← West Virginia

Tap water quality report

Ellenboro Psd

EPA monitoring tested this supplier for 14 contaminants and detected 13. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

14
contaminants tested
13
detected
456
people served
23
health-based violations
Water source
SWP
Ownership
Local government
Counties served
Ritchie

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

23
health-based violations
102
violations on file
3
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 2024-10-22
TT Health-based Resolved 2024-10-22
TT Health-based Resolved 2024-10-22
TT Health-based Resolved 2024-10-22
MCL Health-based Resolved 2017-01-01 → 2017-03-31
MCL Health-based Resolved 2017-01-01 → 2017-03-31
MCL Health-based Resolved 2017-01-01 → 2017-03-31
MCL Health-based Resolved 2017-01-01 → 2017-03-31
MCL Health-based Resolved 2016-10-01 → 2016-12-31
MCL Health-based Resolved 2016-10-01 → 2016-12-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Bromodichloromethane
23.2 µg/L
No EPA limit set
worst single sample: 24.8 µg/L
17/17 SYR4 2015–2019
Chloroform
101 µg/L
No EPA limit set
worst single sample: 139 µg/L
17/17 SYR4 2015–2019
Dibromochloromethane
3.72 µg/L
No EPA limit set
worst single sample: 3.8 µg/L
17/17 SYR4 2015–2019
TTHM
125.24 µg/L 157%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 167 µg/L
17/17 SYR4 2015–2019
Dichloroacetic Acid
30.3 µg/L
No EPA limit set
worst single sample: 34.5 µg/L
16/16 SYR4 2015–2019
Total Haloacetic Acids (HAA5)
80.7 µg/L 135%
of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 99.9 µg/L
16/16 SYR4 2015–2019
Trichloroacetic Acid
64.175 µg/L
No EPA limit set
worst single sample: 68.9 µg/L
16/16 SYR4 2015–2019
Copper
235.6 µg/L 18%
of the EPA limit 1300 µg/L
worst single sample: 313 µg/L
13/15 SYR4 2012–2018
Lead
0.0021 mg/L 14%
of the EPA limit 0.0150 mg/L
11/11 LCR 2024
Lead
3.98 µg/L 27%
of the EPA limit 15 µg/L
worst single sample: 4.9 µg/L
9/15 SYR4 2012–2018
Monochloroacetic Acid
2.548 µg/L
No EPA limit set
worst single sample: 2.58 µg/L
9/16 SYR4 2015–2019
Dibromoacetic Acid
1.26975 µg/L
No EPA limit set
worst single sample: 1.3 µg/L
2/16 SYR4 2015–2019
Monobromoacetic Acid
0.6670 µg/L
No EPA limit set
1/16 SYR4 2015–2019
1 contaminants tested, none detected
Bromoform

Utility contact

Contact
HALL, M. T.
Phone
304-643-2430

Frequently asked questions about Ellenboro Psd

Is Ellenboro Psd tap water safe to drink?

EPA monitoring detected 13 contaminants in Ellenboro Psd's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Ellenboro Psd's water?

EPA monitoring detected Bromodichloromethane, Chloroform, Dibromochloromethane, TTHM, Dichloroacetic Acid, and others. The full list with the level and data source for each is above.

How many people does Ellenboro Psd serve?

Ellenboro Psd reports serving 456 people in West Virginia, per its EPA record.

Has Ellenboro Psd had any water quality violations?

The EPA has 102 violations on file for Ellenboro Psd, of which 23 are health-based (a contaminant limit or required treatment was breached) and 3 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.