← Wisconsin

Tap water quality report

Menasha Elec & Water Util

EPA monitoring tested this supplier for 77 contaminants and detected 18. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

77
contaminants tested
18
detected
15,144
people served
0
health-based violations
Water source
Surface water
Ownership
Local government
Counties served
Winnebago

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

0
health-based violations
18
violations on file
1
still open
ViolationTypeStatusPeriod
Other Monitoring Unaddressed 2015-02-16
MR Monitoring Resolved 2015-01-01 → 2015-03-31
MR Monitoring Resolved 2015-01-01 → 2015-03-31
MR Monitoring Resolved 2015-01-01 → 2015-03-31
MR Monitoring Resolved 2015-01-01 → 2015-03-31
MR Monitoring Resolved 2015-01-01 → 2015-03-31
MR Monitoring Resolved 2015-01-01 → 2015-03-31
MR Monitoring Resolved 2015-01-01 → 2015-03-31
MR Monitoring Resolved 2015-01-01 → 2015-03-31
MR Monitoring Resolved 2014-10-01 → 2014-12-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Bromodichloromethane
5.4 µg/L
No EPA limit set
worst single sample: 5.8 µg/L
135/135 SYR4 2012–2019
Chloroform
32 µg/L
No EPA limit set
worst single sample: 38 µg/L
135/135 SYR4 2012–2019
Dichloroacetic Acid
19 µg/L
No EPA limit set
worst single sample: 20 µg/L
127/127 SYR4 2012–2019
TTHM
36.99 µg/L 46%
of the EPA limit 80 µg/L
worst single sample: 43.1 µg/L
127/127 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
32.21 µg/L 54%
of the EPA limit 60 µg/L
worst single sample: 37.1 µg/L
127/127 SYR4 2012–2019
Trichloroacetic Acid
13 µg/L
No EPA limit set
worst single sample: 14 µg/L
127/127 SYR4 2012–2019
Copper
190 µg/L 15%
of the EPA limit 1300 µg/L
worst single sample: 630 µg/L
120/122 SYR4 2014–2018
Lead
24.2 µg/L 161%
of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 38 µg/L
117/122 SYR4 2014–2018
Fluoride
890 µg/L 22%
of the EPA limit 4000 µg/L
worst single sample: 1000 µg/L
101/200 SYR4 2012–2019
Lead
0.0011 mg/L 7.3%
of the EPA limit 0.0150 mg/L
16/16 LCR 2023
Monochloroacetic Acid
3.375 µg/L
No EPA limit set
worst single sample: 3.6 µg/L
16/127 SYR4 2012–2019
Nitrate-Nitrite
900 µg/L 9%
of the EPA limit 10000 µg/L
16/16 SYR4 2012–2019
Dibromochloromethane
0.8265 µg/L
No EPA limit set
worst single sample: 0.9300 µg/L
10/135 SYR4 2012–2019
Barium
19.6 µg/L 1%
of the EPA limit 2000 µg/L
worst single sample: 21 µg/L
8/8 SYR4 2012–2019
Dibromoacetic Acid
0.3220 µg/L
No EPA limit set
worst single sample: 0.3700 µg/L
5/127 SYR4 2012–2019
Combined Radium (-226 And -228)
1.45 pCi/L 29%
of the EPA limit 5 pCi/L
1/1 SYR4 2014
Mercury
0.2500 µg/L 13%
of the EPA limit 2 µg/L
1/8 SYR4 2012–2019
Selenium
6.8 µg/L 14%
of the EPA limit 50 µg/L
1/8 SYR4 2012–2019
59 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-Dichloropropane2,3,7,8-TCDD2,4,5-TP2,4-DAntimony, TotalArsenicAtrazineBhc-GammaBenzeneBenzo(A)PyreneBeryllium, TotalBromoformChlorobenzeneCyanideCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDinosebDiquatEndothallEndrinEthylbenzeneGlyphosateHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMethoxychlorMonobromoacetic AcidNitriteOxamylPentachlorophenolPicloramSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Frequently asked questions about Menasha Elec & Water Util

Is Menasha Elec & Water Util tap water safe to drink?

EPA monitoring detected 18 contaminants in Menasha Elec & Water Util's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Menasha Elec & Water Util's water?

EPA monitoring detected Bromodichloromethane, Chloroform, Dichloroacetic Acid, TTHM, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.

How many people does Menasha Elec & Water Util serve?

Menasha Elec & Water Util reports serving 15,144 people in Wisconsin, per its EPA record.

Has Menasha Elec & Water Util had any water quality violations?

The EPA has 18 violations on file for Menasha Elec & Water Util, of which 0 are health-based (a contaminant limit or required treatment was breached) and 1 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.