EPA monitoring tested this supplier for 76 contaminants and detected 21. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

76
contaminants tested
21
detected
3,469
people served
9
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Wood

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

9
health-based violations
144
violations on file
7
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 2020-12-02
TT Health-based Resolved 2020-12-02
TT Health-based Resolved 2020-12-02
TT Health-based Resolved 2020-12-02
TT Health-based Resolved 2020-12-02
MCL Health-based Resolved 2002-04-01 → 2002-04-30
MCL Health-based Resolved 2002-04-01 → 2002-04-30
MCL Health-based Resolved 2002-04-01 → 2002-04-30
MCL Health-based Resolved 2002-04-01 → 2002-04-30
MR Monitoring Unaddressed 2025-10-01

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
315.05 µg/L 24%
of the EPA limit 1300 µg/L
worst single sample: 660 µg/L
58/60 SYR4 2012–2018
Lead
8.48 µg/L 57%
of the EPA limit 15 µg/L
worst single sample: 17.1 µg/L
43/60 SYR4 2012–2018
Nitrate
6577.5 µg/L 66%
of the EPA limit 10000 µg/L
worst single sample: 6910 µg/L
40/40 SYR4 2012–2019
Nitrate-Nitrite
6647.5 µg/L 66%
of the EPA limit 10000 µg/L
worst single sample: 6910 µg/L
16/16 SYR4 2013–2019
Lead
0.0034 mg/L 23%
of the EPA limit 0.0150 mg/L
12/12 LCR 2022
Bromodichloromethane
7.817 µg/L
No EPA limit set
worst single sample: 8 µg/L
7/7 SYR4 2012–2019
Bromoform
2.803 µg/L
No EPA limit set
worst single sample: 2.86 µg/L
7/7 SYR4 2012–2019
Chloroform
3.491 µg/L
No EPA limit set
worst single sample: 3.5 µg/L
7/7 SYR4 2012–2019
Dibromoacetic Acid
4.808 µg/L
No EPA limit set
worst single sample: 4.88 µg/L
7/7 SYR4 2012–2019
Dibromochloromethane
7.879 µg/L
No EPA limit set
worst single sample: 8.2 µg/L
7/7 SYR4 2012–2019
Dichloroacetic Acid
8.315 µg/L
No EPA limit set
worst single sample: 9.74 µg/L
7/7 SYR4 2012–2019
TTHM
21.56 µg/L 27%
of the EPA limit 80 µg/L
worst single sample: 22.1 µg/L
7/7 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
15.46 µg/L 26%
of the EPA limit 60 µg/L
worst single sample: 17.2 µg/L
7/7 SYR4 2012–2019
Monochloroacetic Acid
2.42 µg/L
No EPA limit set
worst single sample: 2.62 µg/L
5/7 SYR4 2012–2019
Barium
580.09 µg/L 29%
of the EPA limit 2000 µg/L
worst single sample: 637 µg/L
3/3 SYR4 2012–2019
Fluoride
634 µg/L 16%
of the EPA limit 4000 µg/L
worst single sample: 660 µg/L
3/3 SYR4 2012–2019
Trichloroacetic Acid
1.146 µg/L
No EPA limit set
worst single sample: 1.16 µg/L
3/7 SYR4 2012–2019
Gross Alpha, Excl. Radon And U
0.5541 pCi/L 3.7%
of the EPA limit 15 pCi/L
worst single sample: 0.5560 pCi/L
2/2 SYR4 2012–2019
Chromium
1.2 µg/L 1.2%
of the EPA limit 100 µg/L
1/3 SYR4 2012–2019
Selenium
2.6 µg/L 5.2%
of the EPA limit 50 µg/L
1/3 SYR4 2012–2019
Thallium, Total
0.2000 µg/L 10%
of the EPA limit 2 µg/L
1/3 SYR4 2012–2019
55 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalArsenicAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebEthylene DibromideEndrinEthylbenzeneHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidNitriteOxamylPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
JORDAN, PAUL L
Phone
304-375-7761
Email
[email protected]

Frequently asked questions about Williamstown Water Dept

Is Williamstown Water Dept tap water safe to drink?

EPA monitoring detected 21 contaminants in Williamstown Water Dept's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Williamstown Water Dept's water?

EPA monitoring detected Copper, Lead, Nitrate, Nitrate-Nitrite, Lead, and others. The full list with the level and data source for each is above.

How many people does Williamstown Water Dept serve?

Williamstown Water Dept reports serving 3,469 people in West Virginia, per its EPA record.

Has Williamstown Water Dept had any water quality violations?

The EPA has 144 violations on file for Williamstown Water Dept, of which 9 are health-based (a contaminant limit or required treatment was breached) and 7 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.