← Yardley, PA

Tap water quality report

ZIP 19067 — Yardley, PA

EPA monitoring across the 3 water suppliers serving ZIP 19067 in Yardley, PA detected 29 contaminants. A detection doesn't automatically mean the water is unsafe — see the level at the main supplier below, with the EPA limit for each.

3
water suppliers
70,913
people served
29
contaminants found

What was found in ZIP 19067

The level at this ZIP's main supplier, the highest level anywhere in it, the EPA limit for each, and where the figure comes from.

ContaminantLevel vs EPA limitSuppliersSource
Nitrate
3650 µg/L 37%
of the EPA limit 10000 µg/L
Main supplier: PA AMERICAN WATER CO YARDLEY · 33,171 people · 2019
2/3 SYR4
Barium
500 µg/L 25%
of the EPA limit 2000 µg/L
Main supplier: PA AMERICAN WATER CO YARDLEY · 33,171 people · 2019
2/3 SYR4
Copper
127.5 µg/L 9.8%
of the EPA limit 1300 µg/L
Main supplier: PA AMERICAN WATER CO YARDLEY · 33,171 people · 2019
Highest in the ZIP: 286.65 µg/L — MORRISVILLE MUNIC AUTHORITY · 13,342 people · 2019
3/3 SYR4
Chloroform
74.48 µg/L
No EPA limit set
Main supplier: PA AMERICAN WATER CO YARDLEY · 33,171 people · 2019
Highest in the ZIP: 142.58 µg/L — MORRISVILLE MUNIC AUTHORITY · 13,342 people · 2019
3/3 SYR4
TTHM
85 µg/L 106%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
Main supplier: PA AMERICAN WATER CO YARDLEY · 33,171 people · 2019
Highest in the ZIP: 127.775 µg/L — MORRISVILLE MUNIC AUTHORITY · 13,342 people · 2019
3/3 SYR4
Trichloroacetic Acid
40.95 µg/L
No EPA limit set
Main supplier: PA AMERICAN WATER CO YARDLEY · 33,171 people · 2019
Highest in the ZIP: 118.9 µg/L — MORRISVILLE MUNIC AUTHORITY · 13,342 people · 2019
3/3 SYR4
Total Haloacetic Acids (HAA5)
64.08 µg/L 107%
of the EPA limit, at the 95th percentile of samples — 60 µg/L
Main supplier: PA AMERICAN WATER CO YARDLEY · 33,171 people · 2019
Highest in the ZIP: 112.77 µg/L — MORRISVILLE MUNIC AUTHORITY · 13,342 people · 2019
3/3 SYR4
Dichloroacetic Acid
24.85 µg/L
No EPA limit set
Main supplier: PA AMERICAN WATER CO YARDLEY · 33,171 people · 2019
Highest in the ZIP: 91.2 µg/L — MORRISVILLE MUNIC AUTHORITY · 13,342 people · 2019
3/3 SYR4
Bromodichloromethane
11.59 µg/L
No EPA limit set
Main supplier: PA AMERICAN WATER CO YARDLEY · 33,171 people · 2019
Highest in the ZIP: 17.7 µg/L — FALLS TWP WATER & SEWER DEPT · 24,400 people · 2019
3/3 SYR4
Lead
12.6 µg/L 84%
of the EPA limit 15 µg/L
Main supplier: PA AMERICAN WATER CO YARDLEY · 33,171 people · 2019
Highest in the ZIP: 14.6 µg/L — MORRISVILLE MUNIC AUTHORITY · 13,342 people · 2019
3/3 SYR4
Monochloroacetic Acid
2.98 µg/L
No EPA limit set
Main supplier: PA AMERICAN WATER CO YARDLEY · 33,171 people · 2019
Highest in the ZIP: 6.445 µg/L — MORRISVILLE MUNIC AUTHORITY · 13,342 people · 2019
3/3 SYR4
Dibromochloromethane
2.1 µg/L
No EPA limit set
Main supplier: PA AMERICAN WATER CO YARDLEY · 33,171 people · 2019
Highest in the ZIP: 4.84 µg/L — FALLS TWP WATER & SEWER DEPT · 24,400 people · 2019
3/3 SYR4
Combined Uranium
4.75534 µg/L 16%
of the EPA limit 30 µg/L
Main supplier: PA AMERICAN WATER CO YARDLEY · 33,171 people · 2017
