Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2023-06-01 |
| TT | Health-based | Resolved | 2023-06-01 |
| TT | Health-based | Resolved | 2017-01-21 |
| TT | Health-based | Resolved | 2017-01-21 |
| TT | Health-based | Resolved | 2017-01-21 |
| MCL | Health-based | Archived | 1995-08-01 → 1995-08-31 |
| MR | Monitoring | Resolved | 2021-10-01 |
| MR | Monitoring | Resolved | 2021-10-01 |
| Other | Monitoring | Resolved | 2020-10-01 |
| Other | Monitoring | Resolved | 2020-10-01 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 208.25 µg/L 16% of the EPA limit 1300 µg/L
worst single sample: 352 µg/L | 30/30 | SYR4 | 2014–2018 |
| Lead | 15.6 µg/L 104% of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 21 µg/L | 19/30 | SYR4 | 2014–2018 |
| Nitrate-Nitrite | 220 µg/L 2.2% of the EPA limit 10000 µg/L | 16/16 | SYR4 | 2012–2019 |
| TTHM | 25.8 µg/L 32% of the EPA limit 80 µg/L
worst single sample: 28 µg/L | 12/12 | SYR4 | 2012–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 11/11 | LCR | 2024 |
| Bromodichloromethane | 8.005 µg/L No EPA limit set
worst single sample: 9.4 µg/L | 10/11 | SYR4 | 2014–2019 |
| Dibromochloromethane | 8.845 µg/L No EPA limit set
worst single sample: 9.7 µg/L | 10/11 | SYR4 | 2014–2019 |
| Bromoform | 5.72 µg/L No EPA limit set
worst single sample: 6 µg/L | 9/11 | SYR4 | 2014–2019 |
| Chloroform | 6.36 µg/L No EPA limit set
worst single sample: 7.6 µg/L | 9/11 | SYR4 | 2014–2019 |
| Total Haloacetic Acids (HAA5) | 6.435 µg/L 11% of the EPA limit 60 µg/L
worst single sample: 7.1 µg/L | 8/8 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 2.41 µg/L No EPA limit set
worst single sample: 2.5 µg/L | 7/7 | SYR4 | 2014–2019 |
| Dichloroacetic Acid | 3 µg/L No EPA limit set
worst single sample: 3.2 µg/L | 6/7 | SYR4 | 2014–2019 |
| Gross Alpha, Excl. Radon And U | 13.845 pCi/L 92% of the EPA limit 15 pCi/L
worst single sample: 14.7 pCi/L | 4/4 | SYR4 | 2013–2019 |
| Combined Uranium | 5.64 µg/L 19% of the EPA limit 30 µg/L
worst single sample: 6 µg/L | 3/4 | SYR4 | 2013–2019 |
| Fluoride | 2250 µg/L 56% of the EPA limit 4000 µg/L
worst single sample: 2300 µg/L | 3/3 | SYR4 | 2012–2017 |
| Selenium | 7.7 µg/L 15% of the EPA limit 50 µg/L
worst single sample: 8 µg/L | 3/3 | SYR4 | 2012–2017 |
| Combined Radium (-226 And -228) | 1.185 pCi/L 24% of the EPA limit 5 pCi/L
worst single sample: 1.2 pCi/L | 2/4 | SYR4 | 2013–2019 |
| Trichloroacetic Acid | 0.9805 µg/L No EPA limit set
worst single sample: 1 µg/L | 2/7 | SYR4 | 2014–2019 |
| Monobromoacetic Acid | 0.6400 µg/L No EPA limit set | 1/7 | SYR4 | 2014–2019 |
60 contaminants tested, none detected
Utility contact
Frequently asked questions about Moorcroft, Town of
Is Moorcroft, Town of tap water safe to drink?
EPA monitoring detected 19 contaminants in Moorcroft, Town of's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Moorcroft, Town of's water?
EPA monitoring detected Copper, Lead, Nitrate-Nitrite, TTHM, Lead, and others. The full list with the level and data source for each is above.
How many people does Moorcroft, Town of serve?
Moorcroft, Town of reports serving 1,009 people in Wyoming, per its EPA record.
Has Moorcroft, Town of had any water quality violations?
The EPA has 40 violations on file for Moorcroft, Town of, of which 6 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.