← Wyoming

Tap water quality report

Alpine, Town of

EPA monitoring tested this supplier for 80 contaminants and detected 19. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

80
contaminants tested
19
detected
1,300
people served
12
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Lincoln

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

12
health-based violations
57
violations on file
0
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 2020-02-26
TT Health-based Resolved 2020-02-26
TT Health-based Resolved 2016-02-04
TT Health-based Resolved 2016-02-04
TT Health-based Resolved 2016-02-04
TT Health-based Resolved 2016-02-04
TT Health-based Resolved 2016-02-04
TT Health-based Resolved 2016-02-04
MCL Health-based Archived 2006-08-01 → 2006-08-31
MCL Health-based Archived 2001-08-01 → 2001-08-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
210 µg/L 16%
of the EPA limit 1300 µg/L
worst single sample: 447 µg/L
86/90 SYR4 2015–2019
Lead
17.95 µg/L 120%
of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 45 µg/L
42/90 SYR4 2015–2019
Nitrate-Nitrite
430 µg/L 4.3%
of the EPA limit 10000 µg/L
16/16 SYR4 2012–2019
Bromoform
2.42 µg/L
No EPA limit set
worst single sample: 2.6 µg/L
11/11 SYR4 2014–2019
Dibromochloromethane
3.65 µg/L
No EPA limit set
worst single sample: 3.9 µg/L
11/11 SYR4 2014–2019
Lead
0.0020 mg/L 13%
of the EPA limit 0.0150 mg/L
11/11 LCR 2023
TTHM
9.37 µg/L 12%
of the EPA limit 80 µg/L
worst single sample: 10 µg/L
10/11 SYR4 2014–2019
Dibromoacetic Acid
1.365 µg/L
No EPA limit set
worst single sample: 1.4 µg/L
8/9 SYR4 2014–2019
Total Haloacetic Acids (HAA5)
2.08 µg/L 3.5%
of the EPA limit 60 µg/L
worst single sample: 2.5 µg/L
8/9 SYR4 2014–2019
Bromodichloromethane
2.81 µg/L
No EPA limit set
worst single sample: 3.2 µg/L
7/11 SYR4 2014–2019
Barium
200 µg/L 10%
of the EPA limit 2000 µg/L
3/3 SYR4 2013–2018
Fluoride
300 µg/L 7.5%
of the EPA limit 4000 µg/L
3/3 SYR4 2013–2018
Chloroform
1.4585 µg/L
No EPA limit set
worst single sample: 1.5 µg/L
2/11 SYR4 2014–2019
Gross Alpha, Excl. Radon And U
3.985 pCi/L 27%
of the EPA limit 15 pCi/L
worst single sample: 4 pCi/L
2/2 SYR4 2013–2019
Selenium
2 µg/L 4%
of the EPA limit 50 µg/L
2/3 SYR4 2013–2018
Combined Radium (-226 And -228)
0.8000 pCi/L 16%
of the EPA limit 5 pCi/L
1/1 SYR4 2019
Combined Uranium
0.6000 µg/L 2%
of the EPA limit 30 µg/L
1/1 SYR4 2019
Dichloroacetic Acid
1.1 µg/L
No EPA limit set
1/9 SYR4 2014–2019
Thallium, Total
0.4000 µg/L 20%
of the EPA limit 2 µg/L
1/3 SYR4 2013–2018
61 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalArsenicAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidMonochloroacetic AcidNitriteOxamylPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroacetic AcidTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
LESEBERG, MELODY
Phone
307-654-7757
Email
[email protected]

Frequently asked questions about Alpine, Town of

Is Alpine, Town of tap water safe to drink?

EPA monitoring detected 19 contaminants in Alpine, Town of's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Alpine, Town of's water?

EPA monitoring detected Copper, Lead, Nitrate-Nitrite, Bromoform, Dibromochloromethane, and others. The full list with the level and data source for each is above.

How many people does Alpine, Town of serve?

Alpine, Town of reports serving 1,300 people in Wyoming, per its EPA record.

Has Alpine, Town of had any water quality violations?

The EPA has 57 violations on file for Alpine, Town of, of which 12 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.