Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Archived | 2026-01-01 → 2026-03-31 |
| MCL | Health-based | Archived | 2026-01-01 → 2026-03-31 |
| MCL | Health-based | Archived | 2026-01-01 → 2026-03-31 |
| MCL | Health-based | Archived | 2025-10-01 → 2025-12-31 |
| MCL | Health-based | Archived | 2025-10-01 → 2025-12-31 |
| MCL | Health-based | Archived | 2025-10-01 → 2025-12-31 |
| MCL | Health-based | Archived | 2025-07-01 → 2025-09-30 |
| MCL | Health-based | Archived | 2025-07-01 → 2025-09-30 |
| MCL | Health-based | Archived | 2025-07-01 → 2025-09-30 |
| MCL | Health-based | Archived | 2025-04-01 → 2025-06-30 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 860.5 µg/L 66% of the EPA limit 1300 µg/L
worst single sample: 1800 µg/L | 174/177 | SYR4 | 2012–2019 |
| Lead | 16.05 µg/L 107% of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 120 µg/L | 140/177 | SYR4 | 2012–2019 |
| Fluoride | 745.6 µg/L 19% of the EPA limit 4000 µg/L
worst single sample: 870 µg/L | 103/199 | SYR4 | 2012–2019 |
| Combined Radium (-226 And -228) | 5.3325 pCi/L 107% of the EPA limit, at the 95th percentile of samples — 5 pCi/L
worst single sample: 6.18 pCi/L | 46/46 | SYR4 | 2012–2019 |
| Gross Alpha, Excl. Radon And U | 14.2633 pCi/L 95% of the EPA limit 15 pCi/L
worst single sample: 18.42 pCi/L | 46/46 | SYR4 | 2012–2019 |
| Combined Uranium | 2.354 µg/L 7.8% of the EPA limit 30 µg/L
worst single sample: 2.72 µg/L | 29/29 | SYR4 | 2012–2019 |
| Lead | 0.0 mg/L 0% of the EPA limit 0.0150 mg/L | 23/23 | LCR | 2024 |
| Nitrate | 210 µg/L 2.1% of the EPA limit 10000 µg/L | 12/42 | SYR4 | 2012–2019 |
| Bromodichloromethane | 3.035 µg/L No EPA limit set
worst single sample: 3.8 µg/L | 10/12 | SYR4 | 2013–2019 |
| Chloroform | 5.21 µg/L No EPA limit set
worst single sample: 5.3 µg/L | 10/13 | SYR4 | 2013–2019 |
| TTHM | 11.2475 µg/L 14% of the EPA limit 80 µg/L
worst single sample: 12.35 µg/L | 8/8 | SYR4 | 2013–2019 |
| Barium | 110.7 µg/L 5.5% of the EPA limit 2000 µg/L
worst single sample: 120 µg/L | 7/7 | SYR4 | 2014–2017 |
| Dibromochloromethane | 2.49 µg/L No EPA limit set
worst single sample: 2.7 µg/L | 7/11 | SYR4 | 2013–2019 |
| Total Haloacetic Acids (HAA5) | 1.46 µg/L 2.4% of the EPA limit 60 µg/L
worst single sample: 1.63 µg/L | 6/8 | SYR4 | 2013–2019 |
| Dibromoacetic Acid | 0.2375 µg/L No EPA limit set
worst single sample: 0.2400 µg/L | 2/8 | SYR4 | 2013–2019 |
| Dichloroacetic Acid | 0.5045 µg/L No EPA limit set
worst single sample: 0.5200 µg/L | 2/8 | SYR4 | 2013–2019 |
| Nitrate-Nitrite | 148 µg/L 1.5% of the EPA limit 10000 µg/L
worst single sample: 150 µg/L | 2/5 | SYR4 | 2014–2017 |
| Trichloroacetic Acid | 0.8160 µg/L No EPA limit set
worst single sample: 0.8300 µg/L | 2/8 | SYR4 | 2013–2019 |
| Arsenic | 1.2 µg/L 12% of the EPA limit 10 µg/L | 1/7 | SYR4 | 2014–2017 |
| Bromoform | 0.8700 µg/L No EPA limit set | 1/10 | SYR4 | 2013–2019 |
55 contaminants tested, none detected
Utility contact
Frequently asked questions about Pewaukee Village Waterworks
Is Pewaukee Village Waterworks tap water safe to drink?
EPA monitoring detected 20 contaminants in Pewaukee Village Waterworks's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Pewaukee Village Waterworks's water?
EPA monitoring detected Copper, Lead, Fluoride, Combined Radium (-226 And -228), Gross Alpha, Excl. Radon And U, and others. The full list with the level and data source for each is above.
How many people does Pewaukee Village Waterworks serve?
Pewaukee Village Waterworks reports serving 8,166 people in Wisconsin, per its EPA record.
Has Pewaukee Village Waterworks had any water quality violations?
The EPA has 183 violations on file for Pewaukee Village Waterworks, of which 131 are health-based (a contaminant limit or required treatment was breached) and 12 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.