Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2002-10-01 → 2002-12-31 |
| MCL | Health-based | Resolved | 2002-10-01 → 2002-12-31 |
| MCL | Health-based | Resolved | 2002-10-01 → 2002-12-31 |
| MCL | Health-based | Resolved | 2002-10-01 → 2002-12-31 |
| MCL | Health-based | Resolved | 2002-07-01 → 2002-09-30 |
| MCL | Health-based | Resolved | 2002-07-01 → 2002-09-30 |
| MCL | Health-based | Resolved | 2002-07-01 → 2002-09-30 |
| MCL | Health-based | Resolved | 2002-07-01 → 2002-09-30 |
| MR | Monitoring | Resolved | 2024-07-01 |
| MR | Monitoring | Resolved | 2024-07-01 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Bromodichloromethane | 16.45 µg/L No EPA limit set
worst single sample: 33 µg/L | 127/127 | SYR4 | 2012–2019 |
| Chloroform | 83.51 µg/L No EPA limit set
worst single sample: 97 µg/L | 127/127 | SYR4 | 2012–2019 |
| TTHM | 99.54 µg/L 124% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 128.27 µg/L | 127/127 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 34.8 µg/L No EPA limit set
worst single sample: 40.4 µg/L | 126/127 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 67.55 µg/L 113% of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 82.7 µg/L | 126/127 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 35.27 µg/L No EPA limit set
worst single sample: 49.4 µg/L | 124/127 | SYR4 | 2012–2019 |
| Dibromochloromethane | 2.6995 µg/L No EPA limit set
worst single sample: 4.7 µg/L | 122/127 | SYR4 | 2012–2019 |
| Copper | 147 µg/L 11% of the EPA limit 1300 µg/L
worst single sample: 340 µg/L | 91/91 | SYR4 | 2013–2019 |
| Monochloroacetic Acid | 3.826 µg/L No EPA limit set
worst single sample: 5.63 µg/L | 89/127 | SYR4 | 2012–2019 |
| Lead | 11.84 µg/L 79% of the EPA limit 15 µg/L
worst single sample: 44 µg/L | 73/91 | SYR4 | 2013–2019 |
| Nitrate | 829.5 µg/L 8.3% of the EPA limit 10000 µg/L
worst single sample: 870 µg/L | 24/24 | SYR4 | 2012–2019 |
| Lead | 0.0013 mg/L 8.7% of the EPA limit 0.0150 mg/L | 23/23 | LCR | 2026 |
| Dibromoacetic Acid | 1.126 µg/L No EPA limit set
worst single sample: 1.17 µg/L | 9/127 | SYR4 | 2012–2019 |
| Barium | 38.85 µg/L 1.9% of the EPA limit 2000 µg/L
worst single sample: 42 µg/L | 8/8 | SYR4 | 2012–2019 |
| Fluoride | 934 µg/L 23% of the EPA limit 4000 µg/L
worst single sample: 990 µg/L | 8/8 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 3.82 µg/L No EPA limit set
worst single sample: 4.22 µg/L | 5/127 | SYR4 | 2012–2019 |
| Chromium | 1.1 µg/L 1.1% of the EPA limit 100 µg/L | 1/8 | SYR4 | 2012–2019 |
| Di(2-ethylhexyl) Phthalate | 1.42 µg/L 24% of the EPA limit 6 µg/L | 1/14 | SYR4 | 2015–2019 |
| Gross Alpha, Excl. Radon And U | 0.0860 pCi/L 0.6% of the EPA limit 15 pCi/L | 1/1 | SYR4 | 2017 |
56 contaminants tested, none detected
Utility contact
Frequently asked questions about Clarksburg Water Board
Is Clarksburg Water Board tap water safe to drink?
EPA monitoring detected 19 contaminants in Clarksburg Water Board's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Clarksburg Water Board's water?
EPA monitoring detected Bromodichloromethane, Chloroform, TTHM, Dichloroacetic Acid, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.
How many people does Clarksburg Water Board serve?
Clarksburg Water Board reports serving 19,072 people in West Virginia, per its EPA record.
Has Clarksburg Water Board had any water quality violations?
The EPA has 108 violations on file for Clarksburg Water Board, of which 8 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.