Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2018-08-08 |
| TT | Health-based | Resolved | 2018-08-08 |
| TT | Health-based | Resolved | 2018-08-08 |
| TT | Health-based | Resolved | 2018-08-08 |
| MCL | Health-based | Resolved | 2005-04-01 → 2005-06-30 |
| MCL | Health-based | Resolved | 2005-04-01 → 2005-06-30 |
| MCL | Health-based | Resolved | 2005-04-01 → 2005-06-30 |
| MCL | Health-based | Resolved | 2005-04-01 → 2005-06-30 |
| MCL | Health-based | Resolved | 2005-01-01 → 2005-03-31 |
| MCL | Health-based | Resolved | 2005-01-01 → 2005-03-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Bromodichloromethane | 16.545 µg/L No EPA limit set
worst single sample: 17.9 µg/L | 50/50 | SYR4 | 2012–2019 |
| Chloroform | 88.205 µg/L No EPA limit set
worst single sample: 112 µg/L | 50/50 | SYR4 | 2012–2019 |
| TTHM | 108.635 µg/L 136% of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 134.1 µg/L | 50/50 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 29.32 µg/L No EPA limit set
worst single sample: 34.5 µg/L | 49/49 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 61.5 µg/L 102% of the EPA limit, at the 95th percentile of samples — 60 µg/L
worst single sample: 77.6 µg/L | 49/49 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 33.84 µg/L No EPA limit set
worst single sample: 42.9 µg/L | 49/49 | SYR4 | 2012–2019 |
| Dibromochloromethane | 3.775 µg/L No EPA limit set
worst single sample: 4.4 µg/L | 46/50 | SYR4 | 2012–2019 |
| Copper | 68.315 µg/L 5.3% of the EPA limit 1300 µg/L
worst single sample: 113 µg/L | 40/40 | SYR4 | 2014–2017 |
| Monochloroacetic Acid | 10.18 µg/L No EPA limit set
worst single sample: 18.2 µg/L | 37/49 | SYR4 | 2012–2019 |
| Lead | 0.0016 mg/L 11% of the EPA limit 0.0150 mg/L | 17/17 | LCR | 2021 |
| Lead | 2.525 µg/L 17% of the EPA limit 15 µg/L
worst single sample: 4.1 µg/L | 16/40 | SYR4 | 2014–2017 |
| Nitrate | 360 µg/L 3.6% of the EPA limit 10000 µg/L | 16/16 | SYR4 | 2012–2019 |
| Barium | 66.99 µg/L 3.3% of the EPA limit 2000 µg/L
worst single sample: 79.8 µg/L | 8/8 | SYR4 | 2012–2019 |
| Fluoride | 803 µg/L 20% of the EPA limit 4000 µg/L
worst single sample: 880 µg/L | 8/8 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 9.835 µg/L No EPA limit set
worst single sample: 10.2 µg/L | 6/49 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 1.126 µg/L No EPA limit set
worst single sample: 1.14 µg/L | 5/49 | SYR4 | 2012–2019 |
| Bromoform | 0.7000 µg/L No EPA limit set | 2/50 | SYR4 | 2012–2019 |
| Selenium | 1.38 µg/L 2.8% of the EPA limit 50 µg/L
worst single sample: 1.4 µg/L | 2/8 | SYR4 | 2012–2019 |
| Antimony, Total | 0.7000 µg/L 12% of the EPA limit 6 µg/L | 1/8 | SYR4 | 2012–2019 |
| Gross Alpha, Excl. Radon And U | 0.3860 pCi/L 2.6% of the EPA limit 15 pCi/L | 1/2 | SYR4 | 2013–2016 |
| Nitrate-Nitrite | 230 µg/L 2.3% of the EPA limit 10000 µg/L | 1/1 | SYR4 | 2019 |
| Thallium, Total | 0.2000 µg/L 10% of the EPA limit 2 µg/L | 1/8 | SYR4 | 2012–2019 |
54 contaminants tested, none detected
Utility contact
Frequently asked questions about Milton Water
Is Milton Water tap water safe to drink?
EPA monitoring detected 22 contaminants in Milton Water's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Milton Water's water?
EPA monitoring detected Bromodichloromethane, Chloroform, TTHM, Dichloroacetic Acid, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.
How many people does Milton Water serve?
Milton Water reports serving 5,446 people in West Virginia, per its EPA record.
Has Milton Water had any water quality violations?
The EPA has 382 violations on file for Milton Water, of which 24 are health-based (a contaminant limit or required treatment was breached) and 6 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.