← Wyoming

Tap water quality report

Dubois, Town of

EPA monitoring tested this supplier for 72 contaminants and detected 15. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

72
contaminants tested
15
detected
1,822
people served
2
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Fremont

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

2
health-based violations
261
violations on file
0
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 2024-07-01
MCL Health-based Archived 1997-09-01 → 1997-09-30
MR Monitoring Resolved 2024-07-01
MR Monitoring Resolved 2024-07-01
MON Monitoring Resolved 2022-04-01 → 2022-04-30
MON Monitoring Resolved 2020-12-01 → 2020-12-31
MON Monitoring Resolved 2020-12-01 → 2020-12-31
MON Monitoring Resolved 2020-12-01 → 2020-12-31
MR Monitoring Resolved 2019-09-01 → 2020-08-31
MR Monitoring Resolved 2019-09-01 → 2020-08-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
4825 µg/L 48%
of the EPA limit 10000 µg/L
worst single sample: 5200 µg/L
24/50 SYR4 2013–2019
Copper
845.55 µg/L 65%
of the EPA limit 1300 µg/L
worst single sample: 1540 µg/L
20/20 SYR4 2016–2017
Lead
0.0 mg/L 0%
of the EPA limit 0.0150 mg/L
14/14 LCR 2025
Lead
26.035 µg/L 174%
of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 43.9 µg/L
10/20 SYR4 2016–2017
TTHM
29.66 µg/L 37%
of the EPA limit 80 µg/L
worst single sample: 33.2 µg/L
7/7 SYR4 2014–2019
Total Haloacetic Acids (HAA5)
9.5 µg/L 16%
of the EPA limit 60 µg/L
worst single sample: 9.8 µg/L
7/7 SYR4 2014–2019
Nitrate-Nitrite
1980 µg/L 20%
of the EPA limit 10000 µg/L
worst single sample: 2100 µg/L
5/8 SYR4 2012–2017
Arsenic
1.29 µg/L 13%
of the EPA limit 10 µg/L
worst single sample: 1.3 µg/L
2/2 SYR4 2015
Barium
87.15 µg/L 4.4%
of the EPA limit 2000 µg/L
worst single sample: 88 µg/L
2/2 SYR4 2015
Combined Radium (-226 And -228)
1.4261 pCi/L 29%
of the EPA limit 5 pCi/L
worst single sample: 1.457 pCi/L
2/2 SYR4 2016
Combined Uranium
3.184 µg/L 11%
of the EPA limit 30 µg/L
worst single sample: 3.19 µg/L
2/2 SYR4 2016
Fluoride
488.5 µg/L 12%
of the EPA limit 4000 µg/L
worst single sample: 500 µg/L
2/2 SYR4 2015
Gross Alpha, Excl. Radon And U
0.9100 pCi/L 6.1%
of the EPA limit 15 pCi/L
worst single sample: 0.9200 pCi/L
2/2 SYR4 2016
Selenium
3.045 µg/L 6.1%
of the EPA limit 50 µg/L
worst single sample: 3.1 µg/L
2/2 SYR4 2015
Dichloromethane
3.4 µg/L 68%
of the EPA limit 5 µg/L
1/2 SYR4 2015
57 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalAsbestosAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNitriteOxamylPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneThallium, TotalTolueneToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
HARRINGTON, MICKEY
Phone
307-455-2345
Email
[email protected]

Frequently asked questions about Dubois, Town of

Is Dubois, Town of tap water safe to drink?

EPA monitoring detected 15 contaminants in Dubois, Town of's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Dubois, Town of's water?

EPA monitoring detected Nitrate, Copper, Lead, Lead, TTHM, and others. The full list with the level and data source for each is above.

How many people does Dubois, Town of serve?

Dubois, Town of reports serving 1,822 people in Wyoming, per its EPA record.

Has Dubois, Town of had any water quality violations?

The EPA has 261 violations on file for Dubois, Town of, of which 2 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.