← West Virginia

Tap water quality report

Berkeley Springs City of

EPA monitoring tested this supplier for 77 contaminants and detected 21. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

77
contaminants tested
21
detected
3,526
people served
12
health-based violations
Water source
Surface water
Ownership
Local government
Counties served
Morgan

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

12
health-based violations
290
violations on file
7
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 2019-06-05
TT Health-based Resolved 2019-06-05
TT Health-based Resolved 2019-06-05
TT Health-based Resolved 2019-06-05
TT Health-based Resolved 2018-04-01 → 2018-04-30
TT Health-based Resolved 2018-04-01 → 2018-04-30
TT Health-based Resolved 2018-04-01 → 2018-04-30
TT Health-based Resolved 2018-04-01 → 2018-04-30
TT Health-based Resolved 2002-06-07
TT Health-based Resolved 2002-06-07

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
551.8 µg/L 42%
of the EPA limit 1300 µg/L
worst single sample: 601 µg/L
57/58 SYR4 2013–2019
Lead
6.275 µg/L 42%
of the EPA limit 15 µg/L
worst single sample: 7 µg/L
30/58 SYR4 2013–2019
Lead
0.0035 mg/L 23%
of the EPA limit 0.0150 mg/L
18/18 LCR 2025
Nitrate
760 µg/L 7.6%
of the EPA limit 10000 µg/L
16/16 SYR4 2012–2019
Bromodichloromethane
3.385 µg/L
No EPA limit set
worst single sample: 4.1 µg/L
12/13 SYR4 2012–2019
TTHM
11.975 µg/L 15%
of the EPA limit 80 µg/L
worst single sample: 13.9 µg/L
12/13 SYR4 2012–2019
Dichloroacetic Acid
5.17 µg/L
No EPA limit set
worst single sample: 6.7 µg/L
10/13 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
7.54 µg/L 13%
of the EPA limit 60 µg/L
worst single sample: 8.8 µg/L
10/13 SYR4 2012–2019
Barium
58.6 µg/L 2.9%
of the EPA limit 2000 µg/L
worst single sample: 60 µg/L
8/8 SYR4 2012–2019
Chloroform
9.38 µg/L
No EPA limit set
worst single sample: 9.8 µg/L
8/13 SYR4 2012–2019
Trichloroacetic Acid
2.94 µg/L
No EPA limit set
worst single sample: 3.3 µg/L
7/13 SYR4 2012–2019
Dibromochloromethane
1.35 µg/L
No EPA limit set
worst single sample: 1.4 µg/L
6/13 SYR4 2012–2019
Arsenic
3.975 µg/L 40%
of the EPA limit 10 µg/L
worst single sample: 4.1 µg/L
2/8 SYR4 2012–2019
Di(2-ethylhexyl) Phthalate
1.078 µg/L 18%
of the EPA limit 6 µg/L
worst single sample: 1.08 µg/L
2/5 SYR4 2013–2019
Dibromoacetic Acid
0.6950 µg/L
No EPA limit set
worst single sample: 0.7000 µg/L
2/13 SYR4 2012–2019
Gross Alpha, Excl. Radon And U
3.8375 pCi/L 26%
of the EPA limit 15 pCi/L
worst single sample: 3.92 pCi/L
2/2 SYR4 2012–2019
Antimony, Total
5 µg/L 83%
of the EPA limit 6 µg/L
1/8 SYR4 2012–2019
Chromium
2 µg/L 2%
of the EPA limit 100 µg/L
1/8 SYR4 2012–2019
Combined Uranium
0.5120 µg/L 1.7%
of the EPA limit 30 µg/L
1/1 SYR4 2012
Nitrate-Nitrite
760 µg/L 7.6%
of the EPA limit 10000 µg/L
1/1 SYR4 2019
Selenium
15 µg/L 30%
of the EPA limit 50 µg/L
1/8 SYR4 2012–2019
56 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalBromoformChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneDichloromethaneDalaponDi(2-ethylhexyl) AdipateDinosebEthylene DibromideEndrinEthylbenzeneFluorideHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidMonochloroacetic AcidNitriteOxamylPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
O'CONNELL, DAVID
Phone
304-258-1102

Frequently asked questions about Berkeley Springs City of

Is Berkeley Springs City of tap water safe to drink?

EPA monitoring detected 21 contaminants in Berkeley Springs City of's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Berkeley Springs City of's water?

EPA monitoring detected Copper, Lead, Lead, Nitrate, Bromodichloromethane, and others. The full list with the level and data source for each is above.

How many people does Berkeley Springs City of serve?

Berkeley Springs City of reports serving 3,526 people in West Virginia, per its EPA record.

Has Berkeley Springs City of had any water quality violations?

The EPA has 290 violations on file for Berkeley Springs City of, of which 12 are health-based (a contaminant limit or required treatment was breached) and 7 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.