← West Virginia

Tap water quality report

Ridgeley, Town of

EPA monitoring tested this supplier for 14 contaminants and detected 12. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

14
contaminants tested
12
detected
737
people served
7
health-based violations
Water source
SWP
Ownership
Local government
Counties served
Mineral

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

7
health-based violations
159
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2008-04-01 → 2008-04-30
MCL Health-based Resolved 2008-04-01 → 2008-04-30
MCL Health-based Resolved 2008-04-01 → 2008-04-30
MCL Health-based Resolved 2008-04-01 → 2008-04-30
TT Health-based Resolved 2004-07-01
TT Health-based Resolved 2004-07-01
TT Health-based Resolved 2004-07-01
Other Monitoring Resolved 2022-11-16
Other Monitoring Resolved 2022-11-16
Other Monitoring Resolved 2022-02-12

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
415.55 µg/L 32%
of the EPA limit 1300 µg/L
worst single sample: 1770 µg/L
30/30 SYR4 2013–2019
Bromodichloromethane
5.7735 µg/L
No EPA limit set
worst single sample: 9.05 µg/L
22/22 SYR4 2013–2019
Chloroform
72.625 µg/L
No EPA limit set
worst single sample: 79.6 µg/L
22/22 SYR4 2013–2019
Dichloroacetic Acid
26.11 µg/L
No EPA limit set
worst single sample: 35.8 µg/L
22/22 SYR4 2013–2019
Lead
3.89 µg/L 26%
of the EPA limit 15 µg/L
worst single sample: 4.4 µg/L
22/30 SYR4 2013–2019
Monochloroacetic Acid
2.9635 µg/L
No EPA limit set
worst single sample: 3.78 µg/L
22/22 SYR4 2013–2019
TTHM
78.345 µg/L 98%
of the EPA limit 80 µg/L
worst single sample: 83.8 µg/L
22/22 SYR4 2013–2019
Total Haloacetic Acids (HAA5)
66.18 µg/L 110%
of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 81.8 µg/L
22/22 SYR4 2013–2019
Trichloroacetic Acid
37.205 µg/L
No EPA limit set
worst single sample: 43.4 µg/L
22/22 SYR4 2013–2019
Lead
0.00010 mg/L 0.7%
of the EPA limit 0.0150 mg/L
19/19 LCR 2024
Dibromochloromethane
0.3780 µg/L
No EPA limit set
worst single sample: 0.3800 µg/L
3/22 SYR4 2013–2019
Monobromoacetic Acid
0.8119 µg/L
No EPA limit set
worst single sample: 0.8200 µg/L
2/22 SYR4 2013–2019
2 contaminants tested, none detected
BromoformDibromoacetic Acid

Utility contact

Contact
SHEPHERD, WILLIAM
Phone
304-738-9400

Frequently asked questions about Ridgeley, Town of

Is Ridgeley, Town of tap water safe to drink?

EPA monitoring detected 12 contaminants in Ridgeley, Town of's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Ridgeley, Town of's water?

EPA monitoring detected Copper, Bromodichloromethane, Chloroform, Dichloroacetic Acid, Lead, and others. The full list with the level and data source for each is above.

How many people does Ridgeley, Town of serve?

Ridgeley, Town of reports serving 737 people in West Virginia, per its EPA record.

Has Ridgeley, Town of had any water quality violations?

The EPA has 159 violations on file for Ridgeley, Town of, of which 7 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.