Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2024-10-22 |
| TT | Health-based | Resolved | 2024-10-22 |
| TT | Health-based | Resolved | 2024-10-22 |
| TT | Health-based | Resolved | 2024-10-22 |
| MCL | Health-based | Resolved | 2017-01-01 → 2017-03-31 |
| MCL | Health-based | Resolved | 2017-01-01 → 2017-03-31 |
| MCL | Health-based | Resolved | 2017-01-01 → 2017-03-31 |
| MCL | Health-based | Resolved | 2017-01-01 → 2017-03-31 |
| MCL | Health-based | Resolved | 2016-10-01 → 2016-12-31 |
| MCL | Health-based | Resolved | 2016-10-01 → 2016-12-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Bromodichloromethane | 23.2 µg/L No EPA limit set
worst single sample: 24.8 µg/L | 17/17 | SYR4 | 2015–2019 |
| Chloroform | 101 µg/L No EPA limit set
worst single sample: 139 µg/L | 17/17 | SYR4 | 2015–2019 |
| Dibromochloromethane | 3.72 µg/L No EPA limit set
worst single sample: 3.8 µg/L | 17/17 | SYR4 | 2015–2019 |
| TTHM | 125.24 µg/L 157% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 167 µg/L | 17/17 | SYR4 | 2015–2019 |
| Dichloroacetic Acid | 30.3 µg/L No EPA limit set
worst single sample: 34.5 µg/L | 16/16 | SYR4 | 2015–2019 |
| Total Haloacetic Acids (HAA5) | 80.7 µg/L 135% of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 99.9 µg/L | 16/16 | SYR4 | 2015–2019 |
| Trichloroacetic Acid | 64.175 µg/L No EPA limit set
worst single sample: 68.9 µg/L | 16/16 | SYR4 | 2015–2019 |
| Copper | 235.6 µg/L 18% of the EPA limit 1300 µg/L
worst single sample: 313 µg/L | 13/15 | SYR4 | 2012–2018 |
| Lead | 0.0021 mg/L 14% of the EPA limit 0.0150 mg/L | 11/11 | LCR | 2024 |
| Lead | 3.98 µg/L 27% of the EPA limit 15 µg/L
worst single sample: 4.9 µg/L | 9/15 | SYR4 | 2012–2018 |
| Monochloroacetic Acid | 2.548 µg/L No EPA limit set
worst single sample: 2.58 µg/L | 9/16 | SYR4 | 2015–2019 |
| Dibromoacetic Acid | 1.26975 µg/L No EPA limit set
worst single sample: 1.3 µg/L | 2/16 | SYR4 | 2015–2019 |
| Monobromoacetic Acid | 0.6670 µg/L No EPA limit set | 1/16 | SYR4 | 2015–2019 |
1 contaminants tested, none detected
Utility contact
Frequently asked questions about Ellenboro Psd
Is Ellenboro Psd tap water safe to drink?
EPA monitoring detected 13 contaminants in Ellenboro Psd's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Ellenboro Psd's water?
EPA monitoring detected Bromodichloromethane, Chloroform, Dibromochloromethane, TTHM, Dichloroacetic Acid, and others. The full list with the level and data source for each is above.
How many people does Ellenboro Psd serve?
Ellenboro Psd reports serving 456 people in West Virginia, per its EPA record.
Has Ellenboro Psd had any water quality violations?
The EPA has 102 violations on file for Ellenboro Psd, of which 23 are health-based (a contaminant limit or required treatment was breached) and 3 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.