Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2014-08-01 → 2014-08-31 |
| MCL | Health-based | Resolved | 2014-08-01 → 2014-08-31 |
| MCL | Health-based | Resolved | 2014-08-01 → 2014-08-31 |
| MCL | Health-based | Resolved | 2014-08-01 → 2014-08-31 |
| MCL | Health-based | Resolved | 2005-07-01 → 2005-09-30 |
| MCL | Health-based | Resolved | 2005-07-01 → 2005-09-30 |
| MCL | Health-based | Resolved | 2005-07-01 → 2005-09-30 |
| MCL | Health-based | Resolved | 2005-07-01 → 2005-09-30 |
| MCL | Health-based | Resolved | 2005-04-01 → 2005-06-30 |
| MCL | Health-based | Resolved | 2005-04-01 → 2005-06-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Bromodichloromethane | 5.846 µg/L No EPA limit set
worst single sample: 9.37 µg/L | 57/57 | SYR4 | 2012–2019 |
| Chloroform | 66.94 µg/L No EPA limit set
worst single sample: 73.1 µg/L | 57/57 | SYR4 | 2012–2019 |
| TTHM | 72.008 µg/L 90% of the EPA limit 80 µg/L
worst single sample: 82.9 µg/L | 57/57 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 64.08 µg/L 107% of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 78.6 µg/L | 57/57 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 37.12 µg/L No EPA limit set
worst single sample: 46.4 µg/L | 57/57 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 27.625 µg/L No EPA limit set
worst single sample: 31.2 µg/L | 56/57 | SYR4 | 2012–2019 |
| Copper | 368.1 µg/L 28% of the EPA limit 1300 µg/L
worst single sample: 807 µg/L | 40/40 | SYR4 | 2014–2017 |
| Monochloroacetic Acid | 4.206 µg/L No EPA limit set
worst single sample: 11.4 µg/L | 40/57 | SYR4 | 2012–2019 |
| Lead | 4.59 µg/L 31% of the EPA limit 15 µg/L
worst single sample: 9 µg/L | 34/40 | SYR4 | 2014–2017 |
| Dibromochloromethane | 0.6700 µg/L No EPA limit set
worst single sample: 1.89 µg/L | 25/57 | SYR4 | 2012–2019 |
| Lead | 0.00074 mg/L 4.9% of the EPA limit 0.0150 mg/L | 17/17 | LCR | 2023 |
| Nitrate | 120 µg/L 1.2% of the EPA limit 10000 µg/L | 16/16 | SYR4 | 2012–2019 |
| Barium | 21.37 µg/L 1.1% of the EPA limit 2000 µg/L
worst single sample: 22 µg/L | 8/8 | SYR4 | 2012–2019 |
| Fluoride | 981.5 µg/L 25% of the EPA limit 4000 µg/L
worst single sample: 1020 µg/L | 8/8 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 13.806 µg/L No EPA limit set
worst single sample: 15.9 µg/L | 7/57 | SYR4 | 2012–2019 |
| Gross Alpha, Excl. Radon And U | 0.0340 pCi/L 0.2% of the EPA limit 15 pCi/L | 1/1 | SYR4 | 2019 |
| Nitrate-Nitrite | 120 µg/L 1.2% of the EPA limit 10000 µg/L | 1/1 | SYR4 | 2019 |
59 contaminants tested, none detected
Utility contact
Frequently asked questions about Spencer Water Dept
Is Spencer Water Dept tap water safe to drink?
EPA monitoring detected 17 contaminants in Spencer Water Dept's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Spencer Water Dept's water?
EPA monitoring detected Bromodichloromethane, Chloroform, TTHM, Total Haloacetic Acids (HAA5), Trichloroacetic Acid, and others. The full list with the level and data source for each is above.
How many people does Spencer Water Dept serve?
Spencer Water Dept reports serving 4,630 people in West Virginia, per its EPA record.
Has Spencer Water Dept had any water quality violations?
The EPA has 89 violations on file for Spencer Water Dept, of which 20 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.