← Wisconsin

Tap water quality report

Bowler Waterworks

EPA monitoring tested this supplier for 73 contaminants and detected 16. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

73
contaminants tested
16
detected
357
people served
41
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Shawano

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

41
health-based violations
79
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2012-10-01 → 2012-12-31
MCL Health-based Resolved 2012-10-01 → 2012-12-31
MCL Health-based Resolved 2012-10-01 → 2012-12-31
MCL Health-based Resolved 2012-10-01 → 2012-12-31
MCL Health-based Resolved 2012-10-01 → 2012-12-31
MCL Health-based Resolved 2012-10-01 → 2012-12-31
MCL Health-based Resolved 2012-10-01 → 2012-12-31
MCL Health-based Resolved 2012-10-01 → 2012-12-31
MCL Health-based Resolved 2012-10-01 → 2012-12-31
MCL Health-based Resolved 2012-10-01 → 2012-12-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Nitrate
18200 µg/L 182%
of the EPA limit, at the 95th percentile of samples — 10000 µg/L
worst single sample: 24000 µg/L
176/176 SYR4 2012–2019
Lead
0.00025 mg/L 1.7%
of the EPA limit 0.0150 mg/L
14/14 LCR 2023
Copper
91.25 µg/L 7%
of the EPA limit 1300 µg/L
worst single sample: 98 µg/L
10/10 SYR4 2014–2017
Lead
1.1 µg/L 7.3%
of the EPA limit 15 µg/L
6/10 SYR4 2014–2017
Bromodichloromethane
6.46 µg/L
No EPA limit set
worst single sample: 6.6 µg/L
5/5 SYR4 2013–2019
Chloroform
37.8 µg/L
No EPA limit set
worst single sample: 40 µg/L
5/5 SYR4 2013–2019
Dibromochloromethane
0.8260 µg/L
No EPA limit set
worst single sample: 0.8400 µg/L
3/5 SYR4 2013–2019
Dichloroacetic Acid
10.36 µg/L
No EPA limit set
worst single sample: 11 µg/L
3/3 SYR4 2013–2019
TTHM
45.966 µg/L 57%
of the EPA limit 80 µg/L
worst single sample: 47.44 µg/L
3/3 SYR4 2013–2019
Total Haloacetic Acids (HAA5)
20.067 µg/L 33%
of the EPA limit 60 µg/L
worst single sample: 21.23 µg/L
3/3 SYR4 2013–2019
Trichloroacetic Acid
8.95 µg/L
No EPA limit set
worst single sample: 9.3 µg/L
3/3 SYR4 2013–2019
Arsenic
1.3 µg/L 13%
of the EPA limit 10 µg/L
2/2 SYR4 2014–2017
Barium
12.95 µg/L 0.6%
of the EPA limit 2000 µg/L
worst single sample: 13 µg/L
2/2 SYR4 2014–2017
Fluoride
169 µg/L 4.2%
of the EPA limit 4000 µg/L
worst single sample: 170 µg/L
2/2 SYR4 2014–2017
Nitrate-Nitrite
2000 µg/L 20%
of the EPA limit 10000 µg/L
2/2 SYR4 2014–2017
Combined Radium (-226 And -228)
1.45 pCi/L 29%
of the EPA limit 5 pCi/L
1/1 SYR4 2014
57 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalAtrazineBhc-GammaBenzeneBeryllium, TotalBromoformChlorobenzeneCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumDichloromethaneDalaponDibromoacetic AcidDinosebDiquatEndothallEndrinEthylbenzeneGlyphosateHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidMonochloroacetic AcidNitriteOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneThallium, TotalTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneTrichloroethyleneVinyl ChlorideXylenes, Totalcis-1,2-DichloroethyleneO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Utility contact

Frequently asked questions about Bowler Waterworks

Is Bowler Waterworks tap water safe to drink?

EPA monitoring detected 16 contaminants in Bowler Waterworks's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in Bowler Waterworks's water?

EPA monitoring detected Nitrate, Lead, Copper, Lead, Bromodichloromethane, and others. The full list with the level and data source for each is above.

How many people does Bowler Waterworks serve?

Bowler Waterworks reports serving 357 people in Wisconsin, per its EPA record.

Has Bowler Waterworks had any water quality violations?

The EPA has 79 violations on file for Bowler Waterworks, of which 41 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.