Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2014-08-01 → 2014-08-31 |
| MCL | Health-based | Resolved | 2014-08-01 → 2014-08-31 |
| TT | Health-based | Resolved | 2014-01-01 |
| TT | Health-based | Resolved | 2014-01-01 |
| MCL | Health-based | Resolved | 2005-05-01 → 2005-05-31 |
| MCL | Health-based | Resolved | 2004-07-01 → 2004-07-31 |
| MCL | Health-based | Resolved | 2003-07-01 → 2003-07-31 |
| MCL | Health-based | Resolved | 2003-07-01 → 2003-07-31 |
| MCL | Health-based | Archived | 2000-07-01 → 2000-07-31 |
| MCL | Health-based | Archived | 1998-07-01 → 1998-07-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate-Nitrite | 240 µg/L 2.4% of the EPA limit 10000 µg/L
worst single sample: 250 µg/L | 56/64 | SYR4 | 2012–2019 |
| Copper | 224.25 µg/L 17% of the EPA limit 1300 µg/L
worst single sample: 333 µg/L | 40/40 | SYR4 | 2017–2018 |
| Arsenic | 6.25 µg/L 63% of the EPA limit 10 µg/L
worst single sample: 9 µg/L | 12/12 | SYR4 | 2013–2018 |
| Barium | 120 µg/L 6% of the EPA limit 2000 µg/L | 12/12 | SYR4 | 2013–2018 |
| Fluoride | 400 µg/L 10% of the EPA limit 4000 µg/L | 12/12 | SYR4 | 2013–2018 |
| Gross Alpha, Excl. Radon And U | 7.765 pCi/L 52% of the EPA limit 15 pCi/L
worst single sample: 8.7 pCi/L | 12/12 | SYR4 | 2012–2018 |
| Combined Radium (-226 And -228) | 3.5 pCi/L 70% of the EPA limit 5 pCi/L
worst single sample: 3.8 pCi/L | 11/12 | SYR4 | 2012–2018 |
| Combined Uranium | 3 µg/L 10% of the EPA limit 30 µg/L | 10/12 | SYR4 | 2012–2018 |
| Lead | 0.0010 mg/L 6.7% of the EPA limit 0.0150 mg/L | 9/9 | LCR | 2025 |
| Selenium | 5 µg/L 10% of the EPA limit 50 µg/L | 9/12 | SYR4 | 2013–2018 |
| Lead | 4.4 µg/L 29% of the EPA limit 15 µg/L
worst single sample: 5 µg/L | 7/40 | SYR4 | 2017–2018 |
63 contaminants tested, none detected
Utility contact
Frequently asked questions about Newcastle, City of
Is Newcastle, City of tap water safe to drink?
EPA monitoring detected 11 contaminants in Newcastle, City of's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Newcastle, City of's water?
EPA monitoring detected Nitrate-Nitrite, Copper, Arsenic, Barium, Fluoride, and others. The full list with the level and data source for each is above.
How many people does Newcastle, City of serve?
Newcastle, City of reports serving 3,595 people in Wyoming, per its EPA record.
Has Newcastle, City of had any water quality violations?
The EPA has 330 violations on file for Newcastle, City of, of which 14 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.