2/3 SYR4
Arsenic
2 µg/L 20%
of the EPA limit 10 µg/L
Main supplier: PA AMERICAN WATER CO YARDLEY · 33,171 people · 2019
2/3 SYR4
Chromium
1.4 µg/L 1.4%
of the EPA limit 100 µg/L
Highest in the ZIP: MORRISVILLE MUNIC AUTHORITY · 13,342 people · 2019
1/3 SYR4
Monobromoacetic Acid
1.39 µg/L
No EPA limit set
Highest in the ZIP: FALLS TWP WATER & SEWER DEPT · 24,400 people · 2019
2/3 SYR4
Dibromoacetic Acid
1.265 µg/L
No EPA limit set
Highest in the ZIP: FALLS TWP WATER & SEWER DEPT · 24,400 people · 2019
2/3 SYR4
Bromoform
0.7850 µg/L
No EPA limit set
Main supplier: PA AMERICAN WATER CO YARDLEY · 33,171 people · 2019
2/3 SYR4
Selenium
0.6380 µg/L 1.3%
of the EPA limit 50 µg/L
Highest in the ZIP: MORRISVILLE MUNIC AUTHORITY · 13,342 people · 2019
1/3 SYR4
Hexachlorocyclopentadiene
0.1000 µg/L 0.2%
of the EPA limit 50 µg/L
Main supplier: PA AMERICAN WATER CO YARDLEY · 33,171 people · 2019
1/3 SYR4
Mercury
0.0680 µg/L 3.4%
of the EPA limit 2 µg/L
Highest in the ZIP: MORRISVILLE MUNIC AUTHORITY · 13,342 people · 2019
1/3 SYR4
PFOA
0.0097 µg/L
No EPA limit set
Main supplier: PA AMERICAN WATER CO YARDLEY · 33,171 people · 2024
1/3 UCMR-5
PFOS
0.0061 µg/L
No EPA limit set
Main supplier: PA AMERICAN WATER CO YARDLEY · 33,171 people · 2024
1/3 UCMR-5
Pfba
0.0054 µg/L
No EPA limit set
Main supplier: PA AMERICAN WATER CO YARDLEY · 33,171 people · 2024
1/3 UCMR-5
Pfpea
0.0051 µg/L
No EPA limit set
Main supplier: PA AMERICAN WATER CO YARDLEY · 33,171 people · 2024
3/3 UCMR-5
PFBS
0.0048 µg/L
No EPA limit set
Main supplier: PA AMERICAN WATER CO YARDLEY · 33,171 people · 2024
1/3 UCMR-5
Pfhxa
0.0048 µg/L
No EPA limit set
Main supplier: PA AMERICAN WATER CO YARDLEY · 33,171 people · 2024
2/3 UCMR-5
Pfhpa
0.0030 µg/L
No EPA limit set
Main supplier: PA AMERICAN WATER CO YARDLEY · 33,171 people · 2024
1/3 UCMR-5
Lead
0.0010 mg/L 6.7%
of the EPA limit 0.0150 mg/L
Main supplier: PA AMERICAN WATER CO YARDLEY · 33,171 people · 2025
Highest in the ZIP: 0.0016 mg/L — FALLS TWP WATER & SEWER DEPT · 24,400 people · 2025
3/3 LCR
Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of the system's samples — over 100% is worth reading, but is not by itself a violation. Formal violations are listed separately.

Water suppliers serving ZIP 19067

SupplierStatePopulation served
PA AMERICAN WATER CO YARDLEY PA 33,171
FALLS TWP WATER & SEWER DEPT PA 24,400
MORRISVILLE MUNIC AUTHORITY PA 13,342

Frequently asked questions about ZIP 19067 tap water

Is the tap water in ZIP 19067 safe to drink?

EPA testing detected 29 contaminants across the water suppliers serving ZIP 19067. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and your utility's annual Consumer Confidence Report for the official status.

Which water suppliers serve ZIP 19067?

3 public water suppliers report EPA drinking-water monitoring for ZIP 19067. Each is listed above with its population served.

What contaminants are in ZIP 19067's water?

EPA monitoring detected Nitrate, Barium, Copper, Chloroform, TTHM, and others across this ZIP's suppliers. The full list with levels and sources is above.