Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2020-10-01 → 2020-12-31 |
| MCL | Health-based | Resolved | 2020-10-01 → 2020-12-31 |
| MCL | Health-based | Resolved | 2020-10-01 → 2020-12-31 |
| MCL | Health-based | Resolved | 2020-10-01 → 2020-12-31 |
| MCL | Health-based | Resolved | 2020-07-01 → 2020-09-30 |
| MCL | Health-based | Resolved | 2020-07-01 → 2020-09-30 |
| MCL | Health-based | Resolved | 2020-07-01 → 2020-09-30 |
| MCL | Health-based | Resolved | 2020-07-01 → 2020-09-30 |
| MCL | Health-based | Resolved | 2020-04-01 → 2020-06-30 |
| MCL | Health-based | Resolved | 2020-04-01 → 2020-06-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 503 µg/L 39% of the EPA limit 1300 µg/L
worst single sample: 881 µg/L | 96/97 | SYR4 | 2012–2019 |
| Lead | 27.025 µg/L 180% of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 148 µg/L | 76/97 | SYR4 | 2012–2019 |
| Bromodichloromethane | 8.835 µg/L No EPA limit set
worst single sample: 9.41 µg/L | 32/32 | SYR4 | 2012–2019 |
| TTHM | 259.7 µg/L 325% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 443 µg/L | 32/32 | SYR4 | 2012–2019 |
| Chloroform | 262.5 µg/L No EPA limit set
worst single sample: 436 µg/L | 31/32 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 83.65 µg/L No EPA limit set
worst single sample: 368 µg/L | 31/31 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 143.5 µg/L 239% of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 485.816 µg/L | 31/31 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 58.8 µg/L No EPA limit set
worst single sample: 63.2 µg/L | 29/31 | SYR4 | 2012–2019 |
| Nitrate | 1560 µg/L 16% of the EPA limit 10000 µg/L | 16/16 | SYR4 | 2013–2019 |
| Lead | 0.00023 mg/L 1.5% of the EPA limit 0.0150 mg/L | 15/15 | LCR | 2025 |
| Monochloroacetic Acid | 27.06 µg/L No EPA limit set
worst single sample: 57.3 µg/L | 15/31 | SYR4 | 2012–2019 |
| Dibromochloromethane | 1.282 µg/L No EPA limit set
worst single sample: 1.3 µg/L | 13/32 | SYR4 | 2012–2019 |
| Barium | 30.375 µg/L 1.5% of the EPA limit 2000 µg/L
worst single sample: 33.7 µg/L | 8/8 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 1387.5 µg/L 14% of the EPA limit 10000 µg/L
worst single sample: 1560 µg/L | 6/6 | SYR4 | 2013–2019 |
| Combined Radium (-226 And -228) | 2.0538 pCi/L 41% of the EPA limit 5 pCi/L
worst single sample: 2.38 pCi/L | 5/5 | SYR4 | 2012–2014 |
| Fluoride | 88 µg/L 2.2% of the EPA limit 4000 µg/L
worst single sample: 90 µg/L | 3/8 | SYR4 | 2012–2019 |
| Chromium | 2.065 µg/L 2.1% of the EPA limit 100 µg/L
worst single sample: 2.1 µg/L | 2/8 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 1.27575 µg/L No EPA limit set
worst single sample: 1.32 µg/L | 2/31 | SYR4 | 2012–2019 |
| Gross Alpha, Excl. Radon And U | 0.7612 pCi/L 5.1% of the EPA limit 15 pCi/L
worst single sample: 0.7860 pCi/L | 2/5 | SYR4 | 2012–2019 |
| 2,4-D | 0.3940 µg/L 0.6% of the EPA limit 70 µg/L | 1/8 | SYR4 | 2012–2019 |
| Arsenic | 1.1 µg/L 11% of the EPA limit 10 µg/L | 1/8 | SYR4 | 2012–2019 |
| Cyanide | 44 µg/L 22% of the EPA limit 200 µg/L | 1/8 | SYR4 | 2012–2019 |
| Dalapon | 1.6 µg/L 0.8% of the EPA limit 200 µg/L | 1/8 | SYR4 | 2012–2019 |
| Nitrite | 230 µg/L 23% of the EPA limit 1000 µg/L | 1/6 | SYR4 | 2013–2019 |
| Selenium | 1.3 µg/L 2.6% of the EPA limit 50 µg/L | 1/8 | SYR4 | 2012–2019 |
52 contaminants tested, none detected
Utility contact
Frequently asked questions about Hardy County Psd Baker
Is Hardy County Psd Baker tap water safe to drink?
EPA monitoring detected 25 contaminants in Hardy County Psd Baker's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Hardy County Psd Baker's water?
EPA monitoring detected Copper, Lead, Bromodichloromethane, TTHM, Chloroform, and others. The full list with the level and data source for each is above.
How many people does Hardy County Psd Baker serve?
Hardy County Psd Baker reports serving 150 people in West Virginia, per its EPA record.
Has Hardy County Psd Baker had any water quality violations?
The EPA has 317 violations on file for Hardy County Psd Baker, of which 215 are health-based (a contaminant limit or required treatment was breached) and 1 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.