Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Unaddressed | 2026-01-01 |
| TT | Health-based | Unaddressed | 2026-01-01 |
| TT | Health-based | Unaddressed | 2026-01-01 |
| TT | Health-based | Unaddressed | 2026-01-01 |
| TT | Health-based | Unaddressed | 2026-01-01 |
| TT | Health-based | Unaddressed | 2026-01-01 |
| TT | Health-based | Unaddressed | 2018-12-29 |
| TT | Health-based | Unaddressed | 2018-12-29 |
| TT | Health-based | Unaddressed | 2018-12-29 |
| MCL | Health-based | Resolved | 2016-07-01 → 2016-09-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Bromodichloromethane | 33.92 µg/L No EPA limit set
worst single sample: 39.5 µg/L | 33/33 | SYR4 | 2012–2019 |
| Chloroform | 96.78 µg/L No EPA limit set
worst single sample: 122 µg/L | 33/33 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 29.34 µg/L No EPA limit set
worst single sample: 36.2 µg/L | 33/33 | SYR4 | 2012–2019 |
| TTHM | 137.04 µg/L 171% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 166 µg/L | 33/33 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 59.98 µg/L 100% of the EPA limit 60 µg/L
worst single sample: 94.5 µg/L | 33/33 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 25.715 µg/L No EPA limit set
worst single sample: 54.2 µg/L | 32/33 | SYR4 | 2012–2019 |
| Copper | 205.6 µg/L 16% of the EPA limit 1300 µg/L
worst single sample: 452 µg/L | 29/30 | SYR4 | 2012–2017 |
| Dibromochloromethane | 22.08 µg/L No EPA limit set
worst single sample: 28 µg/L | 29/33 | SYR4 | 2012–2019 |
| Lead | 0.0020 mg/L 13% of the EPA limit 0.0150 mg/L | 20/20 | LCR | 2025 |
| Monochloroacetic Acid | 8.485 µg/L No EPA limit set
worst single sample: 18.7 µg/L | 19/33 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 5.723 µg/L No EPA limit set
worst single sample: 5.74 µg/L | 18/33 | SYR4 | 2012–2019 |
| Lead | 7.4 µg/L 49% of the EPA limit 15 µg/L
worst single sample: 8 µg/L | 16/30 | SYR4 | 2012–2017 |
| Bromoform | 3.111 µg/L No EPA limit set
worst single sample: 4 µg/L | 15/33 | SYR4 | 2012–2019 |
| Nitrate | 475 µg/L 4.8% of the EPA limit 10000 µg/L | 12/16 | SYR4 | 2012–2019 |
| Fluoride | 844 µg/L 21% of the EPA limit 4000 µg/L
worst single sample: 1000 µg/L | 9/9 | SYR4 | 2012–2019 |
| Barium | 73.65 µg/L 3.7% of the EPA limit 2000 µg/L
worst single sample: 74 µg/L | 8/8 | SYR4 | 2012–2019 |
| Selenium | 1.88 µg/L 3.8% of the EPA limit 50 µg/L
worst single sample: 1.9 µg/L | 5/8 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 3.738 µg/L No EPA limit set
worst single sample: 4 µg/L | 3/33 | SYR4 | 2012–2019 |
| Antimony, Total | 0.2000 µg/L 3.3% of the EPA limit 6 µg/L | 1/8 | SYR4 | 2012–2019 |
| Arsenic | 0.5000 µg/L 5% of the EPA limit 10 µg/L | 1/8 | SYR4 | 2012–2019 |
| Chromium | 1.2 µg/L 1.2% of the EPA limit 100 µg/L | 1/8 | SYR4 | 2012–2019 |
| Gross Alpha, Excl. Radon And U | 0.8640 pCi/L 5.8% of the EPA limit 15 pCi/L | 1/1 | SYR4 | 2013 |
52 contaminants tested, none detected
Utility contact
Frequently asked questions about Kermit Water Works
Is Kermit Water Works tap water safe to drink?
EPA monitoring detected 22 contaminants in Kermit Water Works's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Kermit Water Works's water?
EPA monitoring detected Bromodichloromethane, Chloroform, Dichloroacetic Acid, TTHM, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.
How many people does Kermit Water Works serve?
Kermit Water Works reports serving 1,237 people in West Virginia, per its EPA record.
Has Kermit Water Works had any water quality violations?
The EPA has 651 violations on file for Kermit Water Works, of which 26 are health-based (a contaminant limit or required treatment was breached) and 30 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.