Compliance record
Formal violations the EPA has on file for this supplier. A health-based violation means a contaminant limit or a required treatment was breached; the rest are monitoring or reporting failures — still violations, but not a measured health risk.
| Violation | Type | Status | Period |
|---|---|---|---|
| MCL | Health-based | Resolved | 2014-07-01 → 2014-07-31 |
| MCL | Health-based | Resolved | 2014-07-01 → 2014-07-31 |
| MCL | Health-based | Resolved | 2014-07-01 → 2014-07-31 |
| MCL | Health-based | Resolved | 2014-07-01 → 2014-07-31 |
| MCL | Health-based | Resolved | 2010-09-01 → 2010-09-30 |
| MCL | Health-based | Resolved | 2010-09-01 → 2010-09-30 |
| MCL | Health-based | Resolved | 2010-09-01 → 2010-09-30 |
| MCL | Health-based | Resolved | 2010-09-01 → 2010-09-30 |
| MCL | Health-based | Resolved | 2010-09-01 → 2010-09-30 |
| MCL | Health-based | Resolved | 1998-07-01 → 1998-07-31 |
Other contaminants detected
| Contaminant | Level vs EPA limit | Detection rate | Source | Period |
|---|---|---|---|---|
| Fluoride | 1090 µg/L 27% of the EPA limit 4000 µg/L
worst single sample: 1390 µg/L | 106/202 | SYR4 | 2012–2019 |
| Copper | 181 µg/L 14% of the EPA limit 1300 µg/L
worst single sample: 560 µg/L | 60/60 | SYR4 | 2014–2017 |
| Lead | 14 µg/L 93% of the EPA limit 15 µg/L
worst single sample: 33 µg/L | 57/60 | SYR4 | 2014–2017 |
| Combined Radium (-226 And -228) | 8.605 pCi/L 172% of the EPA limit, at the 95th percentile of samples — 5 pCi/L
worst single sample: 9.45 pCi/L | 34/34 | SYR4 | 2012–2017 |
| Nitrate | 545.5 µg/L 5.5% of the EPA limit 10000 µg/L
worst single sample: 640 µg/L | 30/60 | SYR4 | 2012–2019 |
| Lead | 0.0047 mg/L 31% of the EPA limit 0.0150 mg/L | 16/16 | LCR | 2023 |
| Gross Alpha, Excl. Radon And U | 10.7 pCi/L 71% of the EPA limit 15 pCi/L
worst single sample: 14.6 pCi/L | 13/13 | SYR4 | 2013–2017 |
| TTHM | 5.79 µg/L 7.2% of the EPA limit 80 µg/L
worst single sample: 6.03 µg/L | 13/15 | SYR4 | 2012–2019 |
| Chloroform | 4.445 µg/L No EPA limit set
worst single sample: 4.5 µg/L | 12/41 | SYR4 | 2012–2019 |
| Barium | 102.55 µg/L 5.1% of the EPA limit 2000 µg/L
worst single sample: 130 µg/L | 10/10 | SYR4 | 2014–2017 |
| Total Haloacetic Acids (HAA5) | 0.7066 µg/L 1.2% of the EPA limit 60 µg/L
worst single sample: 0.8070 µg/L | 9/15 | SYR4 | 2012–2019 |
| Dibromochloromethane | 1.34 µg/L No EPA limit set
worst single sample: 1.4 µg/L | 7/41 | SYR4 | 2012–2019 |
| Nitrate-Nitrite | 229 µg/L 2.3% of the EPA limit 10000 µg/L
worst single sample: 250 µg/L | 7/10 | SYR4 | 2014–2017 |
| Bromodichloromethane | 1.475 µg/L No EPA limit set
worst single sample: 1.5 µg/L | 6/41 | SYR4 | 2012–2019 |
| Combined Uranium | 1.19 µg/L 4% of the EPA limit 30 µg/L
worst single sample: 1.2 µg/L | 6/6 | SYR4 | 2013–2017 |
| Dichloroacetic Acid | 0.4870 µg/L No EPA limit set
worst single sample: 0.5000 µg/L | 3/15 | SYR4 | 2012–2019 |
| Bromoform | 0.7635 µg/L No EPA limit set
worst single sample: 0.7700 µg/L | 2/41 | SYR4 | 2012–2019 |
| Arsenic | 2.3 µg/L 23% of the EPA limit 10 µg/L | 1/10 | SYR4 | 2014–2017 |
| Toluene | 3.9 µg/L 0.4% of the EPA limit 1000 µg/L | 1/27 | SYR4 | 2012–2017 |
| Trichloroacetic Acid | 0.4400 µg/L No EPA limit set | 1/15 | SYR4 | 2012–2019 |
87 contaminants tested, none detected
Utility contact
Frequently asked questions about Monroe Waterworks
Is Monroe Waterworks tap water safe to drink?
EPA monitoring detected 20 contaminants in Monroe Waterworks's water. A detection isn't the same as a violation — most levels are within federal limits. See each level and source above, and the utility's annual Consumer Confidence Report for its official compliance status.
What contaminants were detected in Monroe Waterworks's water?
EPA monitoring detected Fluoride, Copper, Lead, Combined Radium (-226 And -228), Nitrate, and others. The full list with the level and data source for each is above.
How many people does Monroe Waterworks serve?
Monroe Waterworks reports serving 10,780 people in Wisconsin, per its EPA record.
Has Monroe Waterworks had any water quality violations?
The EPA has 29 violations on file for Monroe Waterworks, of which 19 are health-based (a contaminant limit or required treatment was breached) and 0 remain open. The rest are monitoring or reporting failures.
Where does this data come from?
Every figure is official EPA drinking-water monitoring — the Lead & Copper Rule, the UCMR-5 nationwide testing program, and the EPA Six-Year Review — not our own testing. Each number is labelled with its source and period.