What was found in ZIP 08808
The level at this ZIP's main supplier, the highest level anywhere in it, the EPA limit for each, and where the figure comes from.
| Contaminant | Level vs EPA limit | Suppliers | Source |
|---|---|---|---|
| Nitrate | 5570 µg/L 56% of the EPA limit 10000 µg/L Main supplier: NJ AMERICAN WATER - WASHINGTON/OXFORD · 10,719 people · 2019 | 1/1 | SYR4 |
| Nitrate-Nitrite | 5558 µg/L 56% of the EPA limit 10000 µg/L Main supplier: NJ AMERICAN WATER - WASHINGTON/OXFORD · 10,719 people · 2019 | 1/1 | SYR4 |
| Fluoride | 396.3 µg/L 9.9% of the EPA limit 4000 µg/L Main supplier: NJ AMERICAN WATER - WASHINGTON/OXFORD · 10,719 people · 2019 | 1/1 | SYR4 |
| Copper | 122.2 µg/L 9.4% of the EPA limit 1300 µg/L Main supplier: NJ AMERICAN WATER - WASHINGTON/OXFORD · 10,719 people · 2019 | 1/1 | SYR4 |
| TTHM | 26.78 µg/L 33% of the EPA limit 80 µg/L Main supplier: NJ AMERICAN WATER - WASHINGTON/OXFORD · 10,719 people · 2019 | 1/1 | SYR4 |
| Lithium | 18.7 µg/L No EPA limit set Main supplier: NJ AMERICAN WATER - WASHINGTON/OXFORD · 10,719 people · 2025 | 1/1 | UCMR-5 |
| Dichloroacetic Acid | 17.73 µg/L No EPA limit set Main supplier: NJ AMERICAN WATER - WASHINGTON/OXFORD · 10,719 people · 2019 | 1/1 | SYR4 |
| Total Haloacetic Acids (HAA5) | 15.185 µg/L 25% of the EPA limit 60 µg/L Main supplier: NJ AMERICAN WATER - WASHINGTON/OXFORD · 10,719 people · 2019 | 1/1 | SYR4 |
| Bromoform | 8 µg/L No EPA limit set Main supplier: NJ AMERICAN WATER - WASHINGTON/OXFORD · 10,719 people · 2019 | 1/1 | SYR4 |
| Dibromochloromethane | 7.05 µg/L No EPA limit set Main supplier: NJ AMERICAN WATER - WASHINGTON/OXFORD · 10,719 people · 2019 | 1/1 | SYR4 |
| Chloroform | 6.915 µg/L No EPA limit set Main supplier: NJ AMERICAN WATER - WASHINGTON/OXFORD · 10,719 people · 2019 | 1/1 | SYR4 |
| Bromodichloromethane | 6.31 µg/L No EPA limit set Main supplier: NJ AMERICAN WATER - WASHINGTON/OXFORD · 10,719 people · 2019 | 1/1 | SYR4 |
| Dibromoacetic Acid | 3.89 µg/L No EPA limit set Main supplier: NJ AMERICAN WATER - WASHINGTON/OXFORD · 10,719 people · 2019 | 1/1 | SYR4 |
| Lead | 2.85 µg/L 19% of the EPA limit 15 µg/L Main supplier: NJ AMERICAN WATER - WASHINGTON/OXFORD · 10,719 people · 2019 | 1/1 | SYR4 |
| Monobromoacetic Acid | 2.075 µg/L No EPA limit set Main supplier: NJ AMERICAN WATER - WASHINGTON/OXFORD · 10,719 people · 2019 | 1/1 | SYR4 |
| Combined Radium (-226 And -228) | 1.46 pCi/L 29% of the EPA limit 5 pCi/L Main supplier: NJ AMERICAN WATER - WASHINGTON/OXFORD · 10,719 people · 2017 | 1/1 | SYR4 |
| Trichloroethylene | 1.07 µg/L 21% of the EPA limit 5 µg/L Main supplier: NJ AMERICAN WATER - WASHINGTON/OXFORD · 10,719 people · 2019 | 1/1 | SYR4 |
| Dichloromethane | 1 µg/L 20% of the EPA limit 5 µg/L Main supplier: NJ AMERICAN WATER - WASHINGTON/OXFORD · 10,719 people · 2019 | 1/1 | SYR4 |
| 1,1-Dichloroethylene | 0.7000 µg/L 10% of the EPA limit 7 µg/L Main supplier: NJ AMERICAN WATER - WASHINGTON/OXFORD · 10,719 people · 2019 | 1/1 | SYR4 |
| cis-1,2-Dichloroethylene | 0.6000 µg/L 0.9% of the EPA limit 70 µg/L Main supplier: NJ AMERICAN WATER - WASHINGTON/OXFORD · 10,719 people · 2019 | 1/1 | SYR4 |
| Atrazine | 0.1000 µg/L 3.3% of the EPA limit 3 µg/L Main supplier: NJ AMERICAN WATER - WASHINGTON/OXFORD · 10,719 people · 2019 | 1/1 | SYR4 |
| PFOS | 0.0071 µg/L No EPA limit set Main supplier: NJ AMERICAN WATER - WASHINGTON/OXFORD · 10,719 people · 2025 | 1/1 | UCMR-5 |
| PFOA | 0.0051 µg/L No EPA limit set Main supplier: NJ AMERICAN WATER - WASHINGTON/OXFORD · 10,719 people · 2025 | 1/1 | UCMR-5 |
| PFHXS | 0.0030 µg/L No EPA limit set Main supplier: NJ AMERICAN WATER - WASHINGTON/OXFORD · 10,719 people · 2025 | 1/1 | UCMR-5 |
| Lead | 0.0010 mg/L 6.7% of the EPA limit 0.0150 mg/L Main supplier: NJ AMERICAN WATER - WASHINGTON/OXFORD · 10,719 people · 2023 | 1/1 | LCR |
Water suppliers serving ZIP 08808
| Supplier | State | Population served |
|---|---|---|
| NJ AMERICAN WATER - WASHINGTON/OXFORD | NJ | 10,719 |
Frequently asked questions about ZIP 08808 tap water
Is the tap water in ZIP 08808 safe to drink?
EPA testing detected 25 contaminants across the water suppliers serving ZIP 08808. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and your utility's annual Consumer Confidence Report for the official status.
Which water suppliers serve ZIP 08808?
1 public water supplier report EPA drinking-water monitoring for ZIP 08808. Each is listed above with its population served.
What contaminants are in ZIP 08808's water?
EPA monitoring detected Nitrate, Nitrate-Nitrite, Fluoride, Copper, TTHM, and others across this ZIP's suppliers. The full list with levels and sources is above.