← West Virginia

Tap water quality report

Kingwood Water Board

EPA monitoring tested this supplier for 75 contaminants and detected 17. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

75
contaminants tested
17
detected
7,674
people served
14
health-based violations
Water source
Surface water
Ownership
Local government
Counties served
Preston

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

14
health-based violations
57
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2005-07-01 → 2005-09-30
MCL Health-based Resolved 2005-07-01 → 2005-09-30
MCL Health-based Resolved 2005-07-01 → 2005-09-30
MCL Health-based Resolved 2005-07-01 → 2005-09-30
MCL Health-based Resolved 2005-04-01 → 2005-06-30
MCL Health-based Resolved 2005-04-01 → 2005-06-30
MCL Health-based Resolved 2005-04-01 → 2005-06-30
MCL Health-based Resolved 2005-04-01 → 2005-06-30
TT Health-based Resolved 1998-06-01 → 1998-06-30
TT Health-based Resolved 1998-06-01 → 1998-06-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Dichloroacetic Acid
25.535 µg/L
No EPA limit set
worst single sample: 36 µg/L
44/44 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
58.1 µg/L 97%
of the EPA limit 60 µg/L
worst single sample: 64.6 µg/L
44/44 SYR4 2012–2019
Trichloroacetic Acid
28.365 µg/L
No EPA limit set
worst single sample: 33.7 µg/L
44/44 SYR4 2012–2019
Bromodichloromethane
6.765 µg/L
No EPA limit set
worst single sample: 8.28 µg/L
43/43 SYR4 2012–2019
Chloroform
67.97 µg/L
No EPA limit set
worst single sample: 74.5 µg/L
43/43 SYR4 2012–2019
TTHM
75.88 µg/L 95%
of the EPA limit 80 µg/L
worst single sample: 80.4 µg/L
43/43 SYR4 2012–2019
Copper
48.05 µg/L 3.7%
of the EPA limit 1300 µg/L
worst single sample: 53.1 µg/L
40/40 SYR4 2013–2019
Monochloroacetic Acid
3.574 µg/L
No EPA limit set
worst single sample: 6.54 µg/L
37/44 SYR4 2012–2019
Lead
9.23 µg/L 62%
of the EPA limit 15 µg/L
worst single sample: 13.8 µg/L
34/40 SYR4 2013–2019
Dibromochloromethane
1.116 µg/L
No EPA limit set
worst single sample: 1.42 µg/L
20/43 SYR4 2012–2019
Nitrate
420 µg/L 4.2%
of the EPA limit 10000 µg/L
18/18 SYR4 2012–2019
Fluoride
970 µg/L 24%
of the EPA limit 4000 µg/L
worst single sample: 990 µg/L
9/9 SYR4 2012–2019
Lead
0.0015 mg/L 10%
of the EPA limit 0.0150 mg/L
9/9 LCR 2025
Barium
25.015 µg/L 1.3%
of the EPA limit 2000 µg/L
worst single sample: 25.4 µg/L
8/8 SYR4 2012–2019
Monobromoacetic Acid
2.673 µg/L
No EPA limit set
worst single sample: 2.72 µg/L
2/44 SYR4 2012–2019
Cyanide
15 µg/L 7.5%
of the EPA limit 200 µg/L
1/8 SYR4 2012–2019
Nitrate-Nitrite
420 µg/L 4.2%
of the EPA limit 10000 µg/L
1/1 SYR4 2019
58 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalArsenicAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalBromoformChlorobenzeneCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDibromoacetic AcidDinosebEthylene DibromideEndrinEthylbenzeneHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNitriteOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
DERIGGI, ROBERT.
Phone
304-329-0770

Frequently asked questions about Kingwood Water Board

Is Kingwood Water Board tap water safe to drink?

EPA monitoring detected 17 contaminants in Kingwood Water Board's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Kingwood Water Board's water?

EPA monitoring detected Dichloroacetic Acid, Total Haloacetic Acids (HAA5), Trichloroacetic Acid, Bromodichloromethane, Chloroform, and others. The full list with the level and data source for each is above.

How many people does Kingwood Water Board serve?

Kingwood Water Board reports serving 7,674 people in West Virginia, per its EPA record.

Has Kingwood Water Board had any water quality violations?

The EPA has 57 violations on file for Kingwood Water Board, of which 14 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.