Tap water quality report

West Bend Waterworks

EPA monitoring tested this supplier for 75 contaminants and detected 21. A detection doesn't automatically mean the water is unsafe — the level and EPA source for each is below.

75
contaminants tested
21
detected
31,752
people served
22
health-based violations
Water source
Ground water
Ownership
Local government
Counties served
Washington

Compliance record

Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.

22
health-based violations
273
violations on file
0
still open
ViolationTypeStatusPeriod
MCL Health-based Resolved 2002-07-01 → 2002-07-31
MCL Health-based Resolved 2002-07-01 → 2002-07-31
MCL Health-based Resolved 2002-07-01 → 2002-07-31
MCL Health-based Resolved 2002-07-01 → 2002-07-31
MCL Health-based Resolved 2002-07-01 → 2002-07-31
TT Health-based Resolved 2002-07-01
MCL Health-based Resolved 2001-08-01 → 2001-08-31
MCL Health-based Resolved 2001-08-01 → 2001-08-31
MCL Health-based Resolved 2001-08-01 → 2001-08-31
MCL Health-based Resolved 2001-08-01 → 2001-08-31

Other contaminants detected

Each bar shows the measured level as a share of the EPA limit: green is well under, amber is close to it, red is over. For lead and copper the limit applies to exactly the 90th-percentile figure shown, so red there means a real exceedance. For everything else the limit applies to a running annual average while the figure is the 95th percentile of this system's samples — over 100% is worth reading, but is not by itself a violation. Where a single sample came in higher than that percentile, it is noted under the bar. Formal violations are listed separately.
ContaminantLevel vs EPA limitDetection rateSourcePeriod
Copper
1600 µg/L 123%
of the EPA limit, at the 95th percentile of samples — 1300 µg/L
worst single sample: 6100 µg/L
120/120 SYR4 2012–2017
Lead
13 µg/L 87%
of the EPA limit 15 µg/L
worst single sample: 150 µg/L
117/120 SYR4 2012–2017
Fluoride
717.2 µg/L 18%
of the EPA limit 4000 µg/L
worst single sample: 796 µg/L
105/208 SYR4 2012–2019
Nitrate
2935 µg/L 29%
of the EPA limit 10000 µg/L
worst single sample: 3400 µg/L
74/88 SYR4 2012–2019
Dibromochloromethane
6.21 µg/L
No EPA limit set
worst single sample: 7.1 µg/L
34/124 SYR4 2012–2019
Bromodichloromethane
8.235 µg/L
No EPA limit set
worst single sample: 8.8 µg/L
32/124 SYR4 2012–2019
Chloroform
7.78 µg/L
No EPA limit set
worst single sample: 9.4 µg/L
28/124 SYR4 2012–2019
Lead
0.0072 mg/L 48%
of the EPA limit 0.0150 mg/L
27/27 LCR 2025
TTHM
24.5 µg/L 31%
of the EPA limit 80 µg/L
worst single sample: 25.1 µg/L
25/25 SYR4 2012–2019
Bromoform
2.89 µg/L
No EPA limit set
worst single sample: 3.1 µg/L
22/124 SYR4 2012–2019
Trichloroethylene
3.4 µg/L 68%
of the EPA limit 5 µg/L
21/101 SYR4 2012–2019
Total Haloacetic Acids (HAA5)
3.535 µg/L 5.9%
of the EPA limit 60 µg/L
worst single sample: 3.85 µg/L
19/20 SYR4 2012–2019
Dibromoacetic Acid
1.36 µg/L
No EPA limit set
worst single sample: 1.6 µg/L
17/20 SYR4 2012–2019
Barium
173.5 µg/L 8.7%
of the EPA limit 2000 µg/L
worst single sample: 180 µg/L
14/14 SYR4 2014–2017
cis-1,2-Dichloroethylene
0.8325 µg/L 1.2%
of the EPA limit 70 µg/L
worst single sample: 0.8600 µg/L
12/100 SYR4 2012–2019
Nitrate-Nitrite
3050 µg/L 31%
of the EPA limit 10000 µg/L
worst single sample: 3400 µg/L
11/12 SYR4 2014–2017
Trichloroacetic Acid
1.3 µg/L
No EPA limit set
11/20 SYR4 2012–2019
Dichloroacetic Acid
1.725 µg/L
No EPA limit set
worst single sample: 1.9 µg/L
8/20 SYR4 2012–2019
Combined Radium (-226 And -228)
1.5 pCi/L 30%
of the EPA limit 5 pCi/L
7/7 SYR4 2014
Arsenic
2.52 µg/L 25%
of the EPA limit 10 µg/L
worst single sample: 2.7 µg/L
4/14 SYR4 2014–2017
Thallium, Total
0.5270 µg/L 26%
of the EPA limit 2 µg/L
worst single sample: 0.5300 µg/L
2/14 SYR4 2014–2017
54 contaminants tested, none detected
1,1,1-Trichloroethane1,1,2-Trichloroethane1,1-Dichloroethylene1,2,4-Trichlorobenzene1,2-DIBROMO-3-CHLOROPROPANE1,2-Dichloroethane1,2-Dichloropropane2,4,5-TP2,4-DAntimony, TotalAtrazineBhc-GammaBenzeneBeryllium, TotalChlorobenzeneCadmiumCarbofuranCarbon TetrachlorideChlordaneChromiumDichloromethaneDalaponDinosebDiquatEthylene DibromideEndothallEndrinEthylbenzeneGlyphosateHexachlorobenzeneHeptachlorHeptachlor EpoxideHexachlorocyclopentadieneLassoMercuryMethoxychlorMonobromoacetic AcidMonochloroacetic AcidNitriteOxamylPentachlorophenolPicloramSeleniumSimazineStyreneTetrachloroethyleneTolueneTotal Polychlorinated Biphenyls (PCB)ToxapheneVinyl ChlorideXylenes, TotalO-DichlorobenzeneP-Dichlorobenzenetrans-1,2-Dichloroethylene

Frequently asked questions about West Bend Waterworks

Is West Bend Waterworks tap water safe to drink?

EPA monitoring detected 21 contaminants in West Bend Waterworks's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.

What contaminants were detected in West Bend Waterworks's water?

EPA monitoring detected Copper, Lead, Fluoride, Nitrate, Dibromochloromethane, and others. The full list with the level and data source for each is above.

How many people does West Bend Waterworks serve?

West Bend Waterworks reports serving 31,752 people, per its EPA record.

Has West Bend Waterworks had any water quality violations?

The EPA has 273 violations on file for West Bend Waterworks, of which 22 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.

Where does this data come from?

Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.