Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2019-10-26 |
| TT | Health-based | Resolved | 2019-10-26 |
| TT | Health-based | Resolved | 2019-10-26 |
| TT | Health-based | Resolved | 2019-10-26 |
| MCL | Health-based | Resolved | 2013-08-01 → 2013-08-31 |
| MCL | Health-based | Resolved | 2013-08-01 → 2013-08-31 |
| MCL | Health-based | Resolved | 2013-08-01 → 2013-08-31 |
| MCL | Health-based | Resolved | 2013-08-01 → 2013-08-31 |
| TT | Health-based | Resolved | 2011-05-01 → 2011-05-31 |
| TT | Health-based | Resolved | 2011-05-01 → 2011-05-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 526.6 µg/L 41% of the EPA limit 1300 µg/L
worst single sample: 859 µg/L | 80/80 | SYR4 | 2013–2019 |
| Lead | 7.245 µg/L 48% of the EPA limit 15 µg/L
worst single sample: 18.5 µg/L | 78/80 | SYR4 | 2013–2019 |
| Lead | 0.0020 mg/L 13% of the EPA limit 0.0150 mg/L | 21/21 | LCR | 2023 |
| Nitrate | 3380 µg/L 34% of the EPA limit 10000 µg/L | 16/16 | SYR4 | 2012–2019 |
| Bromodichloromethane | 3.12 µg/L No EPA limit set
worst single sample: 3.2 µg/L | 6/6 | SYR4 | 2013–2019 |
| Bromoform | 1.895 µg/L No EPA limit set
worst single sample: 1.9 µg/L | 6/6 | SYR4 | 2013–2019 |
| Dibromoacetic Acid | 4.4525 µg/L No EPA limit set
worst single sample: 4.81 µg/L | 6/6 | SYR4 | 2013–2019 |
| Dibromochloromethane | 4.205 µg/L No EPA limit set
worst single sample: 4.4 µg/L | 6/6 | SYR4 | 2013–2019 |
| TTHM | 10.57 µg/L 13% of the EPA limit 80 µg/L
worst single sample: 11.1 µg/L | 6/6 | SYR4 | 2013–2019 |
| Total Haloacetic Acids (HAA5) | 5.995 µg/L 10% of the EPA limit 60 µg/L
worst single sample: 6.39 µg/L | 6/6 | SYR4 | 2013–2019 |
| Barium | 88.3 µg/L 4.4% of the EPA limit 2000 µg/L
worst single sample: 88.6 µg/L | 5/5 | SYR4 | 2012–2019 |
| Chloroform | 1.5625 µg/L No EPA limit set
worst single sample: 1.6 µg/L | 4/6 | SYR4 | 2013–2019 |
| Fluoride | 211 µg/L 5.3% of the EPA limit 4000 µg/L
worst single sample: 220 µg/L | 4/4 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 2.0955 µg/L No EPA limit set
worst single sample: 2.13 µg/L | 2/6 | SYR4 | 2013–2019 |
| Cyanide | 12 µg/L 6% of the EPA limit 200 µg/L | 1/4 | SYR4 | 2012–2019 |
| Combined Radium (-226 And -228) | 0.6210 pCi/L 12% of the EPA limit 5 pCi/L | 1/1 | SYR4 | 2016 |
| Gross Alpha, Excl. Radon And U | 0.7650 pCi/L 5.1% of the EPA limit 15 pCi/L | 1/2 | SYR4 | 2016–2019 |
| Nitrate-Nitrite | 3340 µg/L 33% of the EPA limit 10000 µg/L | 1/1 | SYR4 | 2019 |
| Nitrite | 490 µg/L 49% of the EPA limit 1000 µg/L | 1/1 | SYR4 | 2019 |
| Trichloroacetic Acid | 0.8780 µg/L No EPA limit set | 1/6 | SYR4 | 2013–2019 |
57 contaminants tested, none detected
Utility contact
Frequently asked questions about Marshall County Psd 2
Is Marshall County Psd 2 tap water safe to drink?
EPA monitoring detected 20 contaminants in Marshall County Psd 2's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Marshall County Psd 2's water?
EPA monitoring detected Copper, Lead, Lead, Nitrate, Bromodichloromethane, and others. The full list with the level and data source for each is above.
How many people does Marshall County Psd 2 serve?
Marshall County Psd 2 reports serving 1,601 people in West Virginia, per its EPA record.
Has Marshall County Psd 2 had any water quality violations?
The EPA has 290 violations on file for Marshall County Psd 2, of which 12 are health-based (a contaminant limit or required treatment was breached) and 8 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.