Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2021-12-01 → 2021-12-31 |
| TT | Health-based | Resolved | 2021-12-01 → 2021-12-31 |
| TT | Health-based | Resolved | 2021-12-01 → 2021-12-31 |
| TT | Health-based | Resolved | 2021-12-01 → 2021-12-31 |
| TT | Health-based | Resolved | 2021-07-01 → 2021-09-30 |
| TT | Health-based | Resolved | 2021-07-01 → 2021-09-30 |
| TT | Health-based | Resolved | 2021-07-01 → 2021-09-30 |
| TT | Health-based | Resolved | 2021-07-01 → 2021-09-30 |
| TT | Health-based | Resolved | 2018-07-20 |
| TT | Health-based | Resolved | 2018-07-20 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 207 µg/L 16% of the EPA limit 1300 µg/L
worst single sample: 1800 µg/L | 141/141 | SYR4 | 2014–2019 |
| Lead | 3.6 µg/L 24% of the EPA limit 15 µg/L
worst single sample: 5.4 µg/L | 77/141 | SYR4 | 2014–2019 |
| Chloroform | 50.83 µg/L No EPA limit set
worst single sample: 75.2 µg/L | 54/55 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 28.705 µg/L No EPA limit set
worst single sample: 42.3 µg/L | 54/55 | SYR4 | 2012–2019 |
| TTHM | 60.545 µg/L 76% of the EPA limit 80 µg/L
worst single sample: 92.4 µg/L | 54/55 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 67.21 µg/L 112% of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 88.6 µg/L | 54/55 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 38.02 µg/L No EPA limit set
worst single sample: 49 µg/L | 54/55 | SYR4 | 2012–2019 |
| Bromodichloromethane | 14.28 µg/L No EPA limit set
worst single sample: 15.2 µg/L | 53/55 | SYR4 | 2012–2019 |
| Dibromochloromethane | 2.586 µg/L No EPA limit set
worst single sample: 2.89 µg/L | 37/55 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 3.642 µg/L No EPA limit set
worst single sample: 5.16 µg/L | 22/55 | SYR4 | 2012–2019 |
| Lead | 0.0011 mg/L 7.3% of the EPA limit 0.0150 mg/L | 15/15 | LCR | 2023 |
| Nitrate | 2140 µg/L 21% of the EPA limit 10000 µg/L | 12/16 | SYR4 | 2012–2019 |
| Barium | 57.095 µg/L 2.9% of the EPA limit 2000 µg/L
worst single sample: 60.7 µg/L | 8/8 | SYR4 | 2012–2019 |
| Fluoride | 1007 µg/L 25% of the EPA limit 4000 µg/L
worst single sample: 1010 µg/L | 7/8 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 1.1465 µg/L No EPA limit set
worst single sample: 1.15 µg/L | 2/55 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 2.946 µg/L No EPA limit set
worst single sample: 3.03 µg/L | 2/55 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 827.5 µg/L 8.3% of the EPA limit 10000 µg/L
worst single sample: 840 µg/L | 2/3 | SYR4 | 2016–2019 |
| Arsenic | 1 µg/L 10% of the EPA limit 10 µg/L | 1/8 | SYR4 | 2012–2019 |
| Cyanide | 4 µg/L 2% of the EPA limit 200 µg/L | 1/8 | SYR4 | 2012–2019 |
| Chromium | 11.6 µg/L 12% of the EPA limit 100 µg/L | 1/8 | SYR4 | 2012–2019 |
| Di(2-ethylhexyl) Phthalate | 1.71 µg/L 28% of the EPA limit 6 µg/L | 1/6 | SYR4 | 2012–2019 |
| Picloram | 0.1130 µg/L 0% of the EPA limit 500 µg/L | 1/6 | SYR4 | 2012–2019 |
| Selenium | 1.5 µg/L 3% of the EPA limit 50 µg/L | 1/8 | SYR4 | 2012–2019 |
53 contaminants tested, none detected
Utility contact
Frequently asked questions about Frankfort Psd
Is Frankfort Psd tap water safe to drink?
EPA monitoring detected 23 contaminants in Frankfort Psd's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Frankfort Psd's water?
EPA monitoring detected Copper, Lead, Chloroform, Dichloroacetic Acid, TTHM, and others. The full list with the level and data source for each is above.
How many people does Frankfort Psd serve?
Frankfort Psd reports serving 6,747 people in West Virginia, per its EPA record.
Has Frankfort Psd had any water quality violations?
The EPA has 3921 violations on file for Frankfort Psd, of which 13 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.