Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| TT | Health-based | Resolved | 2015-01-01 |
| TT | Health-based | Resolved | 2015-01-01 |
| TT | Health-based | Resolved | 2005-01-01 |
| TT | Health-based | Resolved | 2005-01-01 |
| MCL | Health-based | Resolved | 2000-08-01 → 2000-08-31 |
| MCL | Health-based | Resolved | 2000-08-01 → 2000-08-31 |
| MCL | Health-based | Resolved | 2000-08-01 → 2000-08-31 |
| TT | Health-based | Resolved | 1993-01-01 → 1994-08-03 |
| Other | Monitoring | Unaddressed | 2015-01-01 |
| Other | Monitoring | Unaddressed | 2015-01-01 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Copper | 350 µg/L 27% of the EPA limit 1300 µg/L
worst single sample: 2100 µg/L | 496/497 | SYR4 | 2014–2019 |
| Lead | 12.8 µg/L 85% of the EPA limit 15 µg/L
worst single sample: 620 µg/L | 485/497 | SYR4 | 2014–2019 |
| Fluoride | 760.8 µg/L 19% of the EPA limit 4000 µg/L
worst single sample: 800 µg/L | 100/196 | SYR4 | 2012–2019 |
| Bromodichloromethane | 15 µg/L No EPA limit set
worst single sample: 17 µg/L | 94/94 | SYR4 | 2012–2019 |
| Chloroform | 27 µg/L No EPA limit set
worst single sample: 36 µg/L | 94/94 | SYR4 | 2012–2019 |
| Dibromochloromethane | 7.07 µg/L No EPA limit set
worst single sample: 7.4 µg/L | 94/94 | SYR4 | 2012–2019 |
| Dibromoacetic Acid | 2.045 µg/L No EPA limit set
worst single sample: 2.2 µg/L | 92/92 | SYR4 | 2012–2019 |
| Dichloroacetic Acid | 14 µg/L No EPA limit set
worst single sample: 17 µg/L | 92/92 | SYR4 | 2012–2019 |
| TTHM | 48.4525 µg/L 61% of the EPA limit 80 µg/L
worst single sample: 59.9 µg/L | 92/92 | SYR4 | 2012–2019 |
| Total Haloacetic Acids (HAA5) | 25.87 µg/L 43% of the EPA limit 60 µg/L
worst single sample: 31.08 µg/L | 92/92 | SYR4 | 2012–2019 |
| Trichloroacetic Acid | 9.09 µg/L No EPA limit set
worst single sample: 10 µg/L | 92/92 | SYR4 | 2012–2019 |
| Monobromoacetic Acid | 1.345 µg/L No EPA limit set
worst single sample: 1.4 µg/L | 52/92 | SYR4 | 2012–2019 |
| Lead | 0.0033 mg/L 22% of the EPA limit 0.0150 mg/L | 30/30 | LCR | 2025 |
| Bromoform | 0.9325 µg/L No EPA limit set
worst single sample: 0.9600 µg/L | 28/94 | SYR4 | 2012–2019 |
| Monochloroacetic Acid | 2.25 µg/L No EPA limit set
worst single sample: 2.5 µg/L | 11/92 | SYR4 | 2012–2019 |
| Nitrate | 550 µg/L 5.5% of the EPA limit 10000 µg/L | 8/8 | SYR4 | 2012–2016 |
| Barium | 21.7 µg/L 1.1% of the EPA limit 2000 µg/L
worst single sample: 22 µg/L | 4/4 | SYR4 | 2014–2019 |
| Nitrate-Nitrite | 391 µg/L 3.9% of the EPA limit 10000 µg/L
worst single sample: 400 µg/L | 4/4 | SYR4 | 2014–2019 |
| Combined Radium (-226 And -228) | 0.9500 pCi/L 19% of the EPA limit 5 pCi/L | 1/1 | SYR4 | 2014 |
59 contaminants tested, none detected
Utility contact
Frequently asked questions about Racine Waterworks
Is Racine Waterworks tap water safe to drink?
EPA monitoring detected 19 contaminants in Racine Waterworks's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Racine Waterworks's water?
EPA monitoring detected Copper, Lead, Fluoride, Bromodichloromethane, Chloroform, and others. The full list with the level and data source for each is above.
How many people does Racine Waterworks serve?
Racine Waterworks reports serving 105,100 people in Wisconsin, per its EPA record.
Has Racine Waterworks had any water quality violations?
The EPA has 60 violations on file for Racine Waterworks, of which 8 are health-based (a contaminant limit or required treatment was breached) and 2 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.