← West Virginia

Tap water quality report

Enlarged Hepzibah Psd

EPA monitoring tested this supplier for 14 contaminants and detected 12. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

14
contaminants tested
12
detected
1,912
people served
8
health-based violations
Water source
SWP
Ownership
Local government
Counties served
Harrison

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

8
health-based violations
96
violations on file
6
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2002-04-01 → 2002-04-30
MCL Health-based Resolved 2002-04-01 → 2002-04-30
MCL Health-based Resolved 2002-04-01 → 2002-04-30
MCL Health-based Resolved 2002-04-01 → 2002-04-30
MCL Health-based Resolved 2000-06-01 → 2000-06-30
MCL Health-based Resolved 2000-06-01 → 2000-06-30
MCL Health-based Resolved 2000-06-01 → 2000-06-30
MCL Health-based Resolved 2000-06-01 → 2000-06-30
Other Monitoring Unaddressed 2025-10-01
Other Monitoring Unaddressed 2023-08-13

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Chloroform
92.1 µg/L
No EPA limit set
worst single sample: 106 µg/L
31/40 SYR4 2014–2019
TTHM
102.75 µg/L 128%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 114.8 µg/L
31/40 SYR4 2014–2019
Dichloroacetic Acid
24.58 µg/L
No EPA limit set
worst single sample: 38 µg/L
29/40 SYR4 2014–2019
Total Haloacetic Acids (HAA5)
43.92 µg/L 73%
of the EPA limit 60 µg/L
worst single sample: 58.9 µg/L
29/40 SYR4 2014–2019
Copper
33.95 µg/L 2.6%
of the EPA limit 1300 µg/L
worst single sample: 61 µg/L
28/31 SYR4 2012–2018
Trichloroacetic Acid
21.28 µg/L
No EPA limit set
worst single sample: 28.3 µg/L
25/40 SYR4 2014–2019
Bromodichloromethane
11.86 µg/L
No EPA limit set
worst single sample: 13.3 µg/L
24/40 SYR4 2014–2019
Dibromochloromethane
1.725 µg/L
No EPA limit set
worst single sample: 1.8 µg/L
16/40 SYR4 2014–2019
Lead
0.0020 mg/L 13%
of the EPA limit 0.0150 mg/L
16/16 LCR 2023
Lead
3.08 µg/L 21%
of the EPA limit 15 µg/L
worst single sample: 3.5 µg/L
5/31 SYR4 2012–2018
Monochloroacetic Acid
1.28 µg/L
No EPA limit set
worst single sample: 1.3 µg/L
5/40 SYR4 2014–2019
Dibromoacetic Acid
1.07 µg/L
No EPA limit set
worst single sample: 1.1 µg/L
4/40 SYR4 2014–2019
2 contaminants tested, none detected
BromoformMonobromoacetic Acid

Utility contact

Contact
SWIGER, DARLENE
Phone
304-623-9609

Frequently asked questions about Enlarged Hepzibah Psd

Is Enlarged Hepzibah Psd tap water safe to drink?

EPA monitoring detected 12 contaminants in Enlarged Hepzibah Psd's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Enlarged Hepzibah Psd's water?

EPA monitoring detected Chloroform, TTHM, Dichloroacetic Acid, Total Haloacetic Acids (HAA5), Copper, and others. The full list with the level and data source for each is above.

How many people does Enlarged Hepzibah Psd serve?

Enlarged Hepzibah Psd reports serving 1,912 people in West Virginia, per its EPA record.

Has Enlarged Hepzibah Psd had any water quality violations?

The EPA has 96 violations on file for Enlarged Hepzibah Psd, of which 8 are health-based (a contaminant limit or required treatment was breached) and 6 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.