Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Archived | 2025-07-01 → 2025-09-30 |
| MCL | Health-based | Archived | 2025-07-01 → 2025-09-30 |
| MCL | Health-based | Archived | 2025-07-01 → 2025-09-30 |
| MCL | Health-based | Archived | 2025-04-01 → 2025-06-30 |
| MCL | Health-based | Archived | 2025-04-01 → 2025-06-30 |
| MCL | Health-based | Archived | 2025-04-01 → 2025-06-30 |
| MCL | Health-based | Archived | 2025-01-01 → 2025-03-31 |
| MCL | Health-based | Archived | 2025-01-01 → 2025-03-31 |
| MCL | Health-based | Archived | 2025-01-01 → 2025-03-31 |
| MCL | Health-based | Archived | 2024-10-01 → 2024-12-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Bromodichloromethane | 5.772 µg/L No EPA limit set
worst single sample: 12.2 µg/L | 33/33 | SYR4 | 2012–2019 |
| Chloroform | 42.96 µg/L No EPA limit set
worst single sample: 47.7 µg/L | 33/33 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 25.49 µg/L No EPA limit set
worst single sample: 27.1 µg/L | 32/32 | SYR4 | 2012–2019 |
| TTHM | 49.445 µg/L 62% of the EPA limit 80 µg/L
worst single sample: 57.1 µg/L | 32/32 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 60.18 µg/L 100% of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 75.8 µg/L | 32/32 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 35.28 µg/L No EPA limit set
worst single sample: 45.8 µg/L | 32/32 | SYR4 | 2012–2019 |
| Copper | 182.6 µg/L 14% of the EPA limit 1300 µg/L
worst single sample: 260 µg/L | 26/30 | SYR4 | 2013–2019 |
| Monochloroacetic Acid | 3.388 µg/L No EPA limit set
worst single sample: 6.21 µg/L | 22/32 | SYR4 | 2012–2019 |
| Lead | 2.205 µg/L 15% of the EPA limit 15 µg/L
worst single sample: 2.3 µg/L | 20/30 | SYR4 | 2013–2019 |
| Nitrate | 930 µg/L 9.3% of the EPA limit 10000 µg/L | 16/16 | SYR4 | 2012–2019 |
| Lead | 0.0025 mg/L 17% of the EPA limit 0.0150 mg/L | 9/9 | LCR | 2025 |
| Barium | 29.945 µg/L 1.5% of the EPA limit 2000 µg/L
worst single sample: 30.4 µg/L | 8/8 | SYR4 | 2012–2019 |
| Fluoride | 962 µg/L 24% of the EPA limit 4000 µg/L
worst single sample: 1060 µg/L | 8/8 | SYR4 | 2012–2019 |
| Dibromochloromethane | 1.286 µg/L No EPA limit set
worst single sample: 1.45 µg/L | 5/33 | SYR4 | 2012–2019 |
| Arsenic | 0.5600 µg/L 5.6% of the EPA limit 10 µg/L | 1/8 | SYR4 | 2012–2019 |
| Bromoform | 0.4000 µg/L No EPA limit set | 1/33 | SYR4 | 2012–2019 |
| Gross Alpha, Excl. Radon And U | 1.13 pCi/L 7.5% of the EPA limit 15 pCi/L | 1/1 | SYR4 | 2013 |
| Monobromoacetic Acid | 3.75 µg/L No EPA limit set | 1/32 | SYR4 | 2012–2019 |
57 contaminants tested, none detected
Utility contact
Frequently asked questions about Big Bend Psd
Is Big Bend Psd tap water safe to drink?
EPA monitoring detected 18 contaminants in Big Bend Psd's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Big Bend Psd's water?
EPA monitoring detected Bromodichloromethane, Chloroform, Dichloroacetic Acid, TTHM, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.
How many people does Big Bend Psd serve?
Big Bend Psd reports serving 1,350 people in West Virginia, per its EPA record.
Has Big Bend Psd had any water quality violations?
The EPA has 64 violations on file for Big Bend Psd, of which 24 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.