Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Unaddressed | 2025-08-13 |
| TT | Health-based | Unaddressed | 2025-08-13 |
| TT | Health-based | Unaddressed | 2025-08-13 |
| TT | Health-based | Unaddressed | 2025-08-13 |
| TT | Health-based | Unaddressed | 2025-08-13 |
| TT | Health-based | Unaddressed | 2025-08-13 |
| TT | Health-based | Unaddressed | 2025-08-13 |
| TT | Health-based | Unaddressed | 2025-08-13 |
| TT | Health-based | Unaddressed | 2025-08-13 |
| TT | Health-based | Unaddressed | 2025-08-13 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Bromodichloromethane | 19.95 µg/L No EPA limit set
worst single sample: 26.8 µg/L | 56/56 | SYR4 | 2012–2019 |
| Chloroform | 83.9 µg/L No EPA limit set
worst single sample: 96.9 µg/L | 56/56 | SYR4 | 2012–2019 |
| TTHM | 106.068 µg/L 133% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 115.6 µg/L | 56/56 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 27.53 µg/L No EPA limit set
worst single sample: 31.5 µg/L | 55/55 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 53.49 µg/L 89% of the EPA limit 60 µg/L
worst single sample: 59.8 µg/L | 55/55 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 29.47 µg/L No EPA limit set
worst single sample: 31.9 µg/L | 55/55 | SYR4 | 2012–2019 |
| Dibromochloromethane | 4.316 µg/L No EPA limit set
worst single sample: 7.62 µg/L | 52/56 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 2.804 µg/L No EPA limit set
worst single sample: 3.19 µg/L | 43/55 | SYR4 | 2012–2019 |
| Copper | 71.575 µg/L 5.5% of the EPA limit 1300 µg/L
worst single sample: 216 µg/L | 42/60 | SYR4 | 2012–2018 |
| Lead | 2 µg/L 13% of the EPA limit 15 µg/L
worst single sample: 8 µg/L | 22/60 | SYR4 | 2012–2018 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 18/18 | LCR | 2027 |
| Nitrate | 360 µg/L 3.6% of the EPA limit 10000 µg/L | 16/16 | SYR4 | 2012–2019 |
| Barium | 32.16 µg/L 1.6% of the EPA limit 2000 µg/L
worst single sample: 32.3 µg/L | 8/8 | SYR4 | 2012–2019 |
| Fluoride | 1036.5 µg/L 26% of the EPA limit 4000 µg/L
worst single sample: 1040 µg/L | 8/8 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 1.625 µg/L No EPA limit set
worst single sample: 1.67 µg/L | 7/55 | SYR4 | 2012–2019 |
| Bromoform | 0.6500 µg/L No EPA limit set
worst single sample: 0.7000 µg/L | 6/56 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 3.8035 µg/L No EPA limit set
worst single sample: 3.89 µg/L | 2/55 | SYR4 | 2012–2019 |
| Dalapon | 1 µg/L 0.5% of the EPA limit 200 µg/L | 1/5 | SYR4 | 2013–2019 |
| Gross Alpha, Excl. Radon And U | 0.2770 pCi/L 1.8% of the EPA limit 15 pCi/L | 1/1 | SYR4 | 2013 |
| cis-1,2-Dichloroethylene | 1.05 µg/L 1.5% of the EPA limit 70 µg/L | 1/9 | SYR4 | 2012–2019 |
55 contaminants tested, none detected
Utility contact
Frequently asked questions about Wayne Water Town of
Is Wayne Water Town of tap water safe to drink?
EPA monitoring detected 20 contaminants in Wayne Water Town of's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Wayne Water Town of's water?
EPA monitoring detected Bromodichloromethane, Chloroform, TTHM, Dichloroacetic Acid, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.
How many people does Wayne Water Town of serve?
Wayne Water Town of reports serving 5,519 people in West Virginia, per its EPA record.
Has Wayne Water Town of had any water quality violations?
The EPA has 93 violations on file for Wayne Water Town of, of which 66 are health-based (a contaminant limit or required treatment was breached) and 44 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.