← Wisconsin

Tap water quality report

Mauston Waterworks

EPA monitoring tested this supplier for 74 contaminants and detected 19. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

74
contaminants tested
19
detected
4,456
people served
5
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Juneau

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

5
health-based violations
13
violations on file
1
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 2024-10-17
MCL Health-based Resolved 1993-08-01 → 1993-08-31
MCL Health-based Resolved 1993-08-01 → 1993-08-31
MCL Health-based Resolved 1993-08-01 → 1993-08-31
MCL Health-based Resolved 1993-08-01 → 1993-08-31
Other Monitoring Unaddressed 2024-10-17
MR Monitoring Resolved 2021-02-01
MR Monitoring Resolved 2021-02-01
MR Monitoring Resolved 1993-01-01 → 1993-08-24
MR Monitoring Resolved 1993-01-01 → 1993-08-24

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Fluoride
1169.5 µg/L 29%
of the EPA limit 4000 µg/L
worst single sample: 1220 µg/L
102/200 SYR4 2012–2019
Nitrate
3460 µg/L 35%
of the EPA limit 10000 µg/L
worst single sample: 3940 µg/L
48/48 SYR4 2012–2019
Copper
265.45 µg/L 20%
of the EPA limit 1300 µg/L
worst single sample: 422 µg/L
28/40 SYR4 2014–2017
Lead
0.00094 mg/L 6.3%
of the EPA limit 0.0150 mg/L
21/21 LCR 2023
Lead
106.125 µg/L 708%
of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 280 µg/L
14/40 SYR4 2014–2017
Barium
34.35 µg/L 1.7%
of the EPA limit 2000 µg/L
worst single sample: 37.4 µg/L
6/6 SYR4 2014–2017
Monochloroacetic Acid
13.6175 µg/L
No EPA limit set
worst single sample: 16 µg/L
6/6 SYR4 2014–2019
Nitrate-Nitrite
2717.5 µg/L 27%
of the EPA limit 10000 µg/L
worst single sample: 3140 µg/L
6/6 SYR4 2014–2017
Total Haloacetic Acids (HAA5)
16.0308 µg/L 27%
of the EPA limit 60 µg/L
worst single sample: 19.105 µg/L
6/6 SYR4 2014–2019
Bromodichloromethane
2.738 µg/L
No EPA limit set
worst single sample: 2.95 µg/L
5/6 SYR4 2014–2019
Chloroform
1.574 µg/L
No EPA limit set
worst single sample: 1.62 µg/L
5/6 SYR4 2014–2019
TTHM
11.6424 µg/L 15%
of the EPA limit 80 µg/L
worst single sample: 12.868 µg/L
5/6 SYR4 2014–2019
Combined Radium (-226 And -228)
3.8025 pCi/L 76%
of the EPA limit 5 pCi/L
worst single sample: 4.17 pCi/L
4/4 SYR4 2014–2017
Dibromochloromethane
4.8665 µg/L
No EPA limit set
worst single sample: 5.33 µg/L
4/6 SYR4 2014–2019
Gross Alpha, Excl. Radon And U
5.935 pCi/L 40%
of the EPA limit 15 pCi/L
worst single sample: 6.1 pCi/L
4/4 SYR4 2014–2017
Bromoform
3.565 µg/L
No EPA limit set
worst single sample: 3.78 µg/L
3/6 SYR4 2014–2019
Combined Uranium
0.7200 µg/L 2.4%
of the EPA limit 30 µg/L
1/1 SYR4 2017
Selenium
1 µg/L 2%
of the EPA limit 50 µg/L
1/6 SYR4 2014–2017
Trichloroacetic Acid
2.44 µg/L
No EPA limit set
1/6 SYR4 2014–2019
55 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalArsenicAtrazineBhc-GammaBenzeneBeryllium, TotalChlorobenzeneCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumDichloromethaneDalaponDibromoacetic AcidDichloroacetic AcidDinosebDiquatEndothallEndrinEthylbenzeneGlyphosateHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidNitriteOxamylPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneThallium, TotalTolueneToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Frequently asked questions about Mauston Waterworks

Is Mauston Waterworks tap water safe to drink?

EPA monitoring detected 19 contaminants in Mauston Waterworks's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Mauston Waterworks's water?

EPA monitoring detected Fluoride, Nitrate, Copper, Lead, Lead, and others. The full list with the level and data source for each is above.

How many people does Mauston Waterworks serve?

Mauston Waterworks reports serving 4,456 people in Wisconsin, per its EPA record.

Has Mauston Waterworks had any water quality violations?

The EPA has 13 violations on file for Mauston Waterworks, of which 5 are health-based (a contaminant limit or required treatment was breached) and 1 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.