Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 1998-08-01 → 1998-08-31 |
| MCL | Health-based | Resolved | 1998-08-01 → 1998-08-31 |
| MCL | Health-based | Resolved | 1998-08-01 → 1998-08-31 |
| MCL | Health-based | Resolved | 1998-08-01 → 1998-08-31 |
| Other | Monitoring | Unaddressed | 2025-11-15 |
| Other | Monitoring | Unaddressed | 2025-11-14 |
| MR | Monitoring | Archived | 2025-01-01 → 2025-12-31 |
| MR | Monitoring | Archived | 2025-01-01 → 2025-12-31 |
| MR | Monitoring | Archived | 2025-01-01 → 2025-12-31 |
| MR | Monitoring | Archived | 2025-01-01 → 2025-12-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 5590 µg/L 56% of the EPA limit 10000 µg/L
worst single sample: 7100 µg/L | 48/48 | SYR4 | 2012–2019 |
| Copper | 158.4 µg/L 12% of the EPA limit 1300 µg/L
worst single sample: 308 µg/L | 27/30 | SYR4 | 2012–2018 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 15/15 | LCR | 2025 |
| Lead | 31.2 µg/L 208% of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 42 µg/L | 9/30 | SYR4 | 2012–2018 |
| TTHM | 5.58 µg/L 7% of the EPA limit 80 µg/L
worst single sample: 5.7 µg/L | 4/7 | SYR4 | 2013–2019 |
| Total Haloacetic Acids (HAA5) | 4.19 µg/L 7% of the EPA limit 60 µg/L
worst single sample: 4.7 µg/L | 4/7 | SYR4 | 2013–2019 |
| Barium | 68.1 µg/L 3.4% of the EPA limit 2000 µg/L
worst single sample: 69 µg/L | 3/3 | SYR4 | 2013–2019 |
| Bromodichloromethane | 2.24 µg/L No EPA limit set
worst single sample: 2.3 µg/L | 3/7 | SYR4 | 2013–2019 |
| Chloroform | 5.26 µg/L No EPA limit set
worst single sample: 5.7 µg/L | 3/7 | SYR4 | 2013–2019 |
| Dibromochloromethane | 2.11 µg/L No EPA limit set
worst single sample: 2.2 µg/L | 3/7 | SYR4 | 2013–2019 |
| Fluoride | 777 µg/L 19% of the EPA limit 4000 µg/L
worst single sample: 820 µg/L | 3/3 | SYR4 | 2013–2019 |
| Nitrate-Nitrite | 5093 µg/L 51% of the EPA limit 10000 µg/L
worst single sample: 5140 µg/L | 3/3 | SYR4 | 2016–2019 |
| Dibromoacetic Acid | 0.7950 µg/L No EPA limit set
worst single sample: 0.8000 µg/L | 2/7 | SYR4 | 2013–2019 |
| Dichloroacetic Acid | 3.76 µg/L No EPA limit set
worst single sample: 3.9 µg/L | 2/7 | SYR4 | 2013–2019 |
| Trichloroacetic Acid | 0.7850 µg/L No EPA limit set
worst single sample: 0.8000 µg/L | 2/7 | SYR4 | 2013–2019 |
| Chromium | 1.7 µg/L 1.7% of the EPA limit 100 µg/L | 1/3 | SYR4 | 2013–2019 |
| Gross Alpha, Excl. Radon And U | 2.14 pCi/L 14% of the EPA limit 15 pCi/L | 1/2 | SYR4 | 2013–2019 |
60 contaminants tested, none detected
Utility contact
Frequently asked questions about Rocky Glen Manufactured Housing Communit
Is Rocky Glen Manufactured Housing Communit tap water safe to drink?
EPA monitoring detected 17 contaminants in Rocky Glen Manufactured Housing Communit's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Rocky Glen Manufactured Housing Communit's water?
EPA monitoring detected Nitrate, Copper, Lead, Lead, TTHM, and others. The full list with the level and data source for each is above.
How many people does Rocky Glen Manufactured Housing Communit serve?
Rocky Glen Manufactured Housing Communit reports serving 861 people in West Virginia, per its EPA record.
Has Rocky Glen Manufactured Housing Communit had any water quality violations?
The EPA has 84 violations on file for Rocky Glen Manufactured Housing Communit, of which 4 are health-based (a contaminant limit or required treatment was breached) and 5 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.