← Wisconsin

Tap water quality report

Sheboygan Falls Utilities

EPA monitoring tested this supplier for 14 contaminants and detected 13. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

14
contaminants tested
13
detected
8,687
people served
11
health-based violations
Water source
SWP
Ownership
Local government
Counties served
Sheboygan

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

11
health-based violations
26
violations on file
1
still open
ViolationTypeStatusPeriod
MCL Health-based Archived 2001-09-01 → 2001-09-30
MCL Health-based Archived 2001-09-01 → 2001-09-30
MCL Health-based Archived 2001-09-01 → 2001-09-30
MCL Health-based Archived 2001-09-01 → 2001-09-30
MCL Health-based Archived 2001-09-01 → 2001-09-30
MCL Health-based Resolved 1995-09-01 → 1995-09-30
MCL Health-based Resolved 1995-09-01 → 1995-09-30
MCL Health-based Resolved 1995-09-01 → 1995-09-30
MCL Health-based Resolved 1995-09-01 → 1995-09-30
MCL Health-based Resolved 1995-09-01 → 1995-09-30

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Bromodichloromethane
16.25 µg/L
No EPA limit set
worst single sample: 19 µg/L
56/56 SYR4 2012–2019
Chloroform
44.25 µg/L
No EPA limit set
worst single sample: 54 µg/L
56/56 SYR4 2012–2019
Dibromochloromethane
6.675 µg/L
No EPA limit set
worst single sample: 8.4 µg/L
56/56 SYR4 2012–2019
TTHM
64.325 µg/L 80%
of the EPA limit 80 µg/L
worst single sample: 78.2 µg/L
56/56 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
26 µg/L 43%
of the EPA limit 60 µg/L
worst single sample: 40.45 µg/L
56/56 SYR4 2012–2019
Dichloroacetic Acid
13 µg/L
No EPA limit set
worst single sample: 16 µg/L
53/56 SYR4 2012–2019
Trichloroacetic Acid
14.6 µg/L
No EPA limit set
worst single sample: 23 µg/L
53/56 SYR4 2012–2019
Copper
258.5 µg/L 20%
of the EPA limit 1300 µg/L
worst single sample: 547 µg/L
39/61 SYR4 2012–2018
Dibromoacetic Acid
1 µg/L
No EPA limit set
worst single sample: 1.2 µg/L
36/56 SYR4 2012–2019
Lead
0.0054 mg/L 36%
of the EPA limit 0.0150 mg/L
15/15 LCR 2023
Monobromoacetic Acid
0.8850 µg/L
No EPA limit set
worst single sample: 0.9300 µg/L
10/56 SYR4 2012–2019
Lead
9.7275 µg/L 65%
of the EPA limit 15 µg/L
worst single sample: 10.47 µg/L
6/61 SYR4 2012–2018
Bromoform
0.5800 µg/L
No EPA limit set
1/56 SYR4 2012–2019
1 contaminants tested, none detected
Monochloroacetic Acid

Utility contact

Frequently asked questions about Sheboygan Falls Utilities

Is Sheboygan Falls Utilities tap water safe to drink?

EPA monitoring detected 13 contaminants in Sheboygan Falls Utilities's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Sheboygan Falls Utilities's water?

EPA monitoring detected Bromodichloromethane, Chloroform, Dibromochloromethane, TTHM, Total Haloacetic Acids (HAA5), and others. The full list with the level and data source for each is above.

How many people does Sheboygan Falls Utilities serve?

Sheboygan Falls Utilities reports serving 8,687 people in Wisconsin, per its EPA record.

Has Sheboygan Falls Utilities had any water quality violations?

The EPA has 26 violations on file for Sheboygan Falls Utilities, of which 11 are health-based (a contaminant limit or required treatment was breached) and 1 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.