What was found in Cynthiana's water
The level at the city's main supplier, the highest level anywhere in the city, the EPA limit for each, and where every figure comes from.
| Contaminant | Level vs EPA limit | Suppliers | Source |
|---|---|---|---|
| Nitrate | 2840 µg/L 28% of the EPA limit 10000 µg/L Highest in the city: CYNTHIANA MUNICIPAL WATER WORKS · 7,263 people · 2019 | 1/2 | SYR4 |
| Nitrate-Nitrite | 1600 µg/L 16% of the EPA limit 10000 µg/L Highest in the city: CYNTHIANA MUNICIPAL WATER WORKS · 7,263 people · 2014 | 1/2 | SYR4 |
| Fluoride | 1300 µg/L 33% of the EPA limit 4000 µg/L Highest in the city: CYNTHIANA MUNICIPAL WATER WORKS · 7,263 people · 2019 | 1/2 | SYR4 |
| Chlorite | 840 µg/L 84% of the EPA limit 1000 µg/L Highest in the city: CYNTHIANA MUNICIPAL WATER WORKS · 7,263 people · 2019 | 1/2 | SYR4 |
| Copper | 307.5 µg/L 24% of the EPA limit 1300 µg/L Main supplier: HARRISON CO WATER ASSOCIATION · 16,736 people · 2018 | 2/2 | SYR4 |
| Lead | 13.2 µg/L 88% of the EPA limit 15 µg/L Main supplier: HARRISON CO WATER ASSOCIATION · 16,736 people · 2018
Highest in the city: 113.9 µg/L — CYNTHIANA MUNICIPAL WATER WORKS · 7,263 people · 2019 | 2/2 | SYR4 |
| TTHM | 103 µg/L 129% of the EPA limit, at the 95th percentile of samples — 80 µg/L Main supplier: HARRISON CO WATER ASSOCIATION · 16,736 people · 2019 | 2/2 | SYR4 |
| Total Haloacetic Acids (HAA5) | 54.9 µg/L 91% of the EPA limit 60 µg/L Main supplier: HARRISON CO WATER ASSOCIATION · 16,736 people · 2019
Highest in the city: 55 µg/L — CYNTHIANA MUNICIPAL WATER WORKS · 7,263 people · 2019 | 2/2 | SYR4 |
| Barium | 32.6 µg/L 1.6% of the EPA limit 2000 µg/L Highest in the city: CYNTHIANA MUNICIPAL WATER WORKS · 7,263 people · 2019 | 1/2 | SYR4 |
| Chromium | 10 µg/L 10% of the EPA limit 100 µg/L Highest in the city: CYNTHIANA MUNICIPAL WATER WORKS · 7,263 people · 2019 | 1/2 | SYR4 |
| Selenium | 3 µg/L 6% of the EPA limit 50 µg/L Highest in the city: CYNTHIANA MUNICIPAL WATER WORKS · 7,263 people · 2019 | 1/2 | SYR4 |
| Chlorobenzene | 0.5800 µg/L 0.6% of the EPA limit 100 µg/L Highest in the city: CYNTHIANA MUNICIPAL WATER WORKS · 7,263 people · 2019 | 1/2 | SYR4 |
| Atrazine | 0.2825 µg/L 9.4% of the EPA limit 3 µg/L Highest in the city: CYNTHIANA MUNICIPAL WATER WORKS · 7,263 people · 2019 | 1/2 | SYR4 |
| PFOS | 0.0479 µg/L No EPA limit set Main supplier: HARRISON CO WATER ASSOCIATION · 16,736 people · 2024 | 2/2 | UCMR-5 |
| PFHXS | 0.0153 µg/L No EPA limit set Main supplier: HARRISON CO WATER ASSOCIATION · 16,736 people · 2024 | 2/2 | UCMR-5 |
| Pfpea | 0.0134 µg/L No EPA limit set Main supplier: HARRISON CO WATER ASSOCIATION · 16,736 people · 2024 | 2/2 | UCMR-5 |
| Pfhxa | 0.0089 µg/L No EPA limit set Main supplier: HARRISON CO WATER ASSOCIATION · 16,736 people · 2024 | 2/2 | UCMR-5 |
| Pfba | 0.0079 µg/L No EPA limit set Main supplier: HARRISON CO WATER ASSOCIATION · 16,736 people · 2024 | 1/2 | UCMR-5 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L Main supplier: HARRISON CO WATER ASSOCIATION · 16,736 people · 2021
Highest in the city: 0.0050 mg/L — CYNTHIANA MUNICIPAL WATER WORKS · 7,263 people · 2024 | 2/2 | LCR |
| Pfhpa | 0.0047 µg/L No EPA limit set Main supplier: HARRISON CO WATER ASSOCIATION · 16,736 people · 2024 | 2/2 | UCMR-5 |
| PFBS | 0.0042 µg/L No EPA limit set Main supplier: HARRISON CO WATER ASSOCIATION · 16,736 people · 2024 | 1/2 | UCMR-5 |
Water suppliers serving Cynthiana
| Supplier | Population served |
|---|---|
| HARRISON CO WATER ASSOCIATION | 16,736 |
| CYNTHIANA MUNICIPAL WATER WORKS | 7,263 |
Frequently asked questions about Cynthiana tap water
Is Cynthiana tap water safe to drink?
EPA testing detected 21 contaminants in the water serving Cynthiana. A detection isn't the same as a violation — most detected levels are within federal limits. Check the level and source for each contaminant above, and your utility's annual Consumer Confidence Report for the official compliance status.
How many water suppliers serve Cynthiana?
2 public water suppliers report drinking-water monitoring for Cynthiana, Kentucky to the EPA. Each is listed above with its population served.
What contaminants are in Cynthiana's water?
The contaminants EPA monitoring detected in Cynthiana include Nitrate, Nitrate-Nitrite, Fluoride, Chlorite, Copper. The full list, with the level at the main supplier and the data source, is in the table above.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.