Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2024-04-06 |
| TT | Health-based | Resolved | 2024-04-06 |
| TT | Health-based | Resolved | 2024-04-06 |
| TT | Health-based | Resolved | 2024-04-06 |
| MCL | Health-based | Resolved | 2005-04-01 → 2005-06-30 |
| MCL | Health-based | Resolved | 2005-04-01 → 2005-06-30 |
| MCL | Health-based | Resolved | 2005-04-01 → 2005-06-30 |
| MCL | Health-based | Resolved | 2005-04-01 → 2005-06-30 |
| MCL | Health-based | Resolved | 2005-01-01 → 2005-03-31 |
| MCL | Health-based | Resolved | 2005-01-01 → 2005-03-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Bromodichloromethane | 8.13 µg/L No EPA limit set
worst single sample: 10.6 µg/L | 59/59 | SYR4 | 2012–2019 |
| Chloroform | 84.72 µg/L No EPA limit set
worst single sample: 88.2 µg/L | 59/59 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 30.24 µg/L No EPA limit set
worst single sample: 39.2 µg/L | 59/59 | SYR4 | 2012–2019 |
| TTHM | 91.34 µg/L 114% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 95.4 µg/L | 59/59 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 76.68 µg/L 128% of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 96.7 µg/L | 59/59 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 44.81 µg/L No EPA limit set
worst single sample: 60.1 µg/L | 59/59 | SYR4 | 2012–2019 |
| Copper | 353 µg/L 27% of the EPA limit 1300 µg/L
worst single sample: 514 µg/L | 51/61 | SYR4 | 2012–2018 |
| Monochloroacetic Acid | 5.347 µg/L No EPA limit set
worst single sample: 12.6 µg/L | 48/59 | SYR4 | 2012–2019 |
| Dibromochloromethane | 2.8725 µg/L No EPA limit set
worst single sample: 4 µg/L | 36/59 | SYR4 | 2012–2019 |
| Lead | 13.175 µg/L 88% of the EPA limit 15 µg/L
worst single sample: 46.4 µg/L | 30/61 | SYR4 | 2012–2018 |
| Nitrate | 280 µg/L 2.8% of the EPA limit 10000 µg/L | 16/16 | SYR4 | 2012–2019 |
| Lead | 0.00065 mg/L 4.3% of the EPA limit 0.0150 mg/L | 13/13 | LCR | 2024 |
| Barium | 48.755 µg/L 2.4% of the EPA limit 2000 µg/L
worst single sample: 49 µg/L | 8/8 | SYR4 | 2012–2019 |
| Fluoride | 837.2 µg/L 21% of the EPA limit 4000 µg/L
worst single sample: 868 µg/L | 8/8 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 4.68 µg/L No EPA limit set
worst single sample: 5.58 µg/L | 6/59 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 0.5785 µg/L No EPA limit set
worst single sample: 0.5800 µg/L | 2/59 | SYR4 | 2012–2019 |
| Arsenic | 1.7 µg/L 17% of the EPA limit 10 µg/L | 1/8 | SYR4 | 2012–2019 |
| Bromoform | 0.3000 µg/L No EPA limit set | 1/59 | SYR4 | 2012–2019 |
| Chromium | 0.5180 µg/L 0.5% of the EPA limit 100 µg/L | 1/8 | SYR4 | 2012–2019 |
| Gross Alpha, Excl. Radon And U | 2.2 pCi/L 15% of the EPA limit 15 pCi/L | 1/1 | SYR4 | 2016 |
| Nitrate-Nitrite | 190 µg/L 1.9% of the EPA limit 10000 µg/L | 1/1 | SYR4 | 2019 |
55 contaminants tested, none detected
Utility contact
Frequently asked questions about Wilderness Psd
Is Wilderness Psd tap water safe to drink?
EPA monitoring detected 21 contaminants in Wilderness Psd's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Wilderness Psd's water?
EPA monitoring detected Bromodichloromethane, Chloroform, Dichloroacetic Acid, TTHM, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.
How many people does Wilderness Psd serve?
Wilderness Psd reports serving 6,106 people in West Virginia, per its EPA record.
Has Wilderness Psd had any water quality violations?
The EPA has 82 violations on file for Wilderness Psd, of which 16 are health-based (a contaminant limit or required treatment was breached) and 3 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.