← Wyoming

Tap water quality report

Wheatland, Town of

EPA monitoring tested this supplier for 81 contaminants and detected 21. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

81
contaminants tested
21
detected
3,659
people served
23
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Platte

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

23
health-based violations
270
violations on file
1
still open
ViolationTypeStatusPeriod
MCL Health-based Archived 2026-01-01 → 2026-03-31
TT Health-based Addressed 2025-01-05
TT Health-based Resolved 2022-09-28
TT Health-based Resolved 2022-09-28
TT Health-based Resolved 2022-09-28
MCL Health-based Archived 2017-10-01 → 2017-12-31
TT Health-based Resolved 2017-09-13
MCL Health-based Archived 2015-10-01 → 2015-12-31
MCL Health-based Archived 2015-07-01 → 2015-09-30
MCL Health-based Resolved 2011-08-01 → 2011-08-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
302.25 µg/L 23%
of the EPA limit 1300 µg/L
worst single sample: 536 µg/L
76/80 SYR4 2014–2019
Nitrate-Nitrite
4960 µg/L 50%
of the EPA limit 10000 µg/L
worst single sample: 5000 µg/L
58/58 SYR4 2012–2019
Combined Uranium
32.8 µg/L 109%
of the EPA limit, at the 95th percentile of samples — 30 µg/L
worst single sample: 33 µg/L
41/41 SYR4 2014–2019
Gross Alpha, Excl. Radon And U
12 pCi/L 80%
of the EPA limit 15 pCi/L
worst single sample: 15 pCi/L
25/36 SYR4 2014–2019
Combined Radium (-226 And -228)
2.58 pCi/L 52%
of the EPA limit 5 pCi/L
worst single sample: 3.5 pCi/L
22/39 SYR4 2014–2019
Lead
4 µg/L 27%
of the EPA limit 15 µg/L
worst single sample: 8 µg/L
21/80 SYR4 2014–2019
Bromoform
8.652 µg/L
No EPA limit set
worst single sample: 8.7 µg/L
17/19 SYR4 2014–2019
TTHM
20.025 µg/L 25%
of the EPA limit 80 µg/L
worst single sample: 21 µg/L
16/19 SYR4 2014–2019
Dibromochloromethane
4.741 µg/L
No EPA limit set
worst single sample: 5.3 µg/L
14/19 SYR4 2014–2019
Lead
0.0030 mg/L 20%
of the EPA limit 0.0150 mg/L
14/14 LCR 2025
Bromodichloromethane
4.6875 µg/L
No EPA limit set
worst single sample: 5.3 µg/L
8/19 SYR4 2014–2019
Dibromoacetic Acid
3.41 µg/L
No EPA limit set
worst single sample: 3.5 µg/L
7/8 SYR4 2014–2019
Fluoride
570 µg/L 14%
of the EPA limit 4000 µg/L
worst single sample: 600 µg/L
7/7 SYR4 2014–2019
Total Haloacetic Acids (HAA5)
7.65 µg/L 13%
of the EPA limit 60 µg/L
worst single sample: 8.1 µg/L
7/8 SYR4 2014–2019
Selenium
7 µg/L 14%
of the EPA limit 50 µg/L
6/7 SYR4 2014–2019
Chloroform
6.44 µg/L
No EPA limit set
worst single sample: 6.6 µg/L
5/19 SYR4 2014–2019
Pentachlorophenol
0.1880 µg/L 19%
of the EPA limit 1 µg/L
worst single sample: 0.1900 µg/L
5/17 SYR4 2014–2019
Dichloroacetic Acid
4.28 µg/L
No EPA limit set
worst single sample: 4.5 µg/L
3/8 SYR4 2014–2019
Arsenic
1.95 µg/L 20%
of the EPA limit 10 µg/L
worst single sample: 2 µg/L
2/7 SYR4 2014–2019
Monochloroacetic Acid
0.8900 µg/L
No EPA limit set
1/8 SYR4 2014–2019
Thallium, Total
0.7000 µg/L 35%
of the EPA limit 2 µg/L
1/7 SYR4 2014–2019
60 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalAsbestosAtrazineBhc-GammaBariumBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidNitriteOxamylPicloramSimazineStyreneTetrachloroethyleneTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroacetic AcidTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
WRIGHT, CANDY
Phone
307-322-2962
Email
[email protected]

Frequently asked questions about Wheatland, Town of

Is Wheatland, Town of tap water safe to drink?

EPA monitoring detected 21 contaminants in Wheatland, Town of's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Wheatland, Town of's water?

EPA monitoring detected Copper, Nitrate-Nitrite, Combined Uranium, Gross Alpha, Excl. Radon And U, Combined Radium (-226 And -228), and others. The full list with the level and data source for each is above.

How many people does Wheatland, Town of serve?

Wheatland, Town of reports serving 3,659 people in Wyoming, per its EPA record.

Has Wheatland, Town of had any water quality violations?

The EPA has 270 violations on file for Wheatland, Town of, of which 23 are health-based (a contaminant limit or required treatment was breached) and 1 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.