← Maine

Tap water quality report

Augusta, ME

EPA monitoring detected 21 contaminants across the 5 water suppliers serving Augusta. A detection doesn't automatically mean the water is unsafe — see the level at the main supplier for each below, with its EPA source and period.

5
water suppliers
13,916
people served
21
contaminants found

What was found in Augusta's water

The level at the city's main supplier, the highest level anywhere in the city, the EPA limit for each, and where every figure comes from.

ContaminantLevel vs EPA limitSuppliersSource
Nitrate
1610 µg/L 16%
of the EPA limit 10000 µg/L
Main supplier: GREATER AUGUSTA UTILITY DISTRICT · 13,750 people · 2019
4/5 SYR4
Nitrate-Nitrite
1132.5 µg/L 11%
of the EPA limit 10000 µg/L
Main supplier: GREATER AUGUSTA UTILITY DISTRICT · 13,750 people · 2018
Highest in the city: 1213 µg/L — SUMMER HAVEN APARTMENTS-BLDG 3 · 25 people · 2019
4/5 SYR4
Fluoride
800 µg/L 20%
of the EPA limit 4000 µg/L
Main supplier: GREATER AUGUSTA UTILITY DISTRICT · 13,750 people · 2019
5/5 SYR4
Copper
430 µg/L 33%
of the EPA limit 1300 µg/L
Main supplier: GREATER AUGUSTA UTILITY DISTRICT · 13,750 people · 2019
Highest in the city: 571.4 µg/L — TOGUS POND MOBILE HOME PARK · 53 people · 2018
5/5 SYR4
Nitrite
40 µg/L 4%
of the EPA limit 1000 µg/L
Highest in the city: DEER RIDGE MOBILE HOME PARK · 33 people · 2018
1/5 SYR4
Lead
4.51 µg/L 30%
of the EPA limit 15 µg/L
Main supplier: GREATER AUGUSTA UTILITY DISTRICT · 13,750 people · 2019
Highest in the city: 35.32 µg/L — SUMMER HAVEN APARTMENTS-BLDG 1 · 55 people · 2019
4/5 SYR4
TTHM
30.04 µg/L 38%
of the EPA limit 80 µg/L
Main supplier: GREATER AUGUSTA UTILITY DISTRICT · 13,750 people · 2019
2/5 SYR4
Barium
19.25 µg/L 1%
of the EPA limit 2000 µg/L
Main supplier: GREATER AUGUSTA UTILITY DISTRICT · 13,750 people · 2018
5/5 SYR4
Gross Alpha, Excl. Radon And U
18.985 pCi/L 127%
of the EPA limit, at the 95th percentile of samples — 15 pCi/L
Highest in the city: DEER RIDGE MOBILE HOME PARK · 33 people · 2017
2/5 SYR4
Chloroform
16.6 µg/L
No EPA limit set
Main supplier: GREATER AUGUSTA UTILITY DISTRICT · 13,750 people · 2019
1/5 SYR4
Combined Uranium
3.18 µg/L 11%
of the EPA limit 30 µg/L
Main supplier: GREATER AUGUSTA UTILITY DISTRICT · 13,750 people · 2017
Highest in the city: 12.855 µg/L — DEER RIDGE MOBILE HOME PARK · 33 people · 2018
3/5 SYR4
Total Haloacetic Acids (HAA5)
5.48 µg/L 9.1%
of the EPA limit 60 µg/L
Main supplier: GREATER AUGUSTA UTILITY DISTRICT · 13,750 people · 2019
Highest in the city: 9.9 µg/L — DEER RIDGE MOBILE HOME PARK · 33 people · 2019
2/5 SYR4
Bromodichloromethane
9.4 µg/L
No EPA limit set
Main supplier: GREATER AUGUSTA UTILITY DISTRICT · 13,750 people · 2019
1/5 SYR4
Combined Radium (-226 And -228)
1.033 pCi/L 21%
of the EPA limit 5 pCi/L
Main supplier: GREATER AUGUSTA UTILITY DISTRICT · 13,750 people · 2015
Highest in the city: 5.4795 pCi/L — DEER RIDGE MOBILE HOME PARK · 33 people · 2019
2/5 SYR4
Dibromochloromethane
5.44 µg/L
No EPA limit set
Main supplier: GREATER AUGUSTA UTILITY DISTRICT · 13,750 people · 2019
1/5 SYR4
Arsenic
4.55 µg/L 45%
of the EPA limit 10 µg/L
Main supplier: GREATER AUGUSTA UTILITY DISTRICT · 13,750 people · 2018
5/5 SYR4
Chromium
3.3 µg/L 3.3%
of the EPA limit 100 µg/L
Main supplier: GREATER AUGUSTA UTILITY DISTRICT · 13,750 people · 2018
5/5 SYR4
Dichloroacetic Acid
3.11 µg/L
No EPA limit set
Main supplier: GREATER AUGUSTA UTILITY DISTRICT · 13,750 people · 2019
1/5 SYR4
Trichloroacetic Acid
2.385 µg/L
No EPA limit set
Main supplier: GREATER AUGUSTA UTILITY DISTRICT · 13,750 people · 2019
1/5 SYR4
Styrene
0.6000 µg/L 0.6%
of the EPA limit 100 µg/L
Highest in the city: SUMMER HAVEN APARTMENTS-BLDG 1 · 55 people · 2019
1/5 SYR4
Lead
0.0011 mg/L 7.3%
of the EPA limit 0.0150 mg/L
Main supplier: GREATER AUGUSTA UTILITY DISTRICT · 13,750 people · 2025
Highest in the city: 0.0056 mg/L — SUMMER HAVEN APARTMENTS-BLDG 3 · 25 people · 2023
5/5 LCR
Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of the system's samples — over 100% is worth reading, but is not by itself a violation. Formal violations are listed separately. These are the utilities' own EPA-reported results, not a city-wide average. A detection means the lab measured the substance — it isn't the same as exceeding a legal limit. Hover a source tag to see the EPA program and years behind each figure.

Water suppliers serving Augusta

Frequently asked questions about Augusta tap water

Is Augusta tap water safe to drink?

EPA testing detected 21 contaminants in the water serving Augusta. A detection isn't the same as a violation — most detected levels are within federal limits. Check the level and source for each contaminant above, and your utility's annual Consumer Confidence Report for the official compliance status.

How many water suppliers serve Augusta?

5 public water suppliers report drinking-water monitoring for Augusta, Maine to the EPA. Each is listed above with its population served.

What contaminants are in Augusta's water?

The contaminants EPA monitoring detected in Augusta include Nitrate, Nitrate-Nitrite, Fluoride, Copper, Nitrite. The full list, with the level at the main supplier and the data source, is in the table above.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.