Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2011-07-01 → 2011-07-31 |
| TT | Health-based | Resolved | 2011-07-01 → 2011-07-31 |
| MR | Monitoring | Resolved | 2007-07-01 → 2007-09-30 |
| MR | Monitoring | Resolved | 2007-07-01 → 2007-09-30 |
| MR | Monitoring | Resolved | 2007-07-01 → 2007-09-30 |
| MR | Monitoring | Resolved | 2007-01-01 → 2007-12-31 |
| MR | Monitoring | Resolved | 2007-01-01 → 2007-12-31 |
| MR | Monitoring | Archived | 1994-07-01 → 1994-09-30 |
| MR | Monitoring | Archived | 1994-01-01 → 1994-03-31 |
| MR | Monitoring | Archived | 1993-10-01 → 1993-12-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| TTHM | 80.345 µg/L 100% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 87 µg/L | 38/38 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 34 µg/L 57% of the EPA limit 60 µg/L | 32/32 | SYR4 | 2012–2019 |
| Bromodichloromethane | 20.65 µg/L No EPA limit set
worst single sample: 22 µg/L | 28/28 | SYR4 | 2014–2019 |
| Chloroform | 56.55 µg/L No EPA limit set
worst single sample: 69 µg/L | 28/28 | SYR4 | 2014–2019 |
| Dibromochloromethane | 10.65 µg/L No EPA limit set
worst single sample: 11 µg/L | 28/28 | SYR4 | 2014–2019 |
| Lead | 0.0040 mg/L 27% of the EPA limit 0.0150 mg/L | 23/23 | LCR | 2025 |
| Dichloroacetic Acid | 20.7 µg/L No EPA limit set
worst single sample: 23 µg/L | 22/22 | SYR4 | 2014–2019 |
| Dibromoacetic Acid | 1.8 µg/L No EPA limit set | 21/22 | SYR4 | 2014–2019 |
| Trichloroacetic Acid | 14 µg/L No EPA limit set
worst single sample: 15 µg/L | 21/22 | SYR4 | 2014–2019 |
| Copper | 263 µg/L 20% of the EPA limit 1300 µg/L
worst single sample: 510 µg/L | 20/20 | SYR4 | 2016–2019 |
| Bromoform | 1.557 µg/L No EPA limit set
worst single sample: 1.7 µg/L | 12/28 | SYR4 | 2014–2019 |
| Monochloroacetic Acid | 3.65 µg/L No EPA limit set
worst single sample: 4.5 µg/L | 11/22 | SYR4 | 2014–2019 |
| Fluoride | 465 µg/L 12% of the EPA limit 4000 µg/L
worst single sample: 500 µg/L | 8/8 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 300 µg/L 3% of the EPA limit 10000 µg/L | 7/8 | SYR4 | 2012–2019 |
| Lead | 2.85 µg/L 19% of the EPA limit 15 µg/L
worst single sample: 3 µg/L | 4/20 | SYR4 | 2016–2019 |
| Monobromoacetic Acid | 0.8150 µg/L No EPA limit set
worst single sample: 0.8300 µg/L | 3/22 | SYR4 | 2014–2019 |
| Nitrate | 300 µg/L 3% of the EPA limit 10000 µg/L | 2/2 | SYR4 | 2012 |
| Asbestos | 0.1900 MFL 2.7% of the EPA limit 7 MFL | 1/1 | SYR4 | 2013 |
| Combined Uranium | 0.3000 µg/L 1% of the EPA limit 30 µg/L | 1/2 | SYR4 | 2013–2019 |
| Gross Alpha, Excl. Radon And U | 1.5 pCi/L 10% of the EPA limit 15 pCi/L | 1/2 | SYR4 | 2013–2019 |
63 contaminants tested, none detected
Utility contact
Frequently asked questions about Thermopolis, Town of
Is Thermopolis, Town of tap water safe to drink?
EPA monitoring detected 20 contaminants in Thermopolis, Town of's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Thermopolis, Town of's water?
EPA monitoring detected TTHM, Total Haloacetic Acids (HAA5), Bromodichloromethane, Chloroform, Dibromochloromethane, and others. The full list with the level and data source for each is above.
How many people does Thermopolis, Town of serve?
Thermopolis, Town of reports serving 2,775 people in Wyoming, per its EPA record.
Has Thermopolis, Town of had any water quality violations?
The EPA has 27 violations on file for Thermopolis, Town of, of which 2 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.