What was found in Christiana's water
The level at the city's main supplier, the highest level anywhere in the city, the EPA limit for each, and where every figure comes from.
| Contaminant | Level vs EPA limit | Suppliers | Source |
|---|---|---|---|
| Nitrate | 9190 µg/L 92% of the EPA limit 10000 µg/L Main supplier: CHRISTIANA MUNI WATER AUTH · 1,100 people · 2019 | 2/2 | SYR4 |
| Copper | 816.45 µg/L 63% of the EPA limit 1300 µg/L Main supplier: CHRISTIANA MUNI WATER AUTH · 1,100 people · 2019
Highest in the city: 1044.2 µg/L — VILLAS AT GEORGETOWN · 30 people · 2018 | 2/2 | SYR4 |
| Nitrite | 589 µg/L 59% of the EPA limit 1000 µg/L Main supplier: CHRISTIANA MUNI WATER AUTH · 1,100 people · 2019 | 1/2 | SYR4 |
| Fluoride | 230 µg/L 5.8% of the EPA limit 4000 µg/L Highest in the city: VILLAS AT GEORGETOWN · 30 people · 2018 | 1/2 | SYR4 |
| Barium | 191 µg/L 9.6% of the EPA limit 2000 µg/L Main supplier: CHRISTIANA MUNI WATER AUTH · 1,100 people · 2018 | 1/2 | SYR4 |
| Lead | 18.25 µg/L 122% of the EPA limit, at the 95th percentile of samples — 15 µg/L Main supplier: CHRISTIANA MUNI WATER AUTH · 1,100 people · 2019
Highest in the city: 135 µg/L — VILLAS AT GEORGETOWN · 30 people · 2018 | 2/2 | SYR4 |
| TTHM | 72.08 µg/L 90% of the EPA limit 80 µg/L Main supplier: CHRISTIANA MUNI WATER AUTH · 1,100 people · 2019 | 2/2 | SYR4 |
| Chloroform | 60.55 µg/L No EPA limit set Main supplier: CHRISTIANA MUNI WATER AUTH · 1,100 people · 2019 | 1/2 | SYR4 |
| Combined Uranium | 12.5421 µg/L 42% of the EPA limit 30 µg/L Main supplier: CHRISTIANA MUNI WATER AUTH · 1,100 people · 2019 | 2/2 | SYR4 |
| Total Haloacetic Acids (HAA5) | 10.545 µg/L 18% of the EPA limit 60 µg/L Main supplier: CHRISTIANA MUNI WATER AUTH · 1,100 people · 2019 | 2/2 | SYR4 |
| Bromodichloromethane | 10 µg/L No EPA limit set Main supplier: CHRISTIANA MUNI WATER AUTH · 1,100 people · 2019 | 2/2 | SYR4 |
| Dibromochloromethane | 3.64 µg/L No EPA limit set Main supplier: CHRISTIANA MUNI WATER AUTH · 1,100 people · 2019 | 2/2 | SYR4 |
| Dichloroacetic Acid | 1.6375 µg/L No EPA limit set Main supplier: CHRISTIANA MUNI WATER AUTH · 1,100 people · 2019
Highest in the city: 2 µg/L — VILLAS AT GEORGETOWN · 30 people · 2018 | 2/2 | SYR4 |
| Dibromoacetic Acid | 1.52 µg/L No EPA limit set Main supplier: CHRISTIANA MUNI WATER AUTH · 1,100 people · 2019 | 1/2 | SYR4 |
| Chromium | 1 µg/L 1% of the EPA limit 100 µg/L Main supplier: CHRISTIANA MUNI WATER AUTH · 1,100 people · 2018 | 1/2 | SYR4 |
| Toluene | 1 µg/L 0.1% of the EPA limit 1000 µg/L Main supplier: CHRISTIANA MUNI WATER AUTH · 1,100 people · 2019 | 1/2 | SYR4 |
| Bromoform | 0.9500 µg/L No EPA limit set Main supplier: CHRISTIANA MUNI WATER AUTH · 1,100 people · 2019 | 1/2 | SYR4 |
| Antimony, Total | 0.7000 µg/L 12% of the EPA limit 6 µg/L Main supplier: CHRISTIANA MUNI WATER AUTH · 1,100 people · 2018 | 1/2 | SYR4 |
| Atrazine | 0.1000 µg/L 3.3% of the EPA limit 3 µg/L Main supplier: CHRISTIANA MUNI WATER AUTH · 1,100 people · 2019 | 1/2 | SYR4 |
| Lead | 0.0700 mg/L 467% above the EPA limit of 0.0150 mg/L Main supplier: CHRISTIANA MUNI WATER AUTH · 1,100 people · 1996
Highest in the city: 0.0980 mg/L — VILLAS AT GEORGETOWN · 30 people · 2016 | 2/2 | LCR |
Water suppliers serving Christiana
| Supplier | Population served |
|---|---|
| CHRISTIANA MUNI WATER AUTH | 1,100 |
| VILLAS AT GEORGETOWN | 30 |
Frequently asked questions about Christiana tap water
Is Christiana tap water safe to drink?
EPA testing detected 20 contaminants in the water serving Christiana. A detection isn't the same as a violation — most detected levels are within federal limits. Check the level and source for each contaminant above, and your utility's annual Consumer Confidence Report for the official compliance status.
How many water suppliers serve Christiana?
2 public water suppliers report drinking-water monitoring for Christiana, Pennsylvania to the EPA. Each is listed above with its population served.
What contaminants are in Christiana's water?
The contaminants EPA monitoring detected in Christiana include Nitrate, Copper, Nitrite, Fluoride, Barium. The full list, with the level at the main supplier and the data source, is in the table above.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.