← Wisconsin

Tap water quality report

Weyauwega Waterworks

EPA monitoring tested this supplier for 75 contaminants and detected 16. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

75
contaminants tested
16
detected
1,820
people served
5
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Waupaca

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

5
health-based violations
203
violations on file
0
still open
ViolationTypeStatusPeriod
TT Health-based Resolved 1994-01-01
MCL Health-based Resolved 1993-09-01 → 1993-09-30
MCL Health-based Resolved 1993-09-01 → 1993-09-30
MCL Health-based Resolved 1993-09-01 → 1993-09-30
MCL Health-based Resolved 1993-09-01 → 1993-09-30
MR Monitoring Resolved 2023-01-01 → 2023-12-31
MR Monitoring Resolved 2023-01-01 → 2023-12-31
MR Monitoring Resolved 2023-01-01 → 2023-12-31
MR Monitoring Resolved 2023-01-01 → 2023-12-31
MR Monitoring Resolved 2023-01-01 → 2023-12-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
3627.5 µg/L 36%
of the EPA limit 10000 µg/L
worst single sample: 3770 µg/L
40/40 SYR4 2012–2019
Copper
612.6 µg/L 47%
of the EPA limit 1300 µg/L
worst single sample: 618 µg/L
19/20 SYR4 2014–2017
Lead
0.0060 mg/L 40%
of the EPA limit 0.0150 mg/L
15/15 LCR 2023
TTHM
8.498 µg/L 11%
of the EPA limit 80 µg/L
worst single sample: 9.32 µg/L
7/7 SYR4 2013–2019
Barium
25.45 µg/L 1.3%
of the EPA limit 2000 µg/L
worst single sample: 25.8 µg/L
6/6 SYR4 2014–2017
Chloroform
1.7975 µg/L
No EPA limit set
worst single sample: 1.96 µg/L
6/13 SYR4 2013–2019
Dibromochloromethane
2.9875 µg/L
No EPA limit set
worst single sample: 3.13 µg/L
6/13 SYR4 2013–2019
Nitrate-Nitrite
3280 µg/L 33%
of the EPA limit 10000 µg/L
worst single sample: 3300 µg/L
6/6 SYR4 2014–2017
Total Haloacetic Acids (HAA5)
5.43325 µg/L 9.1%
of the EPA limit 60 µg/L
worst single sample: 5.796 µg/L
6/7 SYR4 2013–2019
Bromodichloromethane
2.53 µg/L
No EPA limit set
worst single sample: 2.67 µg/L
5/13 SYR4 2013–2019
Monochloroacetic Acid
4.422 µg/L
No EPA limit set
worst single sample: 4.62 µg/L
5/7 SYR4 2013–2019
Lead
9.575 µg/L 64%
of the EPA limit 15 µg/L
worst single sample: 10.1 µg/L
4/20 SYR4 2014–2017
Bromoform
1.623 µg/L
No EPA limit set
worst single sample: 1.63 µg/L
3/13 SYR4 2013–2019
Combined Radium (-226 And -228)
1.568 pCi/L 31%
of the EPA limit 5 pCi/L
worst single sample: 1.57 pCi/L
3/3 SYR4 2014
Dibromoacetic Acid
0.7803 µg/L
No EPA limit set
worst single sample: 0.8000 µg/L
2/7 SYR4 2013–2019
Gross Alpha, Excl. Radon And U
1.195 pCi/L 8%
of the EPA limit 15 pCi/L
worst single sample: 1.2 pCi/L
2/2 SYR4 2014
59 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalArsenicAtrazineBhc-GammaBenzeneBeryllium, TotalChlorobenzeneCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumDichloromethaneDalaponDi(2-ethylhexyl) AdipateDi(2-ethylhexyl) PhthalateDichloroacetic AcidDinosebDiquatEndothallEndrinEthylbenzeneFluorideGlyphosateHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidNitriteOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneToxapheneTrichloroacetic AcidTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Frequently asked questions about Weyauwega Waterworks

Is Weyauwega Waterworks tap water safe to drink?

EPA monitoring detected 16 contaminants in Weyauwega Waterworks's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Weyauwega Waterworks's water?

EPA monitoring detected Nitrate, Copper, Lead, TTHM, Barium, and others. The full list with the level and data source for each is above.

How many people does Weyauwega Waterworks serve?

Weyauwega Waterworks reports serving 1,820 people in Wisconsin, per its EPA record.

Has Weyauwega Waterworks had any water quality violations?

The EPA has 203 violations on file for Weyauwega Waterworks, of which 5 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.