Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2019-12-13 |
| TT | Health-based | Resolved | 2019-12-13 |
| TT | Health-based | Resolved | 2019-12-13 |
| TT | Health-based | Resolved | 2019-12-13 |
| TT | Health-based | Resolved | 2019-06-01 → 2019-06-30 |
| TT | Health-based | Resolved | 2019-06-01 → 2019-06-30 |
| TT | Health-based | Resolved | 2019-06-01 → 2019-06-30 |
| TT | Health-based | Resolved | 2019-06-01 → 2019-06-30 |
| TT | Health-based | Resolved | 2018-11-09 |
| TT | Health-based | Resolved | 2018-11-09 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 204.95 µg/L 16% of the EPA limit 1300 µg/L
worst single sample: 3570 µg/L | 80/80 | SYR4 | 2012–2019 |
| Lead | 3.74 µg/L 25% of the EPA limit 15 µg/L
worst single sample: 14.8 µg/L | 57/80 | SYR4 | 2012–2019 |
| Bromodichloromethane | 36.75 µg/L No EPA limit set
worst single sample: 39.6 µg/L | 51/51 | SYR4 | 2012–2019 |
| Chloroform | 53.25 µg/L No EPA limit set
worst single sample: 57.6 µg/L | 51/51 | SYR4 | 2012–2019 |
| Dibromochloromethane | 28.85 µg/L No EPA limit set
worst single sample: 42.6 µg/L | 51/51 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 36.65 µg/L No EPA limit set
worst single sample: 53.3 µg/L | 51/51 | SYR4 | 2012–2019 |
| TTHM | 113.5 µg/L 142% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 121 µg/L | 51/51 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 80.95 µg/L 135% of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 113 µg/L | 51/51 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 35.6 µg/L No EPA limit set
worst single sample: 43.4 µg/L | 51/51 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 8.3945 µg/L No EPA limit set
worst single sample: 11.9 µg/L | 48/51 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 5.9415 µg/L No EPA limit set
worst single sample: 10.9 µg/L | 44/51 | SYR4 | 2012–2019 |
| Bromoform | 9.374 µg/L No EPA limit set
worst single sample: 10.9 µg/L | 35/51 | SYR4 | 2012–2019 |
| Lead | 0.0031 mg/L 21% of the EPA limit 0.0150 mg/L | 17/17 | LCR | 2025 |
| Nitrate | 400 µg/L 4% of the EPA limit 10000 µg/L | 16/16 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 1.465 µg/L No EPA limit set
worst single sample: 1.5 µg/L | 11/51 | SYR4 | 2012–2019 |
| Barium | 79.68 µg/L 4% of the EPA limit 2000 µg/L
worst single sample: 87.1 µg/L | 8/8 | SYR4 | 2012–2019 |
| Fluoride | 902.5 µg/L 23% of the EPA limit 4000 µg/L
worst single sample: 920 µg/L | 8/8 | SYR4 | 2012–2019 |
| Antimony, Total | 0.8600 µg/L 14% of the EPA limit 6 µg/L
worst single sample: 0.9000 µg/L | 3/8 | SYR4 | 2012–2019 |
| Gross Alpha, Excl. Radon And U | 0.6903 pCi/L 4.6% of the EPA limit 15 pCi/L
worst single sample: 0.7160 pCi/L | 2/2 | SYR4 | 2013–2019 |
| Selenium | 1.675 µg/L 3.4% of the EPA limit 50 µg/L
worst single sample: 1.7 µg/L | 2/8 | SYR4 | 2012–2019 |
| Cyanide | 18 µg/L 9% of the EPA limit 200 µg/L | 1/8 | SYR4 | 2012–2019 |
| Di(2-ethylhexyl) Phthalate | 0.6000 µg/L 10% of the EPA limit 6 µg/L | 1/5 | SYR4 | 2013–2019 |
| Nitrate-Nitrite | 50 µg/L 0.5% of the EPA limit 10000 µg/L | 1/1 | SYR4 | 2019 |
| Thallium, Total | 0.2000 µg/L 10% of the EPA limit 2 µg/L | 1/8 | SYR4 | 2012–2019 |
52 contaminants tested, none detected
Utility contact
Frequently asked questions about Kenova Municipal Water
Is Kenova Municipal Water tap water safe to drink?
EPA monitoring detected 24 contaminants in Kenova Municipal Water's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Kenova Municipal Water's water?
EPA monitoring detected Copper, Lead, Bromodichloromethane, Chloroform, Dibromochloromethane, and others. The full list with the level and data source for each is above.
How many people does Kenova Municipal Water serve?
Kenova Municipal Water reports serving 11,192 people in West Virginia, per its EPA record.
Has Kenova Municipal Water had any water quality violations?
The EPA has 185 violations on file for Kenova Municipal Water, of which 36 are health-based (a contaminant limit or required treatment was breached) and 4 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.