia to the EPA. Each is listed above with its population served.
What contaminants are in Ripley's water?
The contaminants EPA monitoring detected in Ripley include Fluoride, Copper, Nitrate, Nitrate-Nitrite, TTHM. The full list, with the level at the main supplier and the data source, is in the table above.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.