Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2014-08-01 → 2014-08-31 |
| MCL | Health-based | Resolved | 2014-08-01 → 2014-08-31 |
| MCL | Health-based | Resolved | 2014-08-01 → 2014-08-31 |
| MCL | Health-based | Resolved | 2014-08-01 → 2014-08-31 |
| MCL | Health-based | Resolved | 2014-08-01 → 2014-08-31 |
| MCL | Health-based | Resolved | 1996-06-01 → 1996-06-30 |
| MCL | Health-based | Resolved | 1996-06-01 → 1996-06-30 |
| MCL | Health-based | Resolved | 1996-06-01 → 1996-06-30 |
| MCL | Health-based | Resolved | 1996-06-01 → 1996-06-30 |
| MR | Monitoring | Resolved | 2021-02-01 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Nitrate | 5600 µg/L 56% of the EPA limit 10000 µg/L
worst single sample: 6560 µg/L | 176/176 | SYR4 | 2012–2019 |
| Fluoride | 1090 µg/L 27% of the EPA limit 4000 µg/L
worst single sample: 1230 µg/L | 105/206 | SYR4 | 2012–2019 |
| Copper | 1825 µg/L 140% of the EPA limit, at the 95th percentile of samples — 1300 µg/L
worst single sample: 5400 µg/L | 66/66 | SYR4 | 2014–2017 |
| Lead | 18.75 µg/L 125% of the EPA limit, at the 95th percentile of samples — 15 µg/L
worst single sample: 230 µg/L | 66/66 | SYR4 | 2014–2017 |
| Dibromochloromethane | 4.175 µg/L No EPA limit set
worst single sample: 4.4 µg/L | 26/36 | SYR4 | 2013–2019 |
| Bromoform | 3.785 µg/L No EPA limit set
worst single sample: 4.3 µg/L | 24/35 | SYR4 | 2013–2019 |
| Lead | 0.0042 mg/L 28% of the EPA limit 0.0150 mg/L | 20/20 | LCR | 2025 |
| Bromodichloromethane | 1.95 µg/L No EPA limit set
worst single sample: 2.4 µg/L | 19/35 | SYR4 | 2013–2019 |
| Barium | 88.8 µg/L 4.4% of the EPA limit 2000 µg/L
worst single sample: 93 µg/L | 15/15 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 5535 µg/L 55% of the EPA limit 10000 µg/L
worst single sample: 5600 µg/L | 14/14 | SYR4 | 2012–2019 |
| Combined Radium (-226 And -228) | 1.86 pCi/L 37% of the EPA limit 5 pCi/L
worst single sample: 2 pCi/L | 5/5 | SYR4 | 2014 |
| Combined Uranium | 0.8260 µg/L 2.8% of the EPA limit 30 µg/L
worst single sample: 0.9100 µg/L | 5/5 | SYR4 | 2014 |
| Dibromoacetic Acid | 1.876 µg/L No EPA limit set
worst single sample: 2.1 µg/L | 5/7 | SYR4 | 2013–2019 |
| TTHM | 6.68 µg/L 8.4% of the EPA limit 80 µg/L
worst single sample: 7.5 µg/L | 5/7 | SYR4 | 2013–2019 |
| Total Haloacetic Acids (HAA5) | 2.082 µg/L 3.5% of the EPA limit 60 µg/L
worst single sample: 2.1 µg/L | 5/7 | SYR4 | 2013–2019 |
| Chromium | 1.38 µg/L 1.4% of the EPA limit 100 µg/L
worst single sample: 1.4 µg/L | 3/15 | SYR4 | 2012–2019 |
| Gross Alpha, Excl. Radon And U | 0.7390 pCi/L 4.9% of the EPA limit 15 pCi/L
worst single sample: 0.7533 pCi/L | 3/3 | SYR4 | 2014 |
| Dichloroacetic Acid | 0.8270 µg/L No EPA limit set
worst single sample: 0.8500 µg/L | 2/7 | SYR4 | 2013–2019 |
| Trichloroethylene | 7.26 µg/L 145% of the EPA limit, at the 95th percentile of samples — 5 µg/L
worst single sample: 7.3 µg/L | 2/49 | SYR4 | 2012–2019 |
| Nitrite | 20 µg/L 2% of the EPA limit 1000 µg/L | 1/14 | SYR4 | 2012–2019 |
60 contaminants tested, none detected
Utility contact
Frequently asked questions about Hartland Waterworks
Is Hartland Waterworks tap water safe to drink?
EPA monitoring detected 20 contaminants in Hartland Waterworks's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Hartland Waterworks's water?
EPA monitoring detected Nitrate, Fluoride, Copper, Lead, Dibromochloromethane, and others. The full list with the level and data source for each is above.
How many people does Hartland Waterworks serve?
Hartland Waterworks reports serving 9,212 people in Wisconsin, per its EPA record.
Has Hartland Waterworks had any water quality violations?
The EPA has 16 violations on file for Hartland Waterworks, of which 9 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.