Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Archived | 2002-08-01 → 2002-08-31 |
| MCL | Health-based | Archived | 2001-08-01 → 2001-08-31 |
| MR | Monitoring | Resolved | 2015-08-01 → 2015-08-31 |
| MR | Monitoring | Archived | 2002-10-01 → 2002-10-31 |
| MR | Monitoring | Resolved | 2002-10-01 |
| MR | Monitoring | Resolved | 2002-10-01 |
| MR | Monitoring | Archived | 2002-09-01 → 2002-09-30 |
| MR | Monitoring | Archived | 2002-08-01 → 2002-08-31 |
| MR | Monitoring | Archived | 2002-07-01 → 2002-07-31 |
| MR | Monitoring | Resolved | 2002-01-01 → 2002-12-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 92.55 µg/L 7.1% of the EPA limit 1300 µg/L
worst single sample: 181 µg/L | 30/31 | SYR4 | 2015–2019 |
| Lead | 19 µg/L 127% of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 37 µg/L | 16/31 | SYR4 | 2015–2019 |
| Nitrate-Nitrite | 60 µg/L 0.6% of the EPA limit 10000 µg/L | 14/16 | SYR4 | 2012–2019 |
| Lead | 0.0020 mg/L 13% of the EPA limit 0.0150 mg/L | 9/9 | LCR | 2025 |
| Bromodichloromethane | 1.685 µg/L No EPA limit set
worst single sample: 1.7 µg/L | 4/4 | SYR4 | 2014–2017 |
| Bromoform | 14.23 µg/L No EPA limit set
worst single sample: 16 µg/L | 4/4 | SYR4 | 2014–2017 |
| Dibromochloromethane | 5.115 µg/L No EPA limit set
worst single sample: 5.4 µg/L | 4/4 | SYR4 | 2014–2017 |
| TTHM | 21.825 µg/L 27% of the EPA limit 80 µg/L
worst single sample: 24 µg/L | 4/4 | SYR4 | 2014–2017 |
| Barium | 280 µg/L 14% of the EPA limit 2000 µg/L | 3/3 | SYR4 | 2013–2017 |
| Chloroform | 0.9270 µg/L No EPA limit set
worst single sample: 0.9400 µg/L | 3/4 | SYR4 | 2014–2017 |
| Fluoride | 1390 µg/L 35% of the EPA limit 4000 µg/L
worst single sample: 1400 µg/L | 3/3 | SYR4 | 2013–2017 |
| Combined Radium (-226 And -228) | 3.04 pCi/L 61% of the EPA limit 5 pCi/L
worst single sample: 3.1 pCi/L | 2/2 | SYR4 | 2013–2019 |
| Dibromoacetic Acid | 0.8645 µg/L No EPA limit set
worst single sample: 0.8700 µg/L | 2/2 | SYR4 | 2014–2017 |
| Gross Alpha, Excl. Radon And U | 2.92 pCi/L 19% of the EPA limit 15 pCi/L
worst single sample: 3 pCi/L | 2/2 | SYR4 | 2013–2019 |
| Total Haloacetic Acids (HAA5) | 0.9935 µg/L 1.7% of the EPA limit 60 µg/L
worst single sample: 1 µg/L | 2/2 | SYR4 | 2014–2017 |
| Selenium | 1 µg/L 2% of the EPA limit 50 µg/L | 1/3 | SYR4 | 2013–2017 |
63 contaminants tested, none detected
Utility contact
Frequently asked questions about Eagle Ridge Mhp, Llc
Is Eagle Ridge Mhp, Llc tap water safe to drink?
EPA monitoring detected 16 contaminants in Eagle Ridge Mhp, Llc's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Eagle Ridge Mhp, Llc's water?
EPA monitoring detected Copper, Lead, Nitrate-Nitrite, Lead, Bromodichloromethane, and others. The full list with the level and data source for each is above.
How many people does Eagle Ridge Mhp, Llc serve?
Eagle Ridge Mhp, Llc reports serving 140 people in Wyoming, per its EPA record.
Has Eagle Ridge Mhp, Llc had any water quality violations?
The EPA has 286 violations on file for Eagle Ridge Mhp, Llc, of which 2 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.