What was found in Canfield's water
The level at the city's main supplier, the highest level anywhere in the city, the EPA limit for each, and where every figure comes from.
| Contaminant | Level vs EPA limit | Suppliers | Source |
|---|---|---|---|
| TTHM | 83.95 µg/L 105% of the EPA limit, at the 95th percentile of samples — 80 µg/L Main supplier: CANFIELD CITY PWS · 7,706 people · 2019 | 1/1 | SYR4 |
| Chloroform | 72.29 µg/L No EPA limit set Main supplier: CANFIELD CITY PWS · 7,706 people · 2019 | 1/1 | SYR4 |
| Copper | 69.76 µg/L 5.4% of the EPA limit 1300 µg/L Main supplier: CANFIELD CITY PWS · 7,706 people · 2019 | 1/1 | SYR4 |
| Total Haloacetic Acids (HAA5) | 52 µg/L 87% of the EPA limit 60 µg/L Main supplier: CANFIELD CITY PWS · 7,706 people · 2019 | 1/1 | SYR4 |
| Dichloroacetic Acid | 40.8 µg/L No EPA limit set Main supplier: CANFIELD CITY PWS · 7,706 people · 2019 | 1/1 | SYR4 |
| Lead | 26.91 µg/L 179% of the EPA limit, at the 95th percentile of samples — 15 µg/L Main supplier: CANFIELD CITY PWS · 7,706 people · 2019 | 1/1 | SYR4 |
| Bromodichloromethane | 13.19 µg/L No EPA limit set Main supplier: CANFIELD CITY PWS · 7,706 people · 2019 | 1/1 | SYR4 |
| Trichloroacetic Acid | 8.422 µg/L No EPA limit set Main supplier: CANFIELD CITY PWS · 7,706 people · 2019 | 1/1 | SYR4 |
| Monochloroacetic Acid | 6.99 µg/L No EPA limit set Main supplier: CANFIELD CITY PWS · 7,706 people · 2019 | 1/1 | SYR4 |
| Dibromochloromethane | 3.9405 µg/L No EPA limit set Main supplier: CANFIELD CITY PWS · 7,706 people · 2019 | 1/1 | SYR4 |
| Monobromoacetic Acid | 3.819 µg/L No EPA limit set Main supplier: CANFIELD CITY PWS · 7,706 people · 2019 | 1/1 | SYR4 |
| Dibromoacetic Acid | 1.88 µg/L No EPA limit set Main supplier: CANFIELD CITY PWS · 7,706 people · 2019 | 1/1 | SYR4 |
| PFOS | 0.0124 µg/L No EPA limit set Main supplier: CANFIELD CITY PWS · 7,706 people · 2024 | 1/1 | UCMR-5 |
| Pfba | 0.0056 µg/L No EPA limit set Main supplier: CANFIELD CITY PWS · 7,706 people · 2024 | 1/1 | UCMR-5 |
| PFHXS | 0.0053 µg/L No EPA limit set Main supplier: CANFIELD CITY PWS · 7,706 people · 2024 | 1/1 | UCMR-5 |
| PFOA | 0.0042 µg/L No EPA limit set Main supplier: CANFIELD CITY PWS · 7,706 people · 2024 | 1/1 | UCMR-5 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L Main supplier: CANFIELD CITY PWS · 7,706 people · 2025 | 1/1 | LCR |
Water suppliers serving Canfield
| Supplier | Population served |
|---|---|
| CANFIELD CITY PWS | 7,706 |
Frequently asked questions about Canfield tap water
Is Canfield tap water safe to drink?
EPA testing detected 17 contaminants in the water serving Canfield. A detection isn't the same as a violation — most detected levels are within federal limits. Check the level and source for each contaminant above, and your utility's annual Consumer Confidence Report for the official compliance status.
How many water suppliers serve Canfield?
1 public water supplier report drinking-water monitoring for Canfield, Ohio to the EPA. Each is listed above with its population served.
What contaminants are in Canfield's water?
The contaminants EPA monitoring detected in Canfield include TTHM, Chloroform, Copper, Total Haloacetic Acids (HAA5), Dichloroacetic Acid. The full list, with the level at the main supplier and the data source, is in the table above.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.