What was found in Elizabethtown's water
The level at the city's main supplier, the highest level anywhere in the city, the EPA limit for each, and where every figure comes from.
| Contaminant | Level vs EPA limit | Suppliers | Source |
|---|---|---|---|
| Nitrate | 3100 µg/L 31% of the EPA limit 10000 µg/L Main supplier: HARDIN COUNTY WATER DISTRICT #2 · 76,326 people · 2019 | 1/1 | SYR4 |
| Fluoride | 1200 µg/L 30% of the EPA limit 4000 µg/L Main supplier: HARDIN COUNTY WATER DISTRICT #2 · 76,326 people · 2019 | 1/1 | SYR4 |
| Copper | 172 µg/L 13% of the EPA limit 1300 µg/L Main supplier: HARDIN COUNTY WATER DISTRICT #2 · 76,326 people · 2019 | 1/1 | SYR4 |
| TTHM | 82.65 µg/L 103% of the EPA limit, at the 95th percentile of samples — 80 µg/L Main supplier: HARDIN COUNTY WATER DISTRICT #2 · 76,326 people · 2019 | 1/1 | SYR4 |
| Total Haloacetic Acids (HAA5) | 75.65 µg/L 126% of the EPA limit, at the 95th percentile of samples — 60 µg/L Main supplier: HARDIN COUNTY WATER DISTRICT #2 · 76,326 people · 2019 | 1/1 | SYR4 |
| Barium | 51.1 µg/L 2.6% of the EPA limit 2000 µg/L Main supplier: HARDIN COUNTY WATER DISTRICT #2 · 76,326 people · 2019 | 1/1 | SYR4 |
| Cyanide | 30 µg/L 15% of the EPA limit 200 µg/L Main supplier: HARDIN COUNTY WATER DISTRICT #2 · 76,326 people · 2019 | 1/1 | SYR4 |
| Lead | 8 µg/L 53% of the EPA limit 15 µg/L Main supplier: HARDIN COUNTY WATER DISTRICT #2 · 76,326 people · 2018 | 1/1 | SYR4 |
| Selenium | 1.7 µg/L 3.4% of the EPA limit 50 µg/L Main supplier: HARDIN COUNTY WATER DISTRICT #2 · 76,326 people · 2019 | 1/1 | SYR4 |
| Thallium, Total | 1 µg/L 50% of the EPA limit 2 µg/L Main supplier: HARDIN COUNTY WATER DISTRICT #2 · 76,326 people · 2019 | 1/1 | SYR4 |
| Arsenic | 0.3000 µg/L 3% of the EPA limit 10 µg/L Main supplier: HARDIN COUNTY WATER DISTRICT #2 · 76,326 people · 2019 | 1/1 | SYR4 |
| Mercury | 0.3000 µg/L 15% of the EPA limit 2 µg/L Main supplier: HARDIN COUNTY WATER DISTRICT #2 · 76,326 people · 2019 | 1/1 | SYR4 |
| 2,4-D | 0.2000 µg/L 0.3% of the EPA limit 70 µg/L Main supplier: HARDIN COUNTY WATER DISTRICT #2 · 76,326 people · 2017 | 1/1 | SYR4 |
| Pfpea | 0.0074 µg/L No EPA limit set Main supplier: HARDIN COUNTY WATER DISTRICT #2 · 76,326 people · 2025 | 1/1 | UCMR-5 |
| PFOA | 0.0062 µg/L No EPA limit set Main supplier: HARDIN COUNTY WATER DISTRICT #2 · 76,326 people · 2025 | 1/1 | UCMR-5 |
| Lead | 0.0060 mg/L 40% of the EPA limit 0.0150 mg/L Main supplier: HARDIN COUNTY WATER DISTRICT #2 · 76,326 people · 2024 | 1/1 | LCR |
| Pfhxa | 0.0053 µg/L No EPA limit set Main supplier: HARDIN COUNTY WATER DISTRICT #2 · 76,326 people · 2025 | 1/1 | UCMR-5 |
| PFOS | 0.0053 µg/L No EPA limit set Main supplier: HARDIN COUNTY WATER DISTRICT #2 · 76,326 people · 2025 | 1/1 | UCMR-5 |
| Pfba | 0.0052 µg/L No EPA limit set Main supplier: HARDIN COUNTY WATER DISTRICT #2 · 76,326 people · 2025 | 1/1 | UCMR-5 |
| PFBS | 0.0052 µg/L No EPA limit set Main supplier: HARDIN COUNTY WATER DISTRICT #2 · 76,326 people · 2025 | 1/1 | UCMR-5 |
| PFNA | 0.0047 µg/L No EPA limit set Main supplier: HARDIN COUNTY WATER DISTRICT #2 · 76,326 people · 2025 | 1/1 | UCMR-5 |
Water suppliers serving Elizabethtown
| Supplier | Population served |
|---|---|
| HARDIN COUNTY WATER DISTRICT #2 | 76,326 |
Frequently asked questions about Elizabethtown tap water
Is Elizabethtown tap water safe to drink?
EPA testing detected 21 contaminants in the water serving Elizabethtown. A detection isn't the same as a violation — most detected levels are within federal limits. Check the level and source for each contaminant above, and your utility's annual Consumer Confidence Report for the official compliance status.
How many water suppliers serve Elizabethtown?
1 public water supplier report drinking-water monitoring for Elizabethtown, Kentucky to the EPA. Each is listed above with its population served.
What contaminants are in Elizabethtown's water?
The contaminants EPA monitoring detected in Elizabethtown include Nitrate, Fluoride, Copper, TTHM, Total Haloacetic Acids (HAA5). The full list, with the level at the main supplier and the data source, is in the table above.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.