Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2024-10-17 |
| TT | Health-based | Resolved | 2024-10-17 |
| MCL | Health-based | Resolved | 2008-01-01 → 2009-04-22 |
| MCL | Health-based | Resolved | 2008-01-01 → 2009-04-22 |
| MCL | Health-based | Resolved | 2008-01-01 → 2009-04-22 |
| MCL | Health-based | Resolved | 2008-01-01 → 2008-12-31 |
| MCL | Health-based | Resolved | 2008-01-01 → 2008-12-31 |
| MCL | Health-based | Resolved | 2008-01-01 → 2008-12-31 |
| MCL | Health-based | Resolved | 2008-01-01 → 2008-12-31 |
| MCL | Health-based | Resolved | 2008-01-01 → 2010-01-15 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 789.5 µg/L 61% of the EPA limit 1300 µg/L
worst single sample: 1700 µg/L | 422/422 | SYR4 | 2014–2019 |
| Lead | 15 µg/L 100% of the EPA limit 15 µg/L
worst single sample: 53 µg/L | 422/422 | SYR4 | 2014–2019 |
| Bromoform | 35.6 µg/L No EPA limit set
worst single sample: 51 µg/L | 129/162 | SYR4 | 2012–2019 |
| Gross Alpha, Excl. Radon And U | 17.84 pCi/L 119% of the EPA limit, at the 95th percentile of samples — 15 pCi/L
worst single sample: 24 pCi/L | 129/129 | SYR4 | 2012–2019 |
| Dibromochloromethane | 9.88 µg/L No EPA limit set
worst single sample: 16 µg/L | 122/162 | SYR4 | 2012–2019 |
| Combined Radium (-226 And -228) | 12.108 pCi/L 242% of the EPA limit, at the 95th percentile of samples — 5 pCi/L
worst single sample: 23.74 pCi/L | 114/114 | SYR4 | 2012–2019 |
| TTHM | 46.761 µg/L 58% of the EPA limit 80 µg/L
worst single sample: 60.67 µg/L | 98/98 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 8.832 µg/L 15% of the EPA limit 60 µg/L
worst single sample: 108.6 µg/L | 98/98 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 6.6 µg/L No EPA limit set
worst single sample: 9.2 µg/L | 97/98 | SYR4 | 2012–2019 |
| Bromodichloromethane | 2.99 µg/L No EPA limit set
worst single sample: 3.6 µg/L | 83/162 | SYR4 | 2012–2019 |
| Fluoride | 982.4 µg/L 25% of the EPA limit 4000 µg/L
worst single sample: 1030 µg/L | 75/141 | SYR4 | 2012–2018 |
| Combined Uranium | 1.672 µg/L 5.6% of the EPA limit 30 µg/L
worst single sample: 1.84 µg/L | 59/59 | SYR4 | 2014–2019 |
| Monobromoacetic Acid | 1.53 µg/L No EPA limit set
worst single sample: 2.1 µg/L | 55/98 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 0.7740 µg/L No EPA limit set
worst single sample: 13 µg/L | 37/98 | SYR4 | 2012–2019 |
| Lead | 0.0061 mg/L 41% of the EPA limit 0.0150 mg/L | 25/25 | LCR | 2025 |
| Nitrate | 148.5 µg/L 1.5% of the EPA limit 10000 µg/L
worst single sample: 150 µg/L | 24/50 | SYR4 | 2012–2019 |
| Arsenic | 4.44 µg/L 44% of the EPA limit 10 µg/L
worst single sample: 4.6 µg/L | 17/34 | SYR4 | 2012–2018 |
| Barium | 51.8 µg/L 2.6% of the EPA limit 2000 µg/L
worst single sample: 61 µg/L | 9/9 | SYR4 | 2014–2017 |
| Nitrate-Nitrite | 110 µg/L 1.1% of the EPA limit 10000 µg/L | 5/9 | SYR4 | 2014–2017 |
| Trichloroacetic Acid | 0.2750 µg/L No EPA limit set
worst single sample: 0.2800 µg/L | 3/98 | SYR4 | 2012–2019 |
| Chloroform | 1.1845 µg/L No EPA limit set
worst single sample: 1.2 µg/L | 2/162 | SYR4 | 2012–2019 |
| Antimony, Total | 1.3 µg/L 22% of the EPA limit 6 µg/L | 1/9 | SYR4 | 2014–2017 |
| Monochloroacetic Acid | 93 µg/L No EPA limit set | 1/98 | SYR4 | 2012–2019 |
| Toluene | 0.6800 µg/L 0.1% of the EPA limit 1000 µg/L | 1/65 | SYR4 | 2012–2019 |
| Xylenes, Total | 3.2 µg/L 0% of the EPA limit 10000 µg/L | 1/64 | SYR4 | 2012–2019 |
52 contaminants tested, none detected
Frequently asked questions about Fond Du Lac Waterworks
Is Fond Du Lac Waterworks tap water safe to drink?
EPA monitoring detected 25 contaminants in Fond Du Lac Waterworks's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Fond Du Lac Waterworks's water?
EPA monitoring detected Copper, Lead, Bromoform, Gross Alpha, Excl. Radon And U, Dibromochloromethane, and others. The full list with the level and data source for each is above.
How many people does Fond Du Lac Waterworks serve?
Fond Du Lac Waterworks reports serving 44,678 people, per its EPA record.
Has Fond Du Lac Waterworks had any water quality violations?
The EPA has 369 violations on file for Fond Du Lac Waterworks, of which 91 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.