Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Unaddressed | 2026-01-01 |
| TT | Health-based | Unaddressed | 2026-01-01 |
| TT | Health-based | Unaddressed | 2026-01-01 |
| TT | Health-based | Archived | 2025-02-01 → 2025-02-28 |
| TT | Health-based | Archived | 2025-02-01 → 2025-02-28 |
| TT | Health-based | Archived | 2025-02-01 → 2025-02-28 |
| TT | Health-based | Unaddressed | 2022-09-02 |
| TT | Health-based | Unaddressed | 2022-09-02 |
| TT | Health-based | Unaddressed | 2022-09-02 |
| TT | Health-based | Unaddressed | 2022-09-02 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Dichloroacetic Acid | 34.95 µg/L No EPA limit set
worst single sample: 49.9 µg/L | 48/48 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 76.285 µg/L 127% of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 105 µg/L | 48/48 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 40.045 µg/L No EPA limit set
worst single sample: 49.7 µg/L | 48/48 | SYR4 | 2012–2019 |
| Bromodichloromethane | 11.14 µg/L No EPA limit set
worst single sample: 13.5 µg/L | 47/47 | SYR4 | 2012–2019 |
| Chloroform | 71.01 µg/L No EPA limit set
worst single sample: 83.3 µg/L | 47/47 | SYR4 | 2012–2019 |
| TTHM | 81.87 µg/L 102% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 91.9 µg/L | 47/47 | SYR4 | 2012–2019 |
| Dibromochloromethane | 1.2905 µg/L No EPA limit set
worst single sample: 2.1 µg/L | 40/47 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 4.59 µg/L No EPA limit set
worst single sample: 8.26 µg/L | 36/48 | SYR4 | 2012–2019 |
| Copper | 44.76 µg/L 3.4% of the EPA limit 1300 µg/L
worst single sample: 68.7 µg/L | 29/31 | SYR4 | 2012–2019 |
| Nitrate | 280 µg/L 2.8% of the EPA limit 10000 µg/L | 16/16 | SYR4 | 2012–2019 |
| Lead | 0.0026 mg/L 17% of the EPA limit 0.0150 mg/L | 15/15 | LCR | 2024 |
| Lead | 3.15 µg/L 21% of the EPA limit 15 µg/L
worst single sample: 3.8 µg/L | 11/31 | SYR4 | 2012–2019 |
| Barium | 51.56 µg/L 2.6% of the EPA limit 2000 µg/L
worst single sample: 52.8 µg/L | 9/9 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 0.5100 µg/L No EPA limit set | 1/48 | SYR4 | 2012–2019 |
| Fluoride | 40 µg/L 1% of the EPA limit 4000 µg/L | 1/11 | SYR4 | 2012–2019 |
| Gross Alpha, Excl. Radon And U | 1.28 pCi/L 8.5% of the EPA limit 15 pCi/L | 1/1 | SYR4 | 2013 |
| Nitrate-Nitrite | 190 µg/L 1.9% of the EPA limit 10000 µg/L | 1/1 | SYR4 | 2017 |
59 contaminants tested, none detected
Utility contact
Frequently asked questions about Clay Water Dept
Is Clay Water Dept tap water safe to drink?
EPA monitoring detected 17 contaminants in Clay Water Dept's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Clay Water Dept's water?
EPA monitoring detected Dichloroacetic Acid, Total Haloacetic Acids (HAA5), Trichloroacetic Acid, Bromodichloromethane, Chloroform, and others. The full list with the level and data source for each is above.
How many people does Clay Water Dept serve?
Clay Water Dept reports serving 1,232 people in West Virginia, per its EPA record.
Has Clay Water Dept had any water quality violations?
The EPA has 406 violations on file for Clay Water Dept, of which 55 are health-based (a contaminant limit or required treatment was breached) and 13 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.