EPA monitoring across the 3 water suppliers serving ZIP 32163 in The Villages, FL detected 12 contaminants. A detection doesn't automatically mean the water is unsafe — see the level at the main supplier below, with the EPA limit for each.

3
water suppliers
47,891
people served
12
contaminants found

What was found in ZIP 32163

The level at this ZIP's main supplier, the highest level anywhere in it, the EPA limit for each, and where the figure comes from.

ContaminantLevel vs EPA limitSuppliersSource
Nitrate
730 µg/L 7.3%
of the EPA limit 10000 µg/L
Main supplier: SOUTH SUMTER UTILITIES · 24,278 people · 2019
Highest in the ZIP: 1560 µg/L — CSU WTP NO. 1 · 19,699 people · 2019
2/3 SYR4
Fluoride
420 µg/L 11%
of the EPA limit 4000 µg/L
Main supplier: SOUTH SUMTER UTILITIES · 24,278 people · 2019
2/3 SYR4
TTHM
40.051 µg/L 50%
of the EPA limit 80 µg/L
Main supplier: SOUTH SUMTER UTILITIES · 24,278 people · 2019
3/3 SYR4
Total Haloacetic Acids (HAA5)
29.934 µg/L 50%
of the EPA limit 60 µg/L
Main supplier: SOUTH SUMTER UTILITIES · 24,278 people · 2019
3/3 SYR4
Copper
25 µg/L 1.9%
of the EPA limit 1300 µg/L
Main supplier: SOUTH SUMTER UTILITIES · 24,278 people · 2019
2/3 SYR4
Barium
9.965 µg/L 0.5%
of the EPA limit 2000 µg/L
Main supplier: SOUTH SUMTER UTILITIES · 24,278 people · 2019
Highest in the ZIP: 10.97 µg/L — CSU WTP NO. 1 · 19,699 people · 2017
2/3 SYR4
Chromium
3.755 µg/L 3.8%
of the EPA limit 100 µg/L
Highest in the ZIP: CSU WTP NO. 1 · 19,699 people · 2017
1/3 SYR4
Di(2-ethylhexyl) Phthalate
2.82 µg/L 47%
of the EPA limit 6 µg/L
Highest in the ZIP: CSU WTP NO. 1 · 19,699 people · 2019
1/3 SYR4
Selenium
2.7 µg/L 5.4%
of the EPA limit 50 µg/L
Highest in the ZIP: CSU WTP NO. 1 · 19,699 people · 2017
1/3 SYR4
Arsenic
1.1 µg/L 11%
of the EPA limit 10 µg/L
Highest in the ZIP: CSU WTP NO. 1 · 19,699 people · 2017
1/3 SYR4
PFHXS
0.0064 µg/L
No EPA limit set
Highest in the ZIP: VILLAGE OF PINE RIDGE (CONSEC) · 3,914 people · 2023
1/3 UCMR-5
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
Main supplier: SOUTH SUMTER UTILITIES · 24,278 people · 2023
Highest in the ZIP: 0.0015 mg/L — CSU WTP NO. 1 · 19,699 people · 2023
3/3 LCR
Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of the system's samples — over 100% is worth reading, but is not by itself a violation. Formal violations are listed separately.

Water suppliers serving ZIP 32163

SupplierStatePopulation served
SOUTH SUMTER UTILITIES FL 24,278
CSU WTP NO. 1 FL 19,699
VILLAGE OF PINE RIDGE (CONSEC) FL 3,914

Frequently asked questions about ZIP 32163 tap water

Is the tap water in ZIP 32163 safe to drink?

EPA testing detected 12 contaminants across the water suppliers serving ZIP 32163. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and your utility's annual Consumer Confidence Report for the official status.

Which water suppliers serve ZIP 32163?

3 public water suppliers report EPA drinking-water monitoring for ZIP 32163. Each is listed above with its population served.

What contaminants are in ZIP 32163's water?

EPA monitoring detected Nitrate, Fluoride, TTHM, Total Haloacetic Acids (HAA5), Copper, and others across this ZIP's suppliers. The full list with levels and sources is above.