Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2023-06-01 |
| TT | Health-based | Resolved | 2021-05-01 → 2021-05-31 |
| TT | Health-based | Resolved | 2021-05-01 → 2021-05-31 |
| MR | Monitoring | Resolved | 2025-01-01 → 2025-12-31 |
| MR | Monitoring | Archived | 2023-01-01 → 2025-12-31 |
| MR | Monitoring | Archived | 2023-01-01 → 2025-12-31 |
| MR | Monitoring | Resolved | 2004-07-01 → 2004-09-30 |
| MR | Monitoring | Resolved | 2004-07-01 → 2004-09-30 |
| MR | Monitoring | Resolved | 2004-07-01 → 2004-09-30 |
| MR | Monitoring | Archived | 1994-10-01 → 1994-12-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| TTHM | 38 µg/L 48% of the EPA limit 80 µg/L
worst single sample: 44 µg/L | 94/150 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 22 µg/L 37% of the EPA limit 60 µg/L
worst single sample: 30 µg/L | 64/108 | SYR4 | 2012–2019 |
| Copper | 545 µg/L 42% of the EPA limit 1300 µg/L
worst single sample: 670 µg/L | 59/60 | SYR4 | 2014–2017 |
| Chloroform | 34.66 µg/L No EPA limit set
worst single sample: 40 µg/L | 55/130 | SYR4 | 2014–2019 |
| Bromodichloromethane | 5.635 µg/L No EPA limit set
worst single sample: 7.1 µg/L | 54/130 | SYR4 | 2014–2019 |
| Trichloroacetic Acid | 16 µg/L No EPA limit set
worst single sample: 19 µg/L | 38/88 | SYR4 | 2014–2019 |
| Dibromochloromethane | 4.46 µg/L No EPA limit set
worst single sample: 5 µg/L | 37/130 | SYR4 | 2014–2019 |
| Lead | 7.2 µg/L 48% of the EPA limit 15 µg/L
worst single sample: 9 µg/L | 37/60 | SYR4 | 2014–2017 |
| Fluoride | 900 µg/L 23% of the EPA limit 4000 µg/L
worst single sample: 2700 µg/L | 30/36 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 10.84 µg/L No EPA limit set
worst single sample: 13 µg/L | 29/88 | SYR4 | 2014–2019 |
| Bromoform | 3.925 µg/L No EPA limit set
worst single sample: 4.5 µg/L | 26/130 | SYR4 | 2014–2019 |
| Dibromoacetic Acid | 0.8480 µg/L No EPA limit set
worst single sample: 0.9400 µg/L | 25/88 | SYR4 | 2014–2019 |
| Combined Radium (-226 And -228) | 5.2 pCi/L 104% of the EPA limit, at the 95th percentile of samples — 5 pCi/L | 20/25 | SYR4 | 2015–2019 |
| Gross Alpha, Excl. Radon And U | 5.845 pCi/L 39% of the EPA limit 15 pCi/L
worst single sample: 6.1 pCi/L | 18/25 | SYR4 | 2015–2019 |
| Nitrate-Nitrite | 60 µg/L 0.6% of the EPA limit 10000 µg/L | 16/238 | SYR4 | 2012–2019 |
| Lead | 0.0040 mg/L 27% of the EPA limit 0.0150 mg/L | 7/7 | LCR | 2023 |
| Monochloroacetic Acid | 0.8500 µg/L No EPA limit set | 3/88 | SYR4 | 2014–2019 |
| Asbestos | 0.2000 MFL 2.9% of the EPA limit 7 MFL | 1/3 | SYR4 | 2015 |
| Combined Uranium | 0.0010 µg/L 0% of the EPA limit 30 µg/L | 1/27 | SYR4 | 2015–2019 |
62 contaminants tested, none detected
Utility contact
Frequently asked questions about Riverton, City of
Is Riverton, City of tap water safe to drink?
EPA monitoring detected 19 contaminants in Riverton, City of's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Riverton, City of's water?
EPA monitoring detected TTHM, Total Haloacetic Acids (HAA5), Copper, Chloroform, Bromodichloromethane, and others. The full list with the level and data source for each is above.
How many people does Riverton, City of serve?
Riverton, City of reports serving 10,330 people in Wyoming, per its EPA record.
Has Riverton, City of had any water quality violations?
The EPA has 12 violations on file for Riverton, City of, of which 3 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.