← West Virginia

Tap water quality report

Weirton Area Water Board

EPA monitoring tested this supplier for 76 contaminants and detected 25. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

76
contaminants tested
25
detected
18,633
people served
89
health-based violations
Water source
Surface water
Ownership
Local government
Counties served
Brooke

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

89
health-based violations
251
violations on file
0
still open
ViolationTypeStatusPeriod
TT Health-based Archived 2026-01-01 → 2026-01-31
TT Health-based Archived 2026-01-01 → 2026-01-31
TT Health-based Resolved 2017-10-02
TT Health-based Resolved 2017-10-02
TT Health-based Resolved 2017-10-02
TT Health-based Resolved 2017-10-02
MCL Health-based Resolved 2017-07-01 → 2017-09-30
MCL Health-based Resolved 2017-07-01 → 2017-09-30
MCL Health-based Resolved 2017-07-01 → 2017-09-30
MCL Health-based Resolved 2017-07-01 → 2017-09-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
489.95 µg/L 38%
of the EPA limit 1300 µg/L
worst single sample: 835 µg/L
210/210 SYR4 2013–2019
Lead
4.15 µg/L 28%
of the EPA limit 15 µg/L
worst single sample: 63.6 µg/L
151/210 SYR4 2013–2019
Bromodichloromethane
29.63 µg/L
No EPA limit set
worst single sample: 41 µg/L
128/128 SYR4 2012–2019
Chloroform
14.895 µg/L
No EPA limit set
worst single sample: 29.4 µg/L
128/128 SYR4 2012–2019
Dibromoacetic Acid
17.83 µg/L
No EPA limit set
worst single sample: 21.4 µg/L
128/128 SYR4 2012–2019
Dibromochloromethane
44.82 µg/L
No EPA limit set
worst single sample: 65.9 µg/L
128/128 SYR4 2012–2019
Dichloroacetic Acid
9.4965 µg/L
No EPA limit set
worst single sample: 16.6 µg/L
128/128 SYR4 2012–2019
TTHM
107 µg/L 134%
of the EPA limit, at the 95th percentile of samples — 80 µg/L
worst single sample: 136 µg/L
128/128 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
36.4 µg/L 61%
of the EPA limit 60 µg/L
worst single sample: 54.5 µg/L
128/128 SYR4 2012–2019
Bromoform
23.81 µg/L
No EPA limit set
worst single sample: 31.8 µg/L
127/128 SYR4 2012–2019
Trichloroacetic Acid
6.28 µg/L
No EPA limit set
worst single sample: 11.5 µg/L
113/128 SYR4 2012–2019
Monochloroacetic Acid
7.805 µg/L
No EPA limit set
worst single sample: 26.8 µg/L
78/128 SYR4 2012–2019
Monobromoacetic Acid
14.06 µg/L
No EPA limit set
worst single sample: 16.6 µg/L
37/128 SYR4 2012–2019
Lead
0.00074 mg/L 4.9%
of the EPA limit 0.0150 mg/L
18/18 LCR 2024
cis-1,2-Dichloroethylene
9.925 µg/L 14%
of the EPA limit 70 µg/L
worst single sample: 10 µg/L
16/16 SYR4 2012–2019
Trichloroethylene
2.941 µg/L 59%
of the EPA limit 5 µg/L
worst single sample: 5.09 µg/L
15/16 SYR4 2012–2019
Nitrate
770 µg/L 7.7%
of the EPA limit 10000 µg/L
14/14 SYR4 2012–2019
Barium
46.54 µg/L 2.3%
of the EPA limit 2000 µg/L
worst single sample: 47.1 µg/L
8/8 SYR4 2012–2019
Fluoride
966.5 µg/L 24%
of the EPA limit 4000 µg/L
worst single sample: 970 µg/L
8/8 SYR4 2012–2019
1,1,1-Trichloroethane
0.4860 µg/L 0.2%
of the EPA limit 200 µg/L
worst single sample: 0.5000 µg/L
5/16 SYR4 2012–2019
Vinyl Chloride
0.5255 µg/L 26%
of the EPA limit 2 µg/L
worst single sample: 0.5300 µg/L
4/16 SYR4 2012–2019
Gross Alpha, Excl. Radon And U
1.773 pCi/L 12%
of the EPA limit 15 pCi/L
worst single sample: 1.81 pCi/L
2/2 SYR4 2013–2019
Antimony, Total
0.4000 µg/L 6.7%
of the EPA limit 6 µg/L
1/8 SYR4 2012–2019
Nitrate-Nitrite
870 µg/L 8.7%
of the EPA limit 10000 µg/L
1/1 SYR4 2016
Selenium
2.4 µg/L 4.8%
of the EPA limit 50 µg/L
1/8 SYR4 2012–2019
51 contaminants tested, none detected
1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DArsenicAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebEthylene DibromideEndrinEthylbenzeneHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorNitriteOxamylPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneXylenes, TotalO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Contact
SHOCKLEY, JAMES

Frequently asked questions about Weirton Area Water Board

Is Weirton Area Water Board tap water safe to drink?

EPA monitoring detected 25 contaminants in Weirton Area Water Board's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Weirton Area Water Board's water?

EPA monitoring detected Copper, Lead, Bromodichloromethane, Chloroform, Dibromoacetic Acid, and others. The full list with the level and data source for each is above.

How many people does Weirton Area Water Board serve?

Weirton Area Water Board reports serving 18,633 people in West Virginia, per its EPA record.

Has Weirton Area Water Board had any water quality violations?

The EPA has 251 violations on file for Weirton Area Water Board, of which 89 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